• Title/Summary/Keyword: Maze door

Search Result 2, Processing Time 0.018 seconds

Derivation of a Verification Formula for the Dose Rate Contributing to the Maze Door of the 6 MV Treatment Room (6 MV 치료실의 미로 도어에 기여하는 선량률의 검증식 유도)

  • Park, Cheol Seo;Kim, Jong Eon;Kang, Eun Bo
    • Journal of the Korean Society of Radiology
    • /
    • v.15 no.1
    • /
    • pp.85-91
    • /
    • 2021
  • The purpose of this study is to derive an equation to verify the accuracy of the dose rate for each component calculated at the measurement point outside the maze door when designing the maze door of 6 MV X-ray beam. Based on the component-specific dose rate calculation formula for the measurement point outside the maze door described in NCRP Report 151 and IAEA Safety Report Series 47, the dose rate calculation formula for each component when applying the values of the drawing-based parameters and the dose rate calculation formula for each component when applying the values of conservative parameters are derived. From the two dose rate calculation formulas for each component, the dose rate verification formula for each component at the measurement point outside the maze door was derived. The resulting dose rate verification formula for each component at the measurement point outside the maze door can be compared and analyzed whether the dose rate for each component at the measurement point outside the maze door calculated by the designer falls within the range of the dose rate obtained from the derived dose rate verification formula for each component. This verification formula is considered to be practically useful in verifying the accuracy of the dose rate for each component calculated by the designer.

Simple Calculation Method as a Supplementary Radiation Safety Assessment for Facility with Radiation Generator

  • Kim, Sang-Tae
    • International Journal of Contents
    • /
    • v.14 no.4
    • /
    • pp.65-69
    • /
    • 2018
  • The objective of this study was to conduct a radiation shielding analysis for the facility equipped with radiation generator. The analysis was carried out in two aspects. First, from the aspect of the effect caused by primary and leakage radiation. Second, effect of scattered radiation was evaluated by applying a simple calculation method based on a scattering rate concept since effect of scattered radiation is significantly important at maze entrance of the radiation facility. The calculated results obtained using the simple method were compared to the results calculated using Geant4 code and the measured values. The results calculated by the suggested method indicate that slight error exists in a radiation shielding analysis done at the maze entrance comparing to other two results, while the results evaluated at the outside of the maze entrance door are relatively consistent with other values.