• 제목/요약/키워드: Looped collection circuit

검색결과 2건 처리시간 0.019초

환상형 분산전원 단지 보호를 위한 전압제어 과전류 계전기 (Voltage-controlled Over-current Relay for Loop-connected Distributed Generators)

  • 김태희;강상희
    • 전기학회논문지
    • /
    • 제65권12호
    • /
    • pp.1979-1985
    • /
    • 2016
  • A protection algorithm using a voltage-controlled overcurrent element for a looped collection circuit in a wind farm is suggested in this paper. Because the proposed algorithm uses voltage relaying signals as well as current relaying signals, any fault in the looped collection circuit can be cleared by voltage-controlled overcurrent relays located at the two adjacent relaying points, the nearest place in each direction from the fault point. The algorithm can also distinguish the external faults which occur at the outside of a wind farm from the internal faults. It means that the proposed algorithm can provide the proper ability of protection coordination to the relays in the looped collection circuits of a large wind farm. The performance of the proposed algorithm is verified under various fault conditions using PSCAD/EMTDC simulations.

풍력발전단지 보호를 위한 내외부 고장 판별 알고리즘 (A Protection Algorithm Discriminating Between Internal and External Faults for Wind Farms)

  • 권영진;강상희
    • 전기학회논문지
    • /
    • 제56권5호
    • /
    • pp.854-859
    • /
    • 2007
  • A wind farm consists of many wind generator(WG)s therefore, it is generally a complex power system. A wind farm as a distributed generation(DG) affects utility power system. If a conventional protection schemes are applied, it is difficult to detect faults correctly and the schemes can't provide proper coordination in some cases. This paper presents a protection algorithm for a wind farm which consists of a looped collection circuit. Because the proposed algorithm can distinguish between an internal fault and an external fault in a wind farm, The proposed algorithm can disconnect the faulted section in a wind farm. This algorithm is based on an overcurrent protection technique with the change of the ratio of the output current of a generator to the current of the looped line connected to each generator to collect the each generator's power. In addition, operating time of the algorithm is shortened by using the voltage drop at a generator collection point. The performance of the proposed algorithm was verified under various fault conditions using PSCAD/EMTDC simulations.