Analysis of Lightning Current Distribution for Reducing the Conductive EMI in a Structure (도전성 EMI 저감을 위한 구조체의 뇌격전류 분류율 분석)

  • Cho, Sung-Chul;Lee, Tae-Hyung;Eom, Ju-Hong;Lee, Bok-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.1630-1631
    • /
    • 2011
  • Lightning current distribution in a building directly hit was studied by using a scaled steel frame structure model. As the test current source, impulse current with the rise time of 10 ${\mu}s$ and sinusoidal current with the frequency of 30 kHz were used to confirm the validity of test results. The current distributions at both horizontal and vertical pillars were measured by using CT. From the test results, the reduction effect for the conductive EMI was verified and a design method reducing the conductive EMI was proposed.

  • PDF

Lightning impulse characteristics of large-scale ground rods with different length (대형 봉상 접지전극의 길이에 따른 뇌 임펄스 특성)

  • Lee, B.H.;Chang, K.C.;Eom, J.H.;Kim, B.K.;Jeong, D.C.;Kil, H.J.
    • Proceedings of the KIEE Conference
    • /
    • 2003.10a
    • /
    • pp.233-235
    • /
    • 2003
  • To obtain a low ground resistance in high resistivity soil or in insufficient place such as downtown, long vertical ground rods are often used. However, if the lightning current or fault current with high frequency flows into the grounding system, the ground impedance is significantly increased. This paper presents how the impulse current works on the long vertical ground rods with a different length. As a result, it can be estimated what the waveform is composed of and how the GPR is affected by the rate of current change.

  • PDF

Transient Impedance Characteristics of Grounding Rods (봉상접지극의 과도임피던스 특성)

  • 김일권;김점식;송재용;길경석
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2000.10a
    • /
    • pp.568-572
    • /
    • 2000
  • This paper describes the experimental results of a transient impedance characteristics of grounding rods to a square pulse and standard lightning impulse current. The test were performed on single grounding rod($\phi$ 10mm, 1m) and triple-grounding rods( $\phi$ 10mm, 1m) of equilateral triangles with 5m spacing. For measurements of transient impedance, a pulse generator which can produce square wave of 30ns rise time and 20U Pulse duration was designed and fabricated. In the experiment, transient impedance of the grounding systems have been investigated from the recorded potential and current waveforms. The results showed that the value of the transient impedance is quite higher than the stationary resistance, and provide useful information for the value of a grounding system considered transient characteristics under a high frequency condition such as lightning stokes and ground-fault.

  • PDF

Characteristics of the Electric Field Waveforms Associated with Lightning Discharges (뇌방전에 의해서 발생하는 전계파형의 특성)

  • Park, Sung-Yeol;Lee, Bok-Hee;Ahn, Chang-Hwan;Jeon, Duk-Kyu
    • Proceedings of the KIEE Conference
    • /
    • 1996.07c
    • /
    • pp.1879-1881
    • /
    • 1996
  • This paper describes the fine structure of electric field waveforms produced by lightning return strokes. The electric field measuring system consists of hemisphere antenna 30 cm in diameter, integrator and data acquisition device. Its frequency bandwidth is from 200 Hz to 1.56 MHz, and the sensitivity is 0.96 mV/V/m. Electric field signals are digitized every 200 ns with the resolution of 12-bit and the length of 5 kilowords, and those are registered by a personal computer. Also data are analyzed by means of the fast Fourier transform (FFT) method.

  • PDF

Development of the Lightning Surge Voltage and Current Counters (뇌써지 전압/전류 카운터의 개발)

  • Kil, K.S.;Chang, S.H.;Lee, B.H.;Lee, Y.K.;Lee, B.K.;Ohk, Y.H.
    • Proceedings of the KIEE Conference
    • /
    • 1996.07c
    • /
    • pp.1882-1884
    • /
    • 1996
  • This paper deals with the lightning surge counter. In order to install the effective surge protective devices, it is important to find the parameters of incident surges. For the purpose of observing the occurrence frequency as a parameter of the amplitude of surge, two type surge counters were designed and fabricated. One is operated by surge currents, and the other is operated by surge voltages. The former consists of current sensor, metal oxide varister (MOV), rectifier, capacitor and electromagnetic counter. The latter consists of rectifier, voltage divider, comparator, photo coupler and counter circuit, and is useful for detecting the surge voltages.

  • PDF

Design and Implementation of Wideband Grounding Impedance Measurement Device using IQ Demodulation Method (IQ 복조 기법을 이용한 광대역 접지 임피던스 측정기의 설계 및 구현)

  • Kim, Young-Jin;Gil, Hyung-Jun;Kim, Sung-Ju;Kim, Jae Hyung
    • Journal of the Korean Society of Safety
    • /
    • v.31 no.6
    • /
    • pp.19-24
    • /
    • 2016
  • One of key parameters on lightning protection system design of electric, information and communication system is grounding impedance. Earth impedance includes numerous information about earthing performance of grounding system. This paper suggests grounding impedance measuring device which is comprised of wideband current source, voltage and current measuring components. We used IQ Demodulation to measure more accurate phase difference of voltage and current. The range of frequency is up to 1 MHz that is IEEE defined as the range of lightning surge. We compared developed grounding impedance measuring device with existing one to test its performance, and we used grounding system while we implemented measurement and analysing by using fall of potential method IEEE Std.81 proposed.

A Basic Study on the Measurement Induced Voltages due to Lightning Discharges (뇌방전에 의한 유도전압의 측정에 대한 기초적 연구)

  • Lee, Bok-Hee;Cho, Sung-Chul;Eom, Ju-Hong;Lee, Woo-Chul
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.559-564
    • /
    • 2004
  • This paper deals with the device for measuring the time-varying magnetic fields and induced voltages caused by lightning discharges. The two magnetic field measuring systems were designed and made. One consists of the loop-type magnetic field sensor with the active integrator operated by a differential amplifier. The other consists of the loop-type magnetic field sensor and Labview software. The loop-type magnetic field sensor detects the time derivative of the magnetic field being measured, and the signal detected is integrated by the Labview software. As a consequence, from the calibration experiments, the frequency bandwidth of the full measuring system ranges from 400 [Hz] to 1 (MHz) and the response sensitivity are 0.98 (mV/nT) and 22 (mV/nT) for the magnetic field sensor of 2 turns and 6 turns, respectively. Also, the results obtained by the two measuring devices well agreed with each other.

  • PDF

Lightning impulse characteristics of large-scale ground rods (대형 봉상 접지전극의 뇌 임펄스 특성)

  • Lee, B.H.;Chang, K.C.;Lee, D.M.;Jeong, D.C.;Lee, S.C.;Ahn, C.H.;Jeong, Y.K.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1849-1851
    • /
    • 2003
  • To obtain a low ground resistance in high resistivity soil, long vertical ground rods are often used. However, if the lightning current or fault current with high frequency flow into the grounding system, the ground impedance is significantly increased because of the inductive behavior. This paper presents how the impulse current works on the long vertical ground electrodes. The different shape of current was impressed between ground rods and auxiliary electrode by using impulse generator and the ground impedance was calculated from the ground potential rise.

  • PDF

The Electrical and Material Characteristics of the Distribution Facilities Suffered from Industrial Pollution (산업오손에 따른 배전설비 절연물의 전기적 및 재료적 특성)

  • Kim, Chan-Young;Jung, Jong-Man;Lee, Jae-Bong;Chun, Sung-Nam;Kim, Dong-Myung;Song, Il-Keun;Kim, Byung-Suk
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.07a
    • /
    • pp.556-557
    • /
    • 2005
  • The distribution facilities, such as suspension insulator, line post insulator, lightning arrester, COS, used for long periods in the industrial pollution area were investigated. The electrical test and the material analyses were performed on the polluted and non-polluted facilities. The low frequency dry flashover voltage of polluted suspension was decreased about 8% in comparison with non-polluted one. The polluted materials turned out with the iron which came from the foundries. The polluted materials turned out with the iron which came from the foundries. This conductive materials decreased the leakage distance, resulting in reducing of electrical properties.

  • PDF

Frequency Dependent Grounding Impedance As a Function of Soil Resistivity (대지저항률에 따른 접지임피던스의 주파수 의존성)

  • Bae, Sung-Bae;Choi, Jong-Hyuk;Park, Geon-Hun;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.57-60
    • /
    • 2008
  • A design criterion of grounding systems is commonly based on low frequency resistance in Korea. When lightning surges which have high frequency components are injected into the grounding system, the grounding impedance is greatly different from the static grounding resistance. This paper presents the grounding adimittance and phase on the frequency range from 100 [Hz] to 15 [MHz] using water tank simulating the grounding system in different water resistivities. As a result, capacitive effect is dominant over the frequency of 100 [kHz] at the water resistivity of 1,000 [$\Omega$ m]. On the other hand, the inductive characteristics appear at the low water resistivity. Consequently, dependence of grounding impedances on the frequency of injected current is strongly related to resistivity.

  • PDF