Dielectric Characteristics of $SF_6$ gas Stressed by the Oscillating Impulse Voltage in the Non-uniform Electric Fields (불평등전계중에서 진동성 임펄스전압에 대한 $SF_6$가스의 절연특성)

  • Lee, Bok-Hee;Kil, Gyung-Suk;Hwang, Kyo-Jung
    • Proceedings of the KIEE Conference
    • /
    • 1994.11a
    • /
    • pp.284-286
    • /
    • 1994
  • This paper describes the dielectric characteristics of $SF_6$ gas in non-uniform electric filed under lightning under lightning impulse and oscillating impulse voltages. The breakdown voltage-time characteristics and the breakdown voltage-pressure characteristics are measured over a pressure range extending from 0.1 to 0.5 [MPa] fur the coaxial electrode with a needle protrusion. The curvature radius of needle protrusion is 0.3[mm]. Also, the growth of the predischarge is simultaneously observed. As a result the polarity effect is pronounced, and the breakdowns voltage under the oscillating impulse voltage are higher than those under the lightning impulse voltage. It is found that the breakdown mechanism md predischarge phenomena ate closely related with the polarity and waveforms of the testing voltage.

  • PDF

A Study of Lightning Impulse Operating Duty and Temperature Dependence of Series Gap Type Arrester (Series Gap Type 피뢰기의 뇌임펄스 동작책무 및 온도의존성에 관한 연구)

  • Cho, Han-Goo;Yoo, Dae-Hoon
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.22 no.8
    • /
    • pp.659-664
    • /
    • 2009
  • This paper describes lightning impulse operating duty performance and temperature dependence of series gap type for transmission line arresters. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by lightning impulse current. In the discharge withstand test, total energy applied to the ZnO arrester each time is 4/10 ${\mu}s$, 30 kA. and in the operating duty test, the arrester has passed the test if thermal stability is achieved, if the residual voltage measured before and after the test is not changed by more than 5 %, and after the test reveals no evidence of puncture, flashover or cracking of the ZnO block. As a results, the residual voltage was in the range of 17.2${\sim}$20.3 kV and ZnO block bear up against at 2 shot of series impulse current of 30 kA. Also it was so excellent that the mechanical destruction does not occur at the 2 groups of 5 impulses current of 2/20 ${\mu}s$ 10 kA. According to the tests, it is thought that the ZnO arrester shows good stability with impulse current test. and it was found that the ambient temperature is increased resistive leakage current was increased in the range 47.3${\sim}$167.4 ${\mu}A$.

Design Circuit Parameter Estimation of Impulse Generator and its application to 10/350${\mu}s$ Lightning Impulse Current Generator (임펄스 발생기의 회로 설계 파라미터 예측계산과 10/350${\mu}s$ 뇌임펄스 전류발생기 적용)

  • Lee, Jae-Bok;Shenderey, S. V.;Chang, Sug-Hun;Myung, Sung-Ho;Cho, Yuen-Gue
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.10
    • /
    • pp.1822-1828
    • /
    • 2008
  • This paper presents design parameter calculation methodology and its realization to construction for the 10/350${\mu}s$ lightning impulse current generator(ICG) modelled as double exponential function waveform with characteristic parameters ${\alpha},{\beta}$. Matlab internal function, "fzero" was applied to find ${\lambda}={\alpha}/{\beta}$ which is solution of nonlinear equation linearly related with two wave parameter $T_1$ and $T_2$. The calculation results for 10/350${\mu}s$ lightning impulse current show very good accuracy with error less 0.03%. Two type of 10/350${\mu}s$ ICGs based on the calculated design circuit parameters were fabricated by considering the load variation. One is applicable to the MOV based Surge protective device(SPD) for less 15 kA and the other is to test small resistive devices such as spark gap arrester and bonding device with maximum current capability 30 kA. The tested waveforms show error within 10% in comparison with the designed estimation and the waveform tolerance recommended in the IEC 61643-1 and IEC 60060-1.

Effects of Lightning Surges on the Life of ZnO Varistors (뇌서지가 ZnO바리스터에 미치는 영향)

  • Lee, Bong;Lee, Su-Bong;Kang, Sung-Man;Lee, Bok-Hee
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.5
    • /
    • pp.257-262
    • /
    • 2006
  • To evaluate the change in protective levels of zinc oxide (ZnO) varistors after the surge absorption, this paper investigated the effects of the number of injection and amplitude of lightning surges on the life of ZnO varistors for low voltages. Leakage currents flowing through ZnO varistors subjected to the $8/20{\mu}s$ impulse currents under 60 Hz AC voltages were measured. The surge simulator system ECAT that can generate $8/20{\mu}s$ impulse currents with a peak short-circuit of 5 $[kA_p]$ was used. The ZnO varistor leakage current increases with exposure to impulse current, and the number of injection of $8/20{\mu}s$ impulse currents to breakdown was inversely proportional to the amplitude of the test current. Behaviors of ZnO varistor leakage currents were strongly dependent on the number of injection and amplitude of $8/20{\mu}s$ impulse currents. ZnO varistors degrade gradually when subjected to impulse current, and the resistive leakage current flowing through ZnO varistors subjected to the $8/20{\mu}s$ impulse currents under 60 Hz AC voltages was significantly increased after a certain number of injection that is dependent on the amplitude of the test impulse current. As a result, the life of ZnO varistors mainly depends on the amplitude and occurrence frequency of lightning surges.

Dielectric Characteristics of SF6 and Dry-Air Gases under Lightning Impulse Voltage (뇌임펄스전압에 대한 SF6와 dry-air의 절연특성)

  • Li, Feng;Yoo, Yang-Woo;Kim, Dong-Kyu;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.8
    • /
    • pp.142-149
    • /
    • 2010
  • This paper describes dielectric characteristics of $SF_6$ and dry-air gases under lightning impulse voltages in a quasi-uniform electric field. In order to simulate to a quasi-uniform electric field, electric field utilization factor of the used sphere-plane electrode is 71[%]. The gas pressure of $SF_6$ ranges from 0.1 to 0.2[MPa] and that of dry-air ranges from 0.2 to 0.6[MPa]. Electrical breakdown voltages of $SF_6$ and dry-air gases are measured and analyzed as functions of the polarity of lightning impulse voltage and gas pressure. As a result, the electrical breakdown voltage of both gases under the positive lightning impulse voltage is higher than that under the negative one. The electrical breakdown voltage in $SF_6$ is almost higher than 2.67 times compared to dry-air. The results presented in this paper can be used as a useful information to evaluate the capability of alternative insulation gases for $SF_6$ in power distribution equipment with prominent ability against lightning surge.

Degradation properties of ZnO surge arrester due to lightning impulse current (뇌임펄스 전류에 의한 ZnO 배전용 피뢰기의 열화특성)

  • Lee, Seung-Ju;Lee, Bok-Hee;Lee, Su-Bong;Kim, Dong-Soung;Shin, Hee-Kyung;Jung, Dong-Cheol
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.1305-1306
    • /
    • 2008
  • In this work, in order to investigate the effect of lightning impulse currents on ZnO surge arrester. and the deterioration characteristics of ZnO surge arrester, 8/20 [${\mu}s$], 2.5 [kA] impulse currents were applied to the ZnO surge arrester under test. The leakage currents of ZnO surge arrester were measured and ZnO element was analyzed by X-ray photoelectron spectroscopy. As a result, the resistive leakage current of ZnO surge arrester was increased with the injection number of lightning impulse currents.

  • PDF

A Study on the Compensation Method in the Measuring System for Chopped Lightning Impulse (충격전압 재단과 측정을 위한 보상회로에 관한 연구)

  • Kim, Ik-Soo;Kim, Young-Bae;Kim, Jin-Gi;Kim, Min-Kyu
    • Proceedings of the KIEE Conference
    • /
    • 1996.07c
    • /
    • pp.1895-1897
    • /
    • 1996
  • Lightning impulse voltage is essential to evaluate the insulation performance of electric power apparatus. Recently international standard (IEC-60) on high voltage measurement techniques are being revised. In the draft of this standard, a new calibration method is introduced and the accuracy of most industrial measuring systems is maintained by means of comparison test against the reference measuring systems. Comparison tests of dividers for chopped lightning impulse measurement were rallied out by KERI. The 700kV shielded resisitive divider with and without compensation element were done comparison test with 300kV PTB divider which have the similar charateristics as that were circulated among the laboratories. This paper reports on the calculation results of response charateristics obtained by EMTP and the comparison test results with chopped lightning impulse voltages from 150kV to 250kV. It is demonstrated that KERI are capable of realizing the idea in the revision of the IEC standand, that is, to establish traceability.

  • PDF

Effects of Soil Discharges on the Impulsive Ground Impedance of Ground Rod with Needles (침상 접지봉의 임펄스접지임피던스에 미치는 지중방전의 영향)

  • Yoo, Yang-Woo;Cho, Sung-Chul;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.5
    • /
    • pp.98-105
    • /
    • 2014
  • Soil discharges near the ground rod play an important role to reduce the ground potential rise and the ground impedance and to help the fault current to spread into the earth. This paper presents the effects of soil discharges on the transient and conventional ground impedances when the lightning impulse voltage was applied to a ground rod with radial needles. The current-voltage (I-V)curves and transient ground impedance curves were calculated based on the measured current and potential traces. Soil discharge behaviors related to I-V curves and transient ground impedance curves were analyzed as a function of the magnitude of lightning impulse voltages. As a result, the soil discharges occurred near the ground electrode contribute to the reduction of conventional ground impedance and limits the ground potential rise effectively under lightning impulse voltages.

Safety Analysis for Passengers of Composite Car-body against Lightning Strikes (복합차체의 낙뢰에 대한 인체 안전성 분석)

  • Kill, Gyung-Suk;Park, Dae-Won;Kim, Sung-Wook;Park, Chan-Yong;Cho, Young-Jin
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.22 no.6
    • /
    • pp.526-531
    • /
    • 2009
  • In this paper, the safety for passengers of composite car-body against lightning strikes was analyzed by the application of an impulse generator which can produce impulse current up to 50 kA with 8/$20{\mu}s$ waveform. Potential difference on inside surface of the car-body was measured as a safety parameter for the passengers against lightning strikes. The potential difference between 20 em distant was 175 V at 37.67 kA, and it corresponds to 875 V between 1 m distant. The amount of charge flowing a passenger at 100 kA impulse current can be estimated to $0.31\;mA{\cdot}s$. This is much less than the limit amount of charge for human body, $30\;mA{\cdot}s$ which is presented by Koeppen and Osypka.

Development of ZnO Varistor for Distribution Surge Arrester (18kV, 5kA) (배전급 피뢰기(18kV, 5kA)용 ZnO 바리스터 소자 개발)

  • 박춘현;윤관준;조이곤;정세영;서형권
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.212-216
    • /
    • 2000
  • ZnO varistors for distribution surge arrester (18kV, 5kA) were developed and tested microstructure and electrical characteristics. Microstructure of ZnO varistor was consisted of ZnO grain, spinel phase and Bi-rich phase. Average grain size of ZnO varistor was $\mu\textrm{m}$ Reference voltage and lightning impulse residual voltage of ZnO varistor exhibited a good haracteristics above 5.5kV and below 11.56kV, respectively. Consequently, discharge capacity which is the most important characteristics of ZnO varistor for surge arrester exhibited excellent properties above 70kA at twice high-current impulse test. Moreover, variation rate of reference voltage and lightning impulse residual voltage showed below 5% and 2% after high-current impulse test, respectively. Leakage current and watt loss of ZnO varistor will not increase during accelerated aging test at stress condition, such as 3.213kV/$115^{\circ}C$/1000h.

  • PDF