• 제목/요약/키워드: Leakage safety

검색결과 845건 처리시간 0.023초

데이터 처리 및 무선통신기능을 갖는 회로차단기 개발 연구 (Development of the Circuit Breaker with Data Processing Function and Wireless-communication Function)

  • 김기현;이상익;신성수;배석명;주남규
    • 전기학회논문지
    • /
    • 제60권8호
    • /
    • pp.1617-1621
    • /
    • 2011
  • In this paper, in order to reduce the electrical disaster such as electrical fire at traditional markets, we need to develop the circuit breaker which is able to monitor the power status of electrical equipments. Therefore, for solving the those problems, we developed the detection censor(ZCT, CT) and equipment of data analysis and transmission. The detection censor and equipment is able to monitor the electrical equipments condition(over current, leakage current, arc, etc.). We constructed Test-Bed for testing reliability of the circuit breaker and obtained certification. And we tested the over current, leakage current and arc under the normal condition. This paper will be used to the data for development an cabinet panel which is able to monitor the actual loads.

잡음영향의 저감을 위한 두 디지털 필터들의 사용에 의한 DFT 기반의 계통주파수 추정 (DFT-based Power System Frequency Estimation using Two Digital Filters for Noise Effect Reduction)

  • 황진권
    • 전기학회논문지
    • /
    • 제62권7호
    • /
    • pp.891-897
    • /
    • 2013
  • The power system frequency plays an important role in monitoring and controlling the power system. The frequency can be measured through discrete Fourier transform (DFT) coefficients of its positive fundamental frequency. The accuracy of the frequency estimate is severely affected by noise in the power system signal and the leakage effect of the negative fundamental frequency in DFT. This paper proposes a DFT-based frequency estimation algorithm to cope with the noise as well as the leakage effect. In this algorithm, two suitable digital filters are introduced to reduce efficiently frequency estimate error due to the noise. These filters are designed to use a digital bandpass filter and a second-degree integrator. The effectiveness of the proposed algorithm in reduction of frequency estimate error is verified through simulations on noise, harmonics and frequency deviation.

인공녹화 기반 콘크리트 구조체의 안전성 확보를 위한 옥상녹화 방수층의 내근성 평가 (Test for Root Penetration Resistance for Waterproofing Layer proper to assure Structural Safety on the Concrete)

  • 권시원;선윤숙;곽규성;오상근
    • 한국콘크리트학회:학술대회논문집
    • /
    • 한국콘크리트학회 2006년도 추계 학술발표회 논문집
    • /
    • pp.873-876
    • /
    • 2006
  • At the green roof on the concrete structure, root penetration can be the most problem to water leakage. Root occur cracks due to penetrate to concrete which have porous organization by itself. Crack on the concrete structure would be constantly shrinks and expands, it occur to water leakage and decrease durability of concrete structure. Therefore, in this paper, the result of the root penetration test for waterproofing which protect concrete structure from the water leakage or other environment conditions would be apply to understand the reason of root penetration.

  • PDF

격납건물 ILRT 본시험시간이 시험에 미치는 영향에 관한 연구 (A Study on the Effect of Integrated Leakage Rate Testing of Containment Vessel due to the Type A Testing Time)

  • 김창수;문용식
    • 한국압력기기공학회 논문집
    • /
    • 제8권3호
    • /
    • pp.1-6
    • /
    • 2012
  • The containment Integrated Leakage Rate Testing(ILRT) of nuclear power plants in Korea is performed in accordance with NSSC(Nuclear Safety and Security Commission) code 2012-16 and ANSI/ANS 56.8-1994. Nuclear power plants in Korea and the United States are to apply same test criteria, ANSI/ANS 56.8-1994, except type A testing time. NPPs in Korea apply 24 hours according to NSSC code 2012-16, but NPPs in United States apply 8 hours according to 10CFR50 App. J for type A test. So, there are many difficulties in order to perform ILRT in Korea. In this study, I review the impact on the ILRT results and the effect of ILRT due to type A testing time. The future, we will continue study to enhance the test reliability and improve these problems.

원전 내 배관의 증기 누설 사고 시 누설 탐지 포집/이송 시스템 예비 해석 (Preliminary Analysis of a Sampling and Transportation System for Leak Detection during Steam Leak Accident of a Pipe in Nuclear Power Plants)

  • 최대경;최청열;권태순;어동진
    • 한국압력기기공학회 논문집
    • /
    • 제16권2호
    • /
    • pp.25-34
    • /
    • 2020
  • As leakage in nuclear power plants could cause a variety of problems, it is very critical to monitor leakage from the safety point of view. Accordingly, a new type of leak detection system is currently being developed and flow characteristics of the sampling and transportation system are investigated by using numerical analysis as a part of the development process in this study. The results showed that the steam mass fraction varied according to the effect of the gap between the insulation and piping component, transportation velocity, and material properties of porous media during the sampling and transportation process. The results of this study should be useful for understanding flow characteristics of the sampling and transportation system and its design and application.

LNG 저장탱크용 작업안전 환경 센싱 모듈의 특성연구 (A Study on the Characteristics of the Work Safety Environment Sensing Module for LNG Storage Tanks)

  • 박병진;김민성
    • 한국멀티미디어학회논문지
    • /
    • 제25권2호
    • /
    • pp.189-196
    • /
    • 2022
  • We have developed an embedded based environment sensing module with high-resolution temperature, humidity and gas sensors to detect gas leakage under the condition of LNG injection. The developed sensing module have linearity with gas concentration. We have confirmed the developed sensing module could detect LNG gas concentration of 5 cmol/mol and 15 cmol/mol, which are gas concentration at risk of explosion. The response time of the developed module was fast within 8 seconds. Therefore it can be used to detect LNG gas leakage.

수상 태양광 발전설비 계통 연계 케이블 손상시 감전 위험에 관한 연구 (A Study on Risk of Electric Shock from Damaged Grid Connection Cable in Floating Photovoltaic System)

  • 송영상;전태현
    • 조명전기설비학회논문지
    • /
    • 제28권9호
    • /
    • pp.14-19
    • /
    • 2014
  • Recently, many renewable energy generating businesses are ongoing progress due to the introduction of the RPS(Renewable Portfolio Standards) as well as the needs of environmentally friendly energy resources. Researches on photovoltaic system are actively being processed since the photovoltaic system is relatively easy to install and becomes commercialized in many domestic application areas. Furthermore, the floating photovoltaic system is likely to be installed more actively since the conventional photovoltaic system requires relatively large areas of land. Also, the floating photovoltaic system is more efficient than photovoltaic system installed in land due to the operation in lower temperature. However, safety problems such as electric shock could arise since the cable should be installed in the water. In this paper, the leakage current and the voltage rising are measured and analyzed for the case when the cables are damaged connecting the floating photovoltaic system to the grid.

IoT 기반 산업용 밸브 안전관리 시스템 구성장치의 성능검증 방안 개발 (Development of Performance Verification Method for Components of IoT-based Industrial Valve Safety Management System)

  • 김재옥;유근준;이경식;김정훈
    • 한국가스학회지
    • /
    • 제24권5호
    • /
    • pp.10-19
    • /
    • 2020
  • 석유화학 플랜트 및 가스 시설물의 밸브 사고는 심각한 인적·물적 피해를 유발하며 이러한 시설에서의 주요사고 원인은 밸브에서의 가스 누출로 인한 흡입, 중독, 화재 및 폭발사고이다. 가스 누출을 예방하기 위한 점검은 인력에 의해 직접 검사가 이루어지는 경우가 많으며, 점검자는 가스 누출사고의 위험에 직접적으로 노출된다. 이러한 사고를 예방하기 위하여 IoT 기반 위험 분석 및 위험성 평가 모니터링 시스템과 자동제어 시스템을 적용하였다. 이를 통하여 산업용 밸브의 내·외부 가스 누출을 검지하고 하이브리드 센서를 통한 국부 및 전역 센싱으로 플랜트 현장에서의 밸브 이상으로 인한 사고를 실시간으로 모니터링 할 수 있다. 이와 같이 새로운 산업용 밸브 안전관리 시스템이 개발됨에 따라 관련 구성장치에 대한 성능 및 현장부합성에 대한 평가방안이 요구되었다. 본 연구에서는 산업용 유무선 통신을 지원하고 가스센서와 광섬유센서를 포함하는 방폭형 하이브리드 센싱 시스템과 자동제어가 가능한 액추에이터 패키지의 성능을 평가하기 위한 시험 항목 및 방법을 제시하였고 시스템의 신뢰성을 확보할 수 있는 구성장치의 성능검증 방안을 개발하였다.

불화수소 누출사고 비교를 통한 하역작업장의 안전성 향상방안에 관한 연구 (A Study on the Improvement of Safety of Unloading Site by Comparison of Hydrogen Fluoride Leakage Accident)

  • 우종운;신창섭
    • 한국가스학회지
    • /
    • 제22권4호
    • /
    • pp.32-38
    • /
    • 2018
  • 본 연구는 불화 수소 탱크 컨테이너 하역장에서 불화수소 누출 시 누출량 및 확산 정도를 정량적으로 평가하여 동종사고의 재발을 방지하고 안전성 향상방안을 제시하는데 목적이 있다. 2012년 H사에서는 최대 저장량이 18 Ton인 탱크컨테이너에서 누출사고가 발생하여 인근 지역으로 8 Ton이 누출되었고, 그로인해 사회적 이슈가 되었다. 가우시안 플럼(Gaussian plume) 모델을 이용하여 계산한 결과 누출지점으로부터 반경 1,321m까지의 농도가 20ppm 이상으로 예측되었다. 2014년 R사에서 발생한 불화수소 누출사고에서는 누출량이 11.02kg으로 추정되었고, 그 중 2.9kg이 세정기로 회수되었다. 가우시안 플럼 모델을 사용하여 계산 한 결과, 누출 원으로 부터 20ppm 이상의 농도를 갖는 피해 범위가 반경 69m로 예상되었다. 위의 두 가지 사고를 비교 한 결과, 누출량은 약 987배 차이가 발생했고, 피해 지역은 19 배 이상 차이가 나는 것으로 나타났다. 따라서 보호구의 착용, 하역 장소의 밀폐 및 세정기 설치, 그리고 비상훈련을 실시하여 하역장에서 불화수소가 대량으로 누출되는 사고가 발생하지 않도록 관리해야 한다는 결론을 얻었다.

감전사고 방지를 위한 물놀이.입욕시설의 조명설비 시설규정 연구 (A Study on the lighting Installation Regulations in Waterpark, Public Bath and Similar Places for the Prevention of Electrical Shock)

  • 김종민;김한상;김기현;황광수
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 학술대회 논문집
    • /
    • pp.339-344
    • /
    • 2005
  • A person's body resistance in the waterpark, public bath and similar places is lower than any other places due to effect of water. So low voltage may create a shock hazard for the human body in case of leakage or fault currents from lighting unit etc. We researched the related regulations these are internal standards, NEC, IEC and investigated the actual conditions for the prevention of electrical shock due to lighting units in the waterpark, public bath and similar places. So we could present actual facilities's problems and solutions

  • PDF