• Title/Summary/Keyword: Kitchen and bathroom exhaust

Search Result 7, Processing Time 0.031 seconds

Simulation of the Kitchen and Bathroom Exhaust Systems in High-Rise Apartment Buildings (고층 아파트의 주방 및 욕실 배기 시스템 시뮬레이션)

  • 김영돈;김광우
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.12
    • /
    • pp.996-1006
    • /
    • 2003
  • The objective of this study is to find major variables which influence the performance of kitchen and bathroom exhaust systems in high-rise apartment buildings. For this purpose, the influencing factors on the exhaust airflow rates from the kitchen or bathroom are identified and in every cases, which are made of combinations between the influencing factors, the exhaust airflow rates are calculated through the simulations. The results of the simulation show that the exhaust airflow rates from the kitchen and bathroom mainly depends on outdoor air temperature, number of floors, airtightness of the building envelope, fan on ratio, vertically connected to same shaft, exhaust fan capacity for kitchen or bathroom, roof ventilator capacity and shaft area for kitchen or bathroom exhaust.

A Study on the Wind Power Generation Using Vertical Exhaust Air Duct of the High-Rise Apartments (초고층 공동주택의 주방.욕실 배기 풍속을 풍력발전에 활용하는 방안)

  • Lee, Yong-Ho;Kim, Seong-Yong;Hwang, Jung-Ha;Park, Jin-Chul
    • Journal of the Korean Solar Energy Society
    • /
    • v.32 no.3
    • /
    • pp.1-10
    • /
    • 2012
  • The purpose of this study was to promote the utilization of wind velocity of kitchen and bathroom exhaust ducts for wind power generation in high-rise apartments. The research content can be summarized as follows: 1) Nine high-rise apartments were examined for the installation of kitchen and bathroom exhaust ducts located in the pipe shaft (PS) section. After selecting simulation candidates, a simulation was performed with the STAR-CCM+ Ver 5.06 program. 2) Of nine high-rise apartments, seven had kitchen and bathroom exhaust ducts, whose cross section was in the range of $0.16m^2{\sim}0.4m^2$. The area ratio between the exhaust ducts and PS section (cross section of exhaust duct/area of PS section ${\times}$ 100) was on average 3.2%. 3) The simulation results were analyzed. As a result, the smaller cross section kitchen and bathroom exhaust ducts had, the more advantages there were for increasing exhaust wind velocity. If an out air inlet duct is installed to the old kitchen and bathroom exhaust ducts, it will increase exhaust wind velocity by 3.01~3.98m/s and contribute to the proper wind velocity level (3.0m/s). 4) When the simultaneous usage rate between the kitchen and bathroom exhaust fan increased from 20% to 60%, exhaust wind velocity increased. The "entire house holds" condition for exhaust fan operation provided more even exhaust wind velocity than the "some house holds" condition. 5) Exhaust wind velocity increased in the order of amplified (T-3), induced (T-2) and vertical (T-1) top of kitchen and bathroom exhaust ducts. Of them, the amplified type (T-3) was under the least influence of external wind velocity and thus the most proper for kitchen and bathroom exhaust duct tops.

A Basic Study on the Utilization of Kitchen and Bathroom Exhaust Wind Velocity in High-Rise Apartment (초고층 공동주택의 주방.욕실 배기풍속 활용을 위한 기초연구)

  • Kim, Seong-Yong;Lee, Yong-Ho;Park, Jin-Chul;Hwang, Jung-Ha
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2011.11a
    • /
    • pp.226-231
    • /
    • 2011
  • This study set out to review the air current fluidity in exhaust common ducts by installing an inlet pipe at a leisure space in the PS(Pipe Shaft)room for the sake of wind power generation with kitchen and bathroom exhaust common ducts of all the equipment and air conditioning shafts in high-rise apartment. The air current functionality of kitchen and bathroom exhaust common ducts was reviewed by analyzing wind velocity changes according to changes to the area of exhaust common ducts through a simulation, changes to the wind velocity of the kitchen hood by applying an external inlet pipe, changes to the usage factor of exhaust common ducts, and changes to wind velocity by altering the form of the ventilator at the bottom of the old exhaust common duct. It was a basic study on the utilization of exhaust wind velocity in exhaust common ducts.

  • PDF

A Study on simulation analysis of the microbe transport of air-born virus in hospital for microbiological safety (미생물 안전을 위한 병원건물의 환기설계에 따른 공기 감염균 확산에 관한 시뮬레이션 연구)

  • Choi, Sang-Gon
    • Journal of the Korea Safety Management & Science
    • /
    • v.19 no.4
    • /
    • pp.115-123
    • /
    • 2017
  • Recently there is a growing interest in the airborne spread of virus. In particular, there is growing interest in secondary infection through the air in the hospital. The distribution of air-born virus depends on ventilation system installed in a hospital. In this study, simulations were carried out to predict the move of air-born virus by ventilation system at hospital. Simulation results showed that pressure distribution was -372.05Pa ~ -3.45 Pa at 1st floor incase of only used mechanical exhaust at bathroom, shower stall, storage, kitchen etc.. if ventilation switch from used mechanical exhaust to mechanical exhaust & mechanical supply. Simulation results showed that pressure distribution was -336.44Pa at stair hall < -0.2Pa at bathroom < mean 1.19Pa at other room. So simulation results showed that using all of the mechanical supply and mechanical exhaust was more effective then the mechanical exhaust for maintain the pressure distribution in hospital. It was also showed that when using the mechanical supply and mechanical exhaust more effectively prevention of air born virus diffusion.

A Study on the Application of a Wind Power Generation System Using Outdoor Air on the Rooftop and Indoor Ventilation (건물 옥상외기와 실내배기를 활용한 풍력발전시스템 적용 연구)

  • Lee, Yong-Ho;Park, Jin-Chul;Hwang, Jung-Ha
    • Journal of the Korean Solar Energy Society
    • /
    • v.34 no.1
    • /
    • pp.72-80
    • /
    • 2014
  • This study proposed a wind power generation system utilizing outdoor air on the rooftop and indoor ventilation, which would increase according to the building height, as a way to help to save energy consumption in a building by using wind power energy of the new renewable energy sources. The study measured the distribution of air currents and power generation according to the usage factor of exhaust pipes in the kitchen and bathroom and identified the elements to consider when applying a wind power generation system to buildings in order to use outdoor air on the rooftop increasing according to the height and the indoor ventilation produced in the facility vertical shafts inside the buildings by installing a wind power generation system on the rooftop. (1) The study measured the ventilation velocity of the kitchen hood and bathroom ventilation fan by changing the zone areas by the households according to the usage factor of [${\alpha}$]=33~100%. As a result, the kitchen ventilation pipe generated the ventilation wind of 3.0m/s or more at the usage factor of [${\alpha}$] 66% or higher, and the bathroom ventilation pipe generated ventilation velocity lower than 3.0m/s, the blade velocity of the wind power generator, even after the usage factor rose to [${\alpha}$]=100%. (2) As the old bathroom ventilation pipe generated the ventilation velocity of 3.0m/s, the blade velocity of the wind power generator, even with the rising usage factor [${\alpha}$], the application of an outdoor air induction module increased the ventilation velocity by 2.9m/s at the usage factor of [${\alpha}$]=33%, 3.8m/s at the usage factor of [${\alpha}$]=66%, and 3.6m/s at the usage factor of [${\alpha}$]=100%. Thus the ventilation velocity of 3.0m/s, the blade velocity of the wind power generator, or higher was secured. (3) The findings prove that the applicability of a wind power generation system using outdoor air on the rooftop and indoor ventilation is excellent, which raises a need for various efforts to increase the possibility of its commercialization such as securing its structural stability according to momentary gusts on the rooftop and typhoons in summer and making the structure light to react to the wind directions of outdoor air on the rooftop according to the seasons.

Control Method to Ensure Uniform Exhaust Function by Household of Apartment House (공동주택의 세대별 균등 배기량을 확보 하는 제어방법에 관한 연구)

  • Kwon, Yong-Il
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.29 no.12
    • /
    • pp.628-637
    • /
    • 2017
  • This study was conducted to present an effective control method for the common duct system to uniformly discharge volume flow rate exhausted from the kitchen and bathroom of each household in an apartment regardless of the position of household. Since the common duct system is installed vertically and the ventilator is installed in the terminal, the static pressure of each household decreases when vertical height increases. Therefore, the volume flow rate exhausted from each household is different. In order to improve such a phenomenon, a constant air volume damper shall be installed in a branch duct coupled with a common vertical duct system. The selected ventilator should also be able to handle the maximum volume flow rate considering diversity factor. Therefore, a uniform volume flow rate must be exhausted from all households where the hood is operated. This paper mainly focuses on suggestion of an optimum exhaust control method by comparing exhaust performance of each household according to the presence or absence of a constant air volume damper.

A Study on the Effect of Open and Closed Room Doors on Apartment Ventilation Characteristics (공동주택에서 각 실 문의 개폐에 따른 환기 특성 연구)

  • Choi, Im-Kyoo;Kim, Young-Il;Chung, Kwang-Seop
    • Proceedings of the SAREK Conference
    • /
    • 2008.11a
    • /
    • pp.469-474
    • /
    • 2008
  • The objective of this study is to propose basic design guidelines for more effective air ventilation system in apartments. It is well known that ventilation depends on whether the room doors are open or closed as well as people's living patterns. This study considers 84 ㎡-sized apartment which has extended living room without balcony. Ventilation of bathroom and kitchen is not considered. The height of the building, external air pressure and air infiltration through the windows are also neglected. The regulation on indoor air quality made it mandatory that the air change per hour be more than 0.7. Four models are suggested to study the effect of open and closed doors. Models 1 and 3 are open door types and models 2 and 4 are closed door types. The open types have 50 mm hole near the top of the door to substitute exhaust outlet. The ventilation effectiveness was evaluated by 3-dimensional numerical simulation using finite volume method by a commercial software. This work compares air flow, temperature of air, age of air and the efficiency of ventilation of apartments with wooden doors of bedroom 1 and 2, which are open or closed.

  • PDF