• Title/Summary/Keyword: Kaolin contamination degree

Search Result 5, Processing Time 0.022 seconds

Classification Technique of Kaolin Contaminants Degree for Polymer Insulator using Electromagnetic Wave (방사전자파를 이용한 고분자애자의 오손량 분류기법)

  • Park Jae-Jun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.19 no.2
    • /
    • pp.162-168
    • /
    • 2006
  • Recently, diagnosis techniques have been investigated to detect a Partial Discharge associated with a dielectric material defect in a high voltage electrical apparatus, However, the properties of detection technique of Partial Discharge aren't completely understood because the physical process of Partial Discharge. Therefore, this paper analyzes the process on surface discharge of polymer insulator using wavelet transform. Wavelet transform provides a direct quantitative measure of spectral content in the time~frequency domain. As it is important to develop a non-contact method for detecting the kaolin contamination degree, this research analyzes the electromagnetic waves emitted from Partial Discharge using wavelet transform. This result experimentally shows the process of Partial Discharge as a two-dimensional distribution in the time-frequency domain. Feature extraction parameter namely, maximum and average of wavelet coefficients values, wavelet coefficients value at the point of $95\%$ in a histogram and number of maximum wavelet coefficient have used electromagnetic wave signals as input signals in the preprocessing process of neural networks in order to identify kaolin contamination rates. As result, root sum square error was produced by the test with a learning of neural networks obtained 0.00828.

Evaluation of Artificially Contaminated Suspension Insulators for Transmission (송전용 현수애자의 인공오손 평가)

  • Kim, Chan Young;Choi, In-Hyuk;Hong, Dong-Suk;Kim, Beom-Soo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.08a
    • /
    • pp.123-127
    • /
    • 2002
  • This paper presented the results of evaluation of artificially contaminated suspension insulators for transmission lines. The suspension insulators were contaminated with kaolin and clay which were included various amount of natural salt. The degree of contamination were evaluated by measuring equivalent salt deposit density(ESDD). Then, the leakage currents were measured as a function of applied voltage, degree of contamination, humidity.

  • PDF

옥외에서 사용되는 배전급 폴리머 현수애자의 오손특성에 관한 연구

  • Lee, Byung-Sung;Han, Sang-Ok
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.50 no.7
    • /
    • pp.340-345
    • /
    • 2001
  • Because they have superior insulating properties and lower in price than their ceramic equivalents, polymeric insulators have been used in outdoor insulators. But polymeric insulators mainly using in an heavy contamination area of outdoor could be easily attached to contaminants such as salt and by-products of industrial processes. To understand its effect on contaminants adhered to these insulators, we dismounted polymeric insulators adhered contaminant in the field, and evaluated its electrical characteristics, CA, and ESDD. We also manufactured slurry mixed by some kaolin and salt for the artificial contamination test and measured the degree of contaminant, AC leakage current for these contaminated samples. Consequently, the adhered contaminants to its surface is likely to be affected the performance of insulation.

  • PDF

Signal analysis of surface discharge and electromagnetic wave for insulator by kaolin contamination (카올린으로 오손된 애자의 표면방전 및 방사전자파의 신호 분석)

  • Park, Jae-Jun
    • The Journal of Information Technology
    • /
    • v.7 no.3
    • /
    • pp.113-118
    • /
    • 2004
  • Recently, diagnosis techniques have been investigated to detect a partial discharge associated with a dielectric material defect in a high voltage electrical apparatus. However, the properties of detection technique of PD aren't completely understood because the physical process of PD. Therefore, this paper analyzes the process on Surface Discharge of Polymer Insulator using Wavelet transform. Wavelet transform provides a direct quantitative measure of spectral content in the time frequency domain. As it is important to develop a non-contact method for detecting the Contamination Degree, this research analyzes the electromagnetic waves emitted from PD using Wavelet transform. This result experimentally shows the process of PD as a two-dimensional distribution in the time-frequency domain. The method is shown to be useful for detecting prediction of contamination degree.

  • PDF

The Characteristics of Artificial Contamination of Distribution Polymer Insulators Used for Outdoor Insulation (옥외에서 사용되는 배전용 폴리머애자의 인공오손 특성)

  • 이병성;한재홍;김찬영;한상옥
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.595-597
    • /
    • 2000
  • Poymeric insulators using in an heavy contamination area are easily attached to contaminants such as salt and by-products of industrial processes. To understand its effect on contaminants adhered to these insulators, we manufactured slurry mixed by some kaolin and salt as artificial contaminated solution. And then put samples in its slurry, for about one minute. And these samples are dried in natural condition for 6 days. We measured the degree of contaminant, AC leakage current for these contaminated samples.