• Title/Summary/Keyword: KEPCO System

Search Result 1,670, Processing Time 0.038 seconds

Simulation of Stability Effect with Hybrid Reclosing of A Sample EHV System (하이브리드 재폐로 방식의 초고압 표본 계통에 대한 안정도 영향 시뮬레이션)

  • Lee, Tae-Hyung;An, Byung-Chen;Park, Peung-Churl;Lee, Uk-Hwa;Shin, Jung-Rin;Lee, Sung-Woo
    • Proceedings of the KIEE Conference
    • /
    • 1996.07b
    • /
    • pp.784-786
    • /
    • 1996
  • This paper presents some stability simulations using EMTP to see the effect of EHV Lines with hybrid reclosing on power system stability. The Hybrid reclosing on EHV lines can improve the reliability of power systems. These studies is performed as a part of the research work which is aimed to find proper scheme of reclosing for EHV lines in Korea. Completing a number of simulation works with the diverse conditions such as ones reported in this paper, some decisions could be made through some stochastic approches for the simulation results for the proper scheme of reclosing for Korean systems.

  • PDF

The Functions and Characteristics of Distribution Automation System Components (국산 배전자동화시스템 구성설비의 보유기능 및 특성)

  • Ha, B.N.;Park, S.M.;Jang, J.T.;Choi, T.I.;Kim, H.Y.;Oh, S.G.
    • Proceedings of the KIEE Conference
    • /
    • 1996.07b
    • /
    • pp.899-901
    • /
    • 1996
  • KODAS is made up of the Central Control System(CCS) as four Vax workstations linked up with LAN networks, six Substation Communication Control Units(SCCU) installed in substation to transfer data, 125 Feeder Remote Units(FRU) located at the lower position of automated switch to provide the information of Fault Indicator(FI) and three kinds of automated switches to have remote control functions such as SF6 gas feeder automation switch, recloser and gas insulated pad mountes switchgear for under ground line. This paper explains the functions and characteristics in detail about each devices mentioned above.

  • PDF

A Study on the Construction of the Flexible Long-Term Generation Mix under Uncertainties of Power System (전력계통(電力系統)의 불확실성(不確實性)을 포함한 유연(柔軟)한 장기전원구성(長期電源構成)의 수립에 관한 연구(硏究))

  • Song, Kil-Yeong;NamGung, Jae-Young;Choi, Jae-Seok
    • Proceedings of the KIEE Conference
    • /
    • 1993.07a
    • /
    • pp.159-162
    • /
    • 1993
  • A new approach using fuzzy dynamic programming is proposed for the flexible long-term generation mix under uncertain circumstances. A characteristic feature of the presented approach is that not only fuzziness in fuel and construction cost. load growth and reliability but also many constraints of generation mix can easily be taken into account by using fuzzy dynamic programming. The method can accommodate arbitrary shape of membership function as well as the operation of pump-generator. And so more realistic solution can be obtained. The effectiveness of the proposed approach is demonstrated by the best generation mix problem of KEPCO-system which contains nuclear, coal, LNG, oil and pump-generator hydro plant in multi-years.

  • PDF

the GOOSE Communication Test of IEC 61850 based IED (IEC 61850기반 IED GOOSE 통신시험)

  • Lee, N.H.;Lee, M.S.;Jang, B.T.;Han, J.Y.;Song, I.J.;An, Y.H.
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.05a
    • /
    • pp.263-266
    • /
    • 2009
  • IEC 61850 based substation automation system is operating with Generic Object Oriented Substation Event message when an IED need to send an important signal to other IEDs or receive the signals from another IED such as trip and interlock. So interoperability of substation automation system may be assured throughout the verification of IED GOOSE. This paper shows a testing contents for GOOSE subscription and publish of IEC 61850 based IED and describes how to analysis the result of GOOSE testing. Now domestic IED completed by GOOSE test of this study are working in KEPCO test field.

  • PDF

A practical approach for analytical reliability evaluation of distribution systems (배전시스템의 해석적 신뢰도 평가를 위한 실제적인 적용방법)

  • Kim, Jae-Chul;Han, Seong-Ho;Lee, Hyun-Hwa;Sun, Ga-In;Jang, Jeong-Tae
    • Proceedings of the KIEE Conference
    • /
    • 1994.11a
    • /
    • pp.33-35
    • /
    • 1994
  • This Paper Presents a practical approach to evaluate the reliability indices of electric distribution systems. The use of reliability evaluation is placed with the framework of distribution system planning. In this paper, the reliability model is based on an analytical method, connecting component failure to load point outage each section. five case studies are reported in the paper. These are to study the effect of varying failure rates and repair times on distribution feeders. The results of a study on sample system are presented in this paper.

  • PDF

Construction of 154kV Intelligent Substation for Verification Test (154kV급 실증시험용 인텔리전트 변전소 구축)

  • Chung, Y.H.;Kim, J.B.;Lee, H.S.;Choi, I.H.;Lee, D.I
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.661-662
    • /
    • 2007
  • We have carried out the construction of the 154kV intelligent substation with KEPRI. The intelligent substation is built in Gochang testing facility of KEPCO and consists of electronic instruments for GIS(gas insulated switchgear), digital control panel, remote monitoring and diagnosis system, and digital relay system. Rogowski coil type CT(RCT) and capacitive voltage divider(CVD) are introduced compared with the instrument transformer of conventional type. Digital control panel(DCP) replaces the LCP(local control panel) which is drived for mechanical operation. For the monitoring of the condition of GIS and TR, various sensors are used. In this paper, we mention the synopsis and report the progress state of project.

  • PDF

A Study on Voltage Stability Assessment Using the Reactive Reserve Iindex (무효전력 예비력 지수를 이용한 전압안정도 평가 방안에 관한 연구)

  • Seo, Sang-Soo;Lee, Byong-Jun;Nam, Su-Chul;Shin, Jeong-Hoon;Kim, Tae-Kyun
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.457-458
    • /
    • 2007
  • The reactive reserves of generators is close to voltage stability. This characteristic has led to the development of a few year monitoring the reactive reserves. In this paper, the reactive reserves have been calculated considering the generator capability curve. In addition, through dividing the systems using electric distance, the reactive reserves of each area has been calculated. Then, using the correlative relationship between reactive reserves and PV margins, the method for monitoring the voltage stability is proposed. The proposed method is tested on PSS/E test system and KEPCO system.

  • PDF

The Development of the Data Verification Module For Transient Stability Analysis (과도 안정도 해석 데이터 검증 모듈 개발)

  • Sim, G.S.;Hwang, J.H.;Cho, Y.S.;Kwon, S.H.;Jang, G.S.;Kim, T.K.;Choo, J.B.
    • Proceedings of the KIEE Conference
    • /
    • 2004.11b
    • /
    • pp.21-23
    • /
    • 2004
  • The purpose of this paper is to explain the techniques of the data verification module achieved while developing a transient stability program which is suitable to korean power system. It concentrates on the concrete explanation about modeling of the dynamic models and the method of the data verification. This proposed module enhances the performance of the developing program. This developing module has been tested with the KEPCO system, and the simulation results obtained from the program are compared to those of commercial programs.

  • PDF

Assessing the Effect of Voltage Sag in Distribution System using Reliability Data (신뢰도 데이터를 이용한 배전계통의 순간전압강하 영향평가)

  • Yun, Sang-Yun;Kim, Jae-Chul;Lim, Seung-Jung;Oh, Jung-Hwan;Kim, Du-Bong;Han, Byung-Duk;Kim, Gi-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 1998.11a
    • /
    • pp.282-285
    • /
    • 1998
  • This paper presents a method to evaluate the effect of voltage sag in distribution system using the component reliability data of utilities. The proposed method is based on Specified CBEMA curve which is the probability curve of the customers' effect by voltage sag. We carried out the experiment for the customers' sensitive equipments using the test facilities in KERI. The Monte Carlo method and the historical reliability data in KEPCO are used for simulations.

  • PDF

Application of Simulated Annealing for Loss Reduction in Distribution System (배전 계통에서 손실 감소를 위한 시뮬레이티드 어닐링의 적용)

  • Jeon, Young-Jae;Choi, Seung-Kyoo;Kim, Hun;Lee, Seung-Youn;Kim, Jae-Chul
    • Proceedings of the KIEE Conference
    • /
    • 1998.11a
    • /
    • pp.335-337
    • /
    • 1998
  • This paper presents a efficient algorithm for loss reduction of distribution system by automatic sectionalizing switch operation in distribution systems of radial type. Simulated Annealing can avoid escape from local minima by accepting improvements in cost, but the use of this algorithm is also responsible for an excessive computation time requirement. To overcome this major limitation of Simulated Annealing Algorithm, we may use advanced Simulated Annealing Algorithm. Numerical examples demonstrate the validity and effectiveness of the proposed methodology.

  • PDF