• Title/Summary/Keyword: KEPCO System

Search Result 1,670, Processing Time 0.03 seconds

The Application of Neutral Reactors to Limit Through fault Duty on Substation Transformer. (전력용(電力用) 변압기(變壓器) 고장전류(故障電流) 감소(減少)를 위(爲)한 중성점(中性点) 리액터 적용(適用) 연구(硏究))

  • Jang, J.K.;Kim, J.B.;Smith, David R.
    • Proceedings of the KIEE Conference
    • /
    • 1990.11a
    • /
    • pp.210-213
    • /
    • 1990
  • This paper presents the countermeasure to present the main transformer of distribution substation from deteriorating and failing due to repeated magnetic force of the transformer winding by ground fault current in 22.9kV multi grounded distribution system. The Winding strength to the short circuit current is designed to be endurable to the stress of over current. But this design is related to the manufactures. In this paper we examine the application of shunt reactor to the neutral point of the low side of the transformer to reduce fault current due to the fault in the distribution lines we have analysed the fault characteristics of the system and calculated the optimum ohmic values of the neutral reactor.

  • PDF

Emergency Service Restoration and Load Balancing in Distribution Networks Using Feeder Loadings Balance Index (피더부하 균등화지수를 이용한 배전계통의 긴급정전복구 및 부하균등화)

  • Choe, Sang-Yeol;Jeong, Ho-Seong;Sin, Myeong-Cheol
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.5
    • /
    • pp.217-224
    • /
    • 2002
  • This paper presents an algorithm to obtain an approximate optimal solution for the service restoration and load balancing of large scale radial distribution system in a real-time operation environment. Since the problem is formulated as a combinatorial optimization problem, it is difficult to solve a large-scale combinatorial optimization problem accurately within the reasonable computation time. Therefore, in order to find an approximate optimal solution quickly, the authors proposed an algorithm which combines optimization technique called cyclic best-first search with heuristic based feeder loadings balance index for computational efficiency and robust performance. To demonstrate the validity of the proposed algorithm, numerical calculations are carried out the KEPCO's 108 bus distribution system.

Analysis of the Load Transfer Capacity and Study of Conductor Sizes for Contingency Levels in Distribution Systems (상정사고별 배전측 부하분담 능력 분석과 도체 규격 검토)

  • 조남훈;전영재;한용희;한병성
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.7
    • /
    • pp.363-370
    • /
    • 2003
  • This paper presents the analysis of the load transfer capacity and study of conductor size for variable contingencies in distribution systems. The operation capacity of feeders was changed to improve operation efficiency in KEPCO, considerations for contingencies are still based on the previous capacity. In order to cope with the changes such as operation capacity, it is necessary to study whether the present "contingency support criteria" is reasonable or not, also to confirm the whether the present criteria should be improved or not. We analyze the load transfer capacity and conductor size on a distribution system for contingency levels such as the substation-level, bank-level, feeder-level, and zone-level.one-level.

Failure Predict of Standard Sand Model Slope using Compact Rainfall Simulation (소형 인공강우 장치에 의한 표준사 모형사면의 붕괴 예측)

  • Moon, Hyo Jong;Kim, Dae Hong;Jeong, Ji Su;Lee, Seung Ho
    • Journal of Korean Society of Disaster and Security
    • /
    • v.8 no.2
    • /
    • pp.21-26
    • /
    • 2015
  • This study analyzes the failure predict of model slope due to changes in ground condition followed by heavy rainfall with a simulated rainfall system. the movement of a slope from the rainfall penetrating the unsaturated soil is investigated with respect to various conditions of pore-water pressure, earth pressure and moisture content, considering rainfall duration and permeability.

Implementation of an Inductively Coupled EM Probe System for PD Diagnosis

  • Kim, Hee-Dong;Park, Noh-Joon;Park, Dae-Hee
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.1
    • /
    • pp.111-118
    • /
    • 2011
  • In recent years, various types of partial discharge (PD) methods such as capacitive, inductive, electromagnetic, and acoustic coupling techniques have been developed for diagnosing rotating machines. An electromagnetic (EM) probe, which is an inductively coupled type of sensor, is required for detecting corona and internal discharges during off-line tests. In this study, a new technique for enhancing the measurement sensitivities for corona and internal discharge based on an EM inductive position sensor is proposed. An EM probe that winds wires around horseshoe-shaped and cylindershaped ferrites as helices is designed and optimized for the implementation of off-line PD monitoring of the stator winding of a rotating machine. The measurement system based on this design is implemented, and it is verified from the results of the experiment performed in this study that the probe provides similar performance as existing commercial products.

Development of the Algorithm for Discriminating Faults from Variation using Wavelet Transform (웨이블릿 변환을 이용한 고장과 Variation의 유형 구분 알고리즘 개발)

  • Seo, Hun-Chul;Lee, Soon-Jeong;Kim, Chul-Hwan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.8
    • /
    • pp.1460-1466
    • /
    • 2011
  • This paper proposes the algorithm for discriminating faults from the variation due to the operation of non-linear components to prevent the mal-operation of protection relay in the distribution system. An IEEE 13 node test feeder is modeled to analyze the characteristics of the fault and each variation using EMTP-RV. Simulations with various operating conditions of transformers, non-linear loads, and unbalanced loads are performed using the test feeder model. Based on simulation results, the wavelet transform is adopted to analyze the current waveforms from the faults and variations to find out the differences between them and the algorithm for discriminating faults from the variation is proposed. The proposed algorithm is verified by using the current waveforms simulated in the KEPCO's distiribution system and IEEE 13 node test feeder.

A Study on the effect on reactive power transmitted to the power station by Voltage (154kV) of Power System (계통전압(154kV)이 소내수전 무효전력에 미치는 영향 연구)

  • Jeon, Kyu-Nam;Chang, Moon-Soung;NamGoong, Hyuk;Jeong, Hae-Jung;Ahn, Joo-Hoon
    • Proceedings of the KIEE Conference
    • /
    • 2007.11b
    • /
    • pp.314-315
    • /
    • 2007
  • As a section of electric power system linked with Kepco was changed, the decrease in qulity of the electric power transmitted to the Hapcheon hydraulic power station occurred. The actual state bring about the overheating and capability decline of electricity accommodation equipment. From now, let's improve the efficiency on the maintenance of generating equipment by studying about the cause and the method for this problem.

  • PDF

Assessment of Benefits on Distributed Generation in KOREA (우리나라 전력계통의 분산형 전원에 대한 정량적 편익산정)

  • Kim, Yong-Ha;Kim, Ui-Gyeong;Oh, Seok-Hyun;Kim, Dong-Gun;Lee, Pyong-Ho;Woo, Sung-Min
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.686-687
    • /
    • 2011
  • In this paper, the method on calculating benefits of combined heat and power is introduced for standard evaluation in electrical power system. This paper calculates benefits about new national viewpoint and viewpoint of independent power producers and assesses benefits of combined heat and power in Korea and In Seoul national capital area. Benefit costs are composed of avoid cost of centralized generation, line upgrading adjustment, loss adjustment and electrical power trade cost per year in earlier study, in addition trade cost of CO2, construction cost of combined heat and power for accurate calculation. Benefit of combined heat and power is calculated by simulation results of real electrical power system.

  • PDF

A New Required Reserve Capacity Determining Scheme with Regard to Real time Load Imbalance

  • Park, Joon Hyung;Kim, Sun Kyo;Yoon, Yong Tae
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.2
    • /
    • pp.511-517
    • /
    • 2015
  • Determination of the required reserve capacity has an important function in operation of power system and it is calculated based on the largest loss of supply. However, conventional method cannot be applied in future power system, because potential grid-connected distributed generator and abnormal temperature cause the large load imbalance. Therefore this paper address new framework for determining the optimal required reserve capacity taking into account the real time load imbalance. At first, we introduce the way of operating reserve resources which are the secondary, tertiary, Direct Load Control (DLC) and Load shedding reserves to make up the load imbalance. Then, the formulated problem can be solved by the Probabilistic Dynamic Programming (PDP) method. In case study, we divide two cases for comparing the cost function between the conventional method and the proposed method.

Calculation of an Induced Voltage on Telecommunication Lines in Parallel Distribution Lines (병행 배전선로에서의 통신선 유도전압 계산)

  • Kim, Hyun-Soo;Rhee, Sang-Bong;Yeo, Sang-Min;Kim, Chul-Hwan;Lyu, Seong-Heon;Kim, Seong-Arm;Weon, Bong-Ju
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.10
    • /
    • pp.1688-1695
    • /
    • 2008
  • Recently, it is common in a distribution system of Korea Electric Power Corporation (KEPCO) to find instances where distribution lines are parallel. A traditional method of an induced voltage calculation is not suitable for parallel distribution lines. For more actual analysis of induced voltage on telecommunication lines in parallel distribution lines, a new calculation method is needed. This paper presents a new calculation method of an induced voltage on telecommunication line using equivalent ${\pi}$ circuits matrix in parallel distribution lines. The advantages of the calculation method are using actual neutral current value and not using screening factor for considering the overhead ground wire and the neutral wire. To verify the effectiveness and the accuracy of the method, various case studies are performed with EMTP(Electro-Magnetic Transients Program).