• Title/Summary/Keyword: Jet fans

Search Result 41, Processing Time 0.02 seconds

Investigate on the rate of change of CO concentration in a tunnel under changed position of the jet fans by using numerical method (제트 팬 가동위치에 따른 장대터널 내 CO 농도 변화율에 대한 전산해석)

  • Min, Jae-Hong;Kim, Dae-Hyun;Chung, Jin-Taek
    • Proceedings of the KSME Conference
    • /
    • 2008.11b
    • /
    • pp.2765-2770
    • /
    • 2008
  • The purpose of tunnel ventilation system for long road tunnels is to keep certain levels of Visibility Index and the concentration of CO. Additional equipments such as jet fans are used in road tunnel to discharge pollutants in the road tunnel. The control algorism of tunnel ventilation system takes the value of sensors as input, and then gives the operation method of jet fans in tunnel as output. Information on the variation of CO concentration in tunnel when jet fans are running is needed to minimize their operation time. Numerical analysis is used in this paper because of the difficulty of conducting experiments under standard condition for ventilation of road tunnel. The concentration of CO has been calculated by using 3-dimensional CFD under transient condition with speed of cars, quantity of air ventilation, and the results for various operation position of jet fans are compared.

  • PDF

A numerical study on effects of thermal buoyance force on number of jet fans for smoke control (도로터널 화재시 열부력이 제연용 제트팬 댓수에 미치는 영향에 대한 해석적 연구)

  • Yoo, Ji-Oh;Shin, Hyun-Jun
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.15 no.3
    • /
    • pp.301-310
    • /
    • 2013
  • Jet fans are installed in road tunnels in order to maintain critical velocity when fire occurs. Generally the number of jet fans against fire are calculated by considering critical velocity and flow resistance by wall friction, vehicle drag force, thermal buoyance force and natural wind. In domestic case, thermal buoyance force is not considered in estimating the number of jet fans. So, in this study, we investigated the pressure loss due to the thermal buoyance force induced by tunnel air temperature rise and the impact of thermal buoyance force on the number of jet fans by the numerical fire simulation for the tunnel length(500, 750, 1000, 1500, 2000, 3500m) and grade (-1.0, -1.5, -2.0%). Considering the thermal buoyance force, number of jet fans have to be increased. Especially in the case of 100MW of heat release rate, the pressure loss due to thermal buoyance force exceed the maximum pressure loss due to vehicle drag resistance, so it is analyzed that number of 2~11 jet fans are needed additionally than current design criteria. Thus, in case of estimating the number of jet fans, it must be considered of thermal buoyance force induced tunnel air temperature rise by fire.

Effects of the Distance between Jet Fans on the Ventilation Performance in a Road Tunnel (제트홴의 이격거리에 따른 터널내 환기특성에 관한 수치적 연구)

  • Kim, Jung-Yup
    • The KSFM Journal of Fluid Machinery
    • /
    • v.14 no.4
    • /
    • pp.25-30
    • /
    • 2011
  • The jet fan is generally used to add thrust in the longitudinal ventilation system of road tunnel and the geometric conditions of jet fan such as the distance from tunnel wall have an effect on the performance of ventilation system. Numerical analyses on the flow in tunnel caused by operation of jet fan are presented to study the ventilation characteristics in tunnel. While the distance between jet fans in parallel installed in tunnel is changed 0.5 L/D to 3.0 L/D, the flowrate and mean velocity through tunnel are calculated for each cases. As the distance between jet fans increases, the flowrate through tunnel increases asymptotically and the momentum of tunnel flow is alike.

분배계통에 따른 지하주차장 환기설비 성능의 예측

  • 김경환;이재헌;오명도;김종필
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.10
    • /
    • pp.982-992
    • /
    • 2001
  • In this paper, the performance of ventilation equipments in enclosed parking garages were investigated for several air distribution systems by numerical method. Air change effectiveness of the non-mixing system was 0.42. It meant that more supply air as much as the design supply air was needed to maintain good indoor air quality. In the high speed nozzle ventilating system which is most expensive one, air change effectiveness was 0.54. Therefore this system satisfied to ventilation design. In the jet fan ventilating systems, air change effectiveness for jet fan ventilating system-A with 18 jet fans and jet fan ventilating system-B with 6 jet fans in circulation mixing arrangement were 0.565 and 0.42 respectively. Jet fan ventilating system-C with 6 jet fans in transport mixing arrangement was 0.535. Jet fan ventilating system-A and jet fan ventilating system-C met the ventilation design. But velocity in jet fan ventilating system-A was over 2.0m/s which is inappropriate in human comfort. Therefore this system is not proper to ventilation. Jet fan ventilating system-C was the optimum one for enclosed parking garages among 5 systems examined in this paper.

  • PDF

Structural Analysis of Lift-Fan Rotor for Jet-VTOL Aircraft

  • Hojo, Masahiro;Ogawa, Akinori;Saito, Yoshio;Hashimoto, Ryosaku
    • Proceedings of the Korean Society of Propulsion Engineers Conference
    • /
    • 2004.03a
    • /
    • pp.521-523
    • /
    • 2004
  • The Japan Aerospace Exploration Agency (JAXA) has proposed new vertical take-off and landing (VTOL) aircraft known as the Jet-VTOL aircraft shown in Fig.1. The Jet-VTOL aircraft is based on a canard wing configuration. The aircraft has the clustered lift-fans mounted near the center of gravity for vertical flight, and has the clustered fans mounted beside the vertical tail for cruise flight. Both fans are driven by the core engine mounted inside the aft end of fuselage. The propulsion system is innovative and attractive not to be seen even in the world.

  • PDF

Model Test for the Determination of Distances between Jet-fans and Analysis of Recirculation (제트팬 설치 간격과 재유입 현상 분석을 위한 모형실험)

  • Kweon, Oh-Sang;Yoon, Chan-Hoon;Yoon, Sung-Wook;Kim, Jin
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.8 no.4
    • /
    • pp.335-344
    • /
    • 2006
  • The domestic standards which used the standards of Road Association of Japan standards presents the distances of between jet-fans by the caliber of jet-fan. However, the Permanent International Association of Road Congress (PIARC) encourages it to be ten times a diameter of the tunnel. The distance of jet-fans installed in bases of two standards differs as much as two times, as so the proper basis after analysis of internal air current is needed since such difference can lead to disadvantage for selection of ventilation configuration. Based on Froude modeling theory, 1/40 scale acrylic model of a tunnel (215mm in diameter and 6.9m in length) and jet-fan (26.3mm and 31.6mm in caliber) was made for the measurement of changes in pressure and velocity due to the extension of tunnel for analysis of internal air current. And we measured the changes in pressure of surroundings of a jet-fan for confirmation of recirculation due to the exterior airs when the jet-fan is on. The results of the model test show that internal air current was not influenced by the caliber of jet-fan and its changes in pressure and velocity were stable in the point where it was nine times of diameter of the tunnel. Also the recirculation when the jet-fan is on could be verified. According to such results, in the cases of installing jet-fan in tunnels, the distances between jet-fans needs to be more than nine times the diameter.

A comparative study on the relationship between estimates of critical velocity and number of jet fans for smoke control - A 'Fire-JF' contour map in road tunnels (임계속도와 제연팬 용량의 상관관계 연구 - 도로터널의 제연팬 특성도 연구)

  • Kim, Hyo-Gyu;Kim, Eun-Soo;Kim, Nam-Young;Lee, Chang-Woo
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.6 no.4
    • /
    • pp.269-278
    • /
    • 2004
  • Recently, critical velocity has become a topic to attract most interests from the researchers in the field of tunnel safety. As the minimum velocity to prevent smoke backlayering during a fire, many equations have been proposed so far, and the following three equations are being considered as a standard method in Korea to calculate the capacity of smoke extraction fans. Equation by Kennedy based on Froude number, Tetzner' s equation with additional variable, ${\beta}$ to modify the Kennedy's equation, and the equation with the concept of super critical velocity by Wu are studied in this paper for the comparative purpose. A contour map describing the relationship between the critical velocity and the capacity of smoke extraction fans is proposed as a tool to calculate the number of jet fans for smoke control during a fire in the local tunnels.

  • PDF

Analysis of Smoke Control According to Jet Fan Location in Straight Long Tunnel (제트 팬 설치 위치에 따른 직선터널 내의 제연해석)

  • Byun, Ju-Suk;Lim, Hyo-Jae;Kang, Shin-Hyung;Lee, Jin-Ho
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.19 no.9
    • /
    • pp.662-668
    • /
    • 2007
  • In this study, jet fans are installed with 4 cases in the straight long tunnel; inlet-side setup, middle-side setup, outlet-side setup, and dispersion setup. A bus is selected as fired car, of which fire size is 20MW. And fired car locates at 100m, 700m, 1500m position from tunnel inlet, respectively. FLUENT, commercial finite-volume code, is used to analyze the performance. The velocity profile, $CO_2$ concentration, temperature distribution are examined for analysis. Performance of smoke control is compared by the backlayering length. Consequently, inlet-side setup of jet fans is a little more efficient than other cases considering the fire occurrence frequency in tunnel.

Study of the Smoke Control Characteristics for Fire Near Jet Fans (Jet fan 근접 화재 발생 시 제연 특성 연구)

  • Kim, Jong-Yoon;Seo, Tae-Beom;Lim, Kyung-Bum;Yoo, Ji-Oh;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.21 no.1 s.65
    • /
    • pp.82-89
    • /
    • 2007
  • In this research, we conducted a PIV-visualization experiment to smoke control from fires by using a neighboring Jet fan at minimum distance. We also compared our experiment results with FDS numerical analysis ones. As a result of quantitative data analysis of smoke control modes against fires in tunnel, we concluded that a neighboring Jet fan should be placed at least 25 m away from its fire source in order to produce satisfactory smoke control results. Jet fan showed the best smoke-controlling performance, if placed 50 m away from its fire source. It tended to show an overspeed around the center of tunnel when it is placed more than 75 away from its fire source.

A Study on a Graphical Method for Determining the Characteristics of Jet-fan Ventilation System using the Contour Map of Required Ventilation Rate in Local Highways (지역별 소요환기량 특성도를 활용한 제트팬 환기방식 가능 터널제원 결정연구)

  • 김효규;김화수;김종대;이창우
    • Tunnel and Underground Space
    • /
    • v.13 no.3
    • /
    • pp.235-243
    • /
    • 2003
  • Recent worldwide trends show that tunnel length is getting longer, and the demand for longitudinal ventilation system with jet-fans in highway tunnels has also increased mainly due to the economic reasons. Improvements in vehicle engine subsequently reduced required ventilation rate(Qreq) which is the decisive factor in choosing the optimal ventilation system. Qreq contour map is a graph that defines the relationship among tunnel length, grade and required ventilation rate. It is important to understand the variation of Qreq in order to evaluate the characteristics of ventilation system with jet fans. Therefore this study aims at studying a graphical method for determining the characteristics of jet-fm ventilation system using Qreq contour map. Also, this study focuses on traffic composition on local highways.