• Title/Summary/Keyword: Jeju system

Search Result 1,703, Processing Time 0.026 seconds

Power Quality Analysis of Jeju Power System during HVDC Overhaul using PSCAD/EMTDC (PSCAD/EMTDC에 의한 직류연계선 오버홀시 제주계통의 전력품질 분석)

  • Kang, Bo-Seung;Kim, Jae-Hong;Kim, Eel-Hwan;Kim, Se-Ho;Oh, Seong-Bo;Song, Ki-Heouk
    • Proceedings of the KIPE Conference
    • /
    • 2008.06a
    • /
    • pp.82-84
    • /
    • 2008
  • This paper presents the modeling and power quality analysis of Jeju island power system connected with wind farm, and thermal power plant. It is for indicating the influence of wind farm operation in steady and transient state in Jeju island power system during the HVDC system overhaul period. For the computer simulation, three kinds of main item are modeled, which are 67[MW] wind farm, thermal power plant and Jeju power load. To analyze the influence of the wind power generation to the Jeju power system, two kinds of simulations are carried out by using the PSCAD/EMTDC program. One is the steady state operation under the variable speed wind, and the other is the transient state operation when all of wind farms in Jeju island are disconnected from the Jeju power grid instantaneously on the rated power output. With the comparison of these results, it is useful for analyzing the power quality of Jeju power system versus wind power generation.

  • PDF

Stability Analysis of Jeju Power System with Wind Turbine Generators and HVDC (풍력발전설비 및 HVDC가 도입된 제주도 계통에 대한 안정도 해석)

  • Kim, Do-Hyung;Kim, Jae-Eon
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.11
    • /
    • pp.1897-1904
    • /
    • 2008
  • In this paper, the method for effective stability analysis of Jeju power system in 2011 is proposed. The stability analysis of Jeju power system was carried out by using proposed method In case of Jeju power system with wind turbine generators or without wind turbine generators, including CSC HVDC or VSC HVDC. The steady-state stability is validated by SCR and ESCR, PV curve, QV curve. And the transient stability is analyzed by CCT(Critical Clearing Time). VSC HVDC has more advantages than CSV HVDC on the stability. Also, Jeju power system without wind turbine generators has more advantages than Jeju power system with Wind Turbine Generators on the stability.

Power Quality Analysis of Wind Farms interconnected in Jeju System during HVDC Overhaul (HVDC Overhaul 기간 중 제주계통에 연계된 풍력발전의 전력품질 분석)

  • Chae, Woo-Kyu;Yoon, Gi-Gab;Cho, Seong-Soo;Jung, Won-Wook
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.11
    • /
    • pp.1946-1953
    • /
    • 2008
  • Power system of Jeju is interconnected to the mainland using HVDC and that is also interconnected to three wind farms. It will be difficult to control of Jeju power system if HVDC is disconnected or HVDC is overhauled under large scale wind farms interconnected. We measured and analysed the power quality of two substation and two wind farms to assess that wind farms have an effect on Jeju system during the HVDC overhaul last May. We concentrated on the power quality like frequency, voltage variation, voltage harmonics, current harmonics, flicker. We can found that the frequency of Jeju system is very unstable during overhaul, so the frequency of Jeju system can be variated easily by wind farm's rapid output power variation. There are some benefits and weak points in power quality between two wind farms because each wind farm is consist of different wind turbines.

Modeling and Analysis of Sangmyeong Wind Farm with HESS (HESS가 연계된 상명풍력발전단지의 모델링과 해석)

  • Shin, Hyun;Kim, Eel-Hwan
    • Proceedings of the KIPE Conference
    • /
    • 2019.07a
    • /
    • pp.422-423
    • /
    • 2019
  • In accordance with the Carbon-Free Island by 2030 policy of Jeju Special Self-Governing Province, renewable energy sources are increasing in Jejudo Island. Due to the intermittent output characteristics of wind turbines, one of the renewable energy sources, which can cause unbalanced system conditions between the demand load and the power generation of Jejudo Island. The Korea Power Exchange limits the output of wind turbines for stabilizing the Jeju power system. Therefore, this paper proposes a method to supply a limited output of Sangmyeong Wind Farm in Jeju Power system to Energy Storage System(ESS) and Water Electrolysis Device(WED). The voltage and frequency fluctuation of the Jeju power system is checked accordingly. The simulation results are performed using the PSCAD/EMTDC program.

  • PDF

Feasibility Analysis of STATCOM Application for Jeiu-Haenam HVDC System (제주-해남 HVDC 시스템에 STASTCOM 적용 타당성 분석)

  • Baek Seung-Taek;Choo Won-Gvo;Han Byung-Moon;Jang Gil-Soo
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.8
    • /
    • pp.401-409
    • /
    • 2005
  • This paper describes a feasibility analysis result of STATCOM application for the Jeju-Haenam HVDC system. The Jeju-Haenam HVDC system is one of the typical HVDC system interconnected with the low short-circuit-ratio AC system, which is vulnerable to the commutation failure due to the AC voltage variation. STATCOM has been considered as an effective reactive-power compensator to increase short-circuit-ratio of the interconnected AC system. In this study, a simulation model of Jeju-Hacnam HVDC system with STATCOM was developed using PSCAD/EMTDC. The developed simulation model was utilized to analyze the dynamic performance analysis of Jeju-Haenam HVDC system with STATCOM. The analysis results show that STATCOM can improve the dynamic performance of Jeju-Haenam HVDC system, such as load-change recovery performance and fault recovery performance.

Feasibility Analysis of STATCOM Application for Jeju-Haenam HVDC System (제주-해남 HVDC 시스템에 STATCOM 적용 타당성 분석)

  • Baek, Seung-Taek;Han, Byung-Moon;Jang, Gil-Soo
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.60-62
    • /
    • 2005
  • This paper describes a feasibility analysis result of STATCOM application for the Jeiu-Haenam HVDC system. The Jeju-Haenam HVDC system is one of the typical HVDC system interconnected with the low short-circuit-ratio AC system, which is vulnerable to the commutation failure due to the AC voltage variation. STATCOM has been considered as an effective reactive-power compensator to increase short-circuit-ratio of the interconnected AC system. In this study, a simulation model of Jeju-Haenam HVDC system with STATCOM was developed using PSCAD/EMTDC. The developed simulation model was utilized to analyze the dynamic performance analysis of Jeju-Haenam HVDC system with STATCOM. The analysis results show that STATCOM can improve the dynamic performance of Jeju-Haenam HVDC system, such as load-change recovery performance and fault recovery performance.

  • PDF

Power Quality Analysis Considering Contingency of STATCOM in Jeju Power Grid (제주계통의 STATCOM 상정사고를 고려한 전력품질 해석)

  • Ko, Ji-Han;Kim, Dong-Wan;Kim, Seong Hyun;Kim, Homin;Kim, Eel-Hwan
    • Journal of the Korean Solar Energy Society
    • /
    • v.34 no.2
    • /
    • pp.91-97
    • /
    • 2014
  • This paper presents the modeling and contingency analysis of Jeju power system. For the analysis of contingency with simulation, thermal power plants, current source type HVDC systems, wind farms, STATCOMs and Jeju power load are modeled by PSCAD/EMTDC program. And three kinds of simulation are carried out. Firstly, two STATCOMSs are in normal operation. Secondly, one STATCOM is in fault. Lastly, all of STATCOMs are in fault. These comparative studies will be useful for evaluating the effectiveness of STATCOM to stabilize for the Jeju power system.

A Study of the Ondol (Gudul, Floor Heating System) and Kitchen Space in the Traditional Houses on Jeju Island, Korea

  • Kim, Bong-Ae;Lee, Jeong-Lim
    • International Journal of Human Ecology
    • /
    • v.4 no.1
    • /
    • pp.15-23
    • /
    • 2003
  • Jeju-do is a volcanic island located off the shore of the Korean peninsula facing the Pacific Ocean. The traditional housing styles of the Jeju Province, therefore, reflect the impact of these natural backgrounds and reveal different housing styles that are distinctive from those of mainland Korea. The purpose of this research is to analyze the peculiarities of the Ondol (floor heating system) and the kitchen space of traditional housing of Jeju Island in terms of lifestyles. This study shall employ two research methods: a literature review and field survey methods. The literature review shall focus on the observations of characteristics noted in previous studies of Jeju's private houses. The field survey shall employ field survey and interview methods originating from the ethnography of the culturological-anthropologist approach. (1) The Jeju-do Ondol system is a “Weibang-eudul” system which means one Gudul per fire hole. (2) The definition of terms for Gulmook show variations depending on the various regions on Jeiu-do. (3) Major facilities in Jeongji include Gulmook, Sotduck, and Busup. Gulmook is a heating facility and Sotduck refers to a cooking facility; Busup refers to a combination of heating, cooking, and illuminating facilities.

Frequency and Voltage Control Strategies of the Jeju Island Power System Based on MMC-HVDC Systems

  • Quach, Ngoc-Thinh;Chae, Sang Heon;Song, Seung-Ho;Kim, Eel-Hwan
    • Journal of Power Electronics
    • /
    • v.18 no.1
    • /
    • pp.204-211
    • /
    • 2018
  • At present, one of two LCC-HVDC systems is responsible for controlling the grid frequency of the Jeju Island Power System (JIPS). The grid voltage is regulated by using STATCOMs. However, these two objectives can be achieved in one device that is called by a modular multilevel converter-high voltage direct current (MMC-HVDC) system. Therefore, this paper proposes frequency and voltage control strategies for the JIPS based on a MMC-HVDC system. In this case, the ancillary frequency and voltage controllers are implemented into the MMC-HVDC system. The modelling of the JIPS is done based on the parameters and measured data from the real JIPS. The simulation results obtained from the PSCAD/EMTDC simulation program are confirmed by comparing them to measured data from the real JIPS. Then, the effect of the MMC-HVDC system on the JIPS will be tested in many cases of operation when the JIPS operates with and without STATCOMs. The objective is to demonstrate the effectiveness of the proposed control strategy.

A Study on Resolving the Radar Blind Sector in Jeju region (제주지역 레이더 음영지역 해소에 관한 연구)

  • Moon, Woo-Choon;Jung, Hyun-Tae;Kim, Bo Young
    • Journal of the Korean Society for Aviation and Aeronautics
    • /
    • v.23 no.4
    • /
    • pp.12-21
    • /
    • 2015
  • Due to the influence of Han-la Mountain which is located at the center of Jeju Island, a radar blind sector has been appearing in the south-east, low-altitude area of Jeju Island. Thus, the region is perilous for aircraft using surveillance in this area with the existing radar equipment that is currently available. In addition, as the popularity for domestic leisure aviation is on the rise, the safety in low-altitude area should be guaranteed. Where not only IFR flights but also VFR flights are mainly used. Therefore, immediate measures to the present state of radar blind sector in Jeju Island should be taken into serious account. Regarding the circumstances, this study's purpose is to help secure the aviation safety in Jeju region by analyzing the current air traffic surveillance system in Jeju Island and comprehending its vulnerable factors. Moreover, this study compares secondary radar surveillance system, ADS-B and MLAT(Multilateration) system with factors based on the guidance materials from ICAO Asia and Pacific region office to suggests an adequate surveillance technology considering the regional characteristics of Jeju.