• 제목/요약/키워드: Insulation diagnostic test

검색결과 55건 처리시간 0.031초

수력발전기 고정자권선의 단말부 절연파괴와 절연특성시험과의 관련성 분석 (Analysis of Correlation Endwinding Breakdown and Insulation Test for Stator winding of Hydro-Generator)

  • 이동근;이광호;최교남;김현일;오봉근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 전기설비
    • /
    • pp.103-105
    • /
    • 2005
  • The test were performed to analyze the cause of endwinding breakdown of hydro-generator which had been in service after being constructed 1971. we conducted insulation diagnostic tests and checked visual inspection and operating condition of protective relays. On the basis of these test results, this paper tried to present the importance of service environment for the generator stator winding.

  • PDF

Recovery Voltage Measurements of Oil-immersed Transformer

  • Li, Ming-Hua;Dong, Ming;Qu, Yan-Ming;Yan, Zhang
    • Transactions on Electrical and Electronic Materials
    • /
    • 제7권5호
    • /
    • pp.230-234
    • /
    • 2006
  • One of the methods currently being investigated as a possible non-intrusive diagnostic tool for condition monitoring of power transformer and cable is the recovery voltage measurement, which will be improving the ability to detect the content of water concentration and the ageing process in the insulation system and may thus be an indicator of insulation quality and its ageing status. The polarization phenomenon was studied using RVM with oil-paper samples. In order to interpret its mechanism, the Extended Debye model was introduced. With different circuit parameters, various simulation results were gotten. Furthermore, with the test samples of different ageing condition, measurements are accomplished in the lab. On the basis of this experiment as well as theoretical analysis, correlations between polarizations and ageing were analyzed.

XLPE 절연체에서의 열이력에 의한 전기, 물리적 특성 평가 (Estimation of Electrical & Physical Characteristics by Thermal History in XLPE Insulation)

  • 이상진;심성익;전승익
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 Techno-Fair 및 합동춘계학술대회 논문집 전기물성,응용부문
    • /
    • pp.183-184
    • /
    • 2008
  • The aim of this study is to find out the effects of thermal aging condition on dielectric strength and degree of crtstallinity of XLPE insulation. Thermal properties of XLPE insulation were investigated by DSC(differential scanning calorimetry) and dielectric strength were analyzed using AC BDV tester. Aging of XLPE samples were conducted through different four conditions. The degree of crtstallinity and AC BDV were changed by thermal history. From these results, it can be suggested that DSC and AC BDV test are suitable for diagnostic method of extra high voltage XLPE cable.

  • PDF

온라인 및 오프라인 PD 모니터링에 관한 연구 동향 (A Research Trend on On-Line/Off-Line PD Insulation Diagnostic System)

  • 추종훈;홍창일;최용성;이경섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.2008-2009
    • /
    • 2007
  • The paper considers the relation between on-line monitoring and diagnostics on the one hand and high-voltage (HV) withstand and partial discharge (PD) on-site testing on the other. HV testing supplies the basic data (fingerprints) for diagnostics. In case of warnings by on-line diagnostic systems, off-line withstand and PD testing delivers the best possible information about defects and enables the classification of the risk. Because alternating voltage (AC) is the most important test voltage, the AC generation on site is considered. Frequency tuned resonant (ACRF) test systems are best adapted to on-site conditions. They can be simply combined with PD measuring equipment. The available ACRF test systems and their application to electric power equipment -from cable systems to power transformers - is introduced.

  • PDF

부분방전 패턴을 이용한 가교폴리에틸렌에서의 트리성장에 관한 연구 (The Study on tree growth in XLPE using PD patterns)

  • 강대용;오광영;신창면;박명섭;조규복;황보승;박대희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 추계학술대회 논문집 학회본부 C
    • /
    • pp.941-943
    • /
    • 1998
  • Exploitation of equipment with cross linked polyethylene (XLPE) insulation requires its condition monitoring and diagnostic. Traditionally diagnostics of insulation is carried out by means of partial discharge detection. Many researchers have developed a lot of methods to identify the defect by the PD form. However, such identification of a defect, for example, void, inclusion or treeing, does not say about its danger from a point of view of full insulation gap breakdown and insulation construction failure. The information about the form and size of formed upon high voltage treeing is necessary for prediction of the remained resource of XLPE insulation. For this purpose we carry out experimental research for determination of the dependencies between PD characteristics in XLPE upon time and three dimension PD patterns of corresponding treeing. The investigations were carried out by means of electrical measurement of PD current and simultaneous optical recording of treeing image. Test results show that the PD patterns can be applied for detecting tree growth well.

  • PDF

고전압회전기 고정자권선 운전중 부분방전진단시스템의 현장적용사례 연구 (A Case Study of On-line PD Measuring System on the Stator Winding for High Voltage Rotating Machine)

  • 오봉근;강동식;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2010년도 하계학술대회 논문집
    • /
    • pp.109-109
    • /
    • 2010
  • On-line partial discharge(PD) diagnostic system is the most prominent systems to diagnose insulation condition for the high voltage rotating machines. Partial discharge measuring system(PDMS) series with ceramic coupler(PD detecting sensor) installed hydro generator and high voltage motor have been measured the PD data for many years. The trend of PD magnitude in the on-line PD system increased for some machines. These machines showed a same result in the conventional off-line PD test and PD magnitude decreased after stator winding insulation cleaning. This case study show that PDMS has been proved to be good results by comparing PD magnitude with on-line and off-line PD test and it is important to plan the maintenance project for the hydro generator stator winding because PD value was decreased after insulation cleaning.

  • PDF

A Study of On-line Monitoring System for a KEPCO Pumped Storage Generator/Motor

  • Kim Hee-Dong;Ju Young-Ho;Kim Yong-Joo;Cho Kyu-Bock
    • Transactions on Electrical and Electronic Materials
    • /
    • 제7권2호
    • /
    • pp.90-95
    • /
    • 2006
  • An on-line diagnostic test has been studied and performed for the pumped storage generator/motor. This study aims at reducing the diagnostic cost, minimizing the technical dependency on third party manufactures. Further design of on-line diagnostic system such as shorted-turn of rotor winding, partial discharge (PD) of stator winding and air-gap between stator and rotor for pumped storage generator/motor has been verified. In addition, it needs to be validated on site performance of the developed continuous on-line monitoring system for corresponding tasks for the improvement of the availability & reliability during operation.

배전용 전력케이블 시스템 포괄진단 설비 개발 (Development of Global Insulation Assessment System for Medium Voltage power Cable System)

  • 이동영
    • 조명전기설비학회논문지
    • /
    • 제17권2호
    • /
    • pp.66-72
    • /
    • 2003
  • 본 연구에서는 국내 배전계통에 사용 중인 전력케이블에 대한 평균열화평가시스템을 개발하였다. 절연진단의 최소한의 목적은 전력공급의 중단을 초래할 수 있는 열화 즉, 사고가능성이 논은 전력케이블을 효율적으로 선별하고 경제적으로 관리하는데 있다. 따라서 이러한 최소한의 진단 목표를 달성하기 위한 가장 효율적인 진단원리로 열화시정수법을 채택하고 감쇠전압을 측정변수로 하여 진단설비를 개발하였다. 현장적용성 시험 및 파괴강도 시험 결과 열화상태 평가결과와 파괴강도의 상관관계를 확인하였으며 본 연구를 통해 개발된 진단장치는 사고를 초래할 수 있는 열화의 효율적이고 경제적인 선별 및 관리에 유용한 설비가 될 수 있음을 알았다.

절연진단시험을 이용한 고전압전동기 운영환경에 따른 절연특성분석 (Insulation Characteristic Analysis According to Operation Environment of High Voltage Motor Using Insulation Diagnostic Test)

  • 오봉근;김현일;장정호;이광호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.214-216
    • /
    • 2008
  • 회전기 고정자권선 절연물은 전기적, 기계적, 열적, 환경적 열화요인이 단독 또는 복합적으로 작용하여 열화된다. 본 논문에서는 실제 산업현장에서 운영중인 고전압 전동기의 운영환경을 조사하여 건조환경에서 운영중인 전동기와 다습환경에서 운영중인 전동기에 대하여 절연진단시험을 실시하고 각 시험에서 도출된 절연진단인자를 비교하여 환경적 열화요인이 우세한 운영환경에 따른 절연물의 특성변화를 분석하였다.

  • PDF

6.6 kV 케이블의 절연저항 측정을 위한 부하전류 및 온도 측정 (Load Current and Temperature Measurement for Measuring the Insulation Resistance of the 6.6 kV Cable)

  • 박용규;조영식;이관우;엄기홍;박대희
    • 한국전기전자재료학회논문지
    • /
    • 제28권1호
    • /
    • pp.46-50
    • /
    • 2015
  • The cable degradation process is largely divided into three steps; Step 1 : Thermal degradation, Step 2 : Weibull degradation, Step 3 : Partial discharge. it is progress in step order. This article aims to explain the process of cable degradation using the method of insulation resistance and accordingly to compose and manufacture a system of measuring the life of electrical cable. Before measuring the insulation resistance, a system of measuring the temperature and current of cables was made, and the established system was installed for test on the site of a power plant to collect the measured data. The current sensor was used TFC30P80A-CL420, and temperature sensor was used the DK-1270 PT100 sensor as RTD sensor. When measured the temperature and the load current at the same position, was confirmed that in case of the load current value was high, also temperature value high. Therefore, the correlation between load currents and temperature was verified, and the analysis of diagnostic data was evaluated, which could be utilized in identifying the fault condition of cable systems.