• Title/Summary/Keyword: Insulated switchgear

Search Result 234, Processing Time 0.032 seconds

Identification of Partial Discharge Defects based on Back- Propagation Algorithm in Eco-friendly Insulation Gas

  • Sung-Wook Kim
    • Journal of information and communication convergence engineering
    • /
    • v.21 no.3
    • /
    • pp.233-238
    • /
    • 2023
  • This study presents a method for identifying partial discharge defects in an eco-friendly gas insulated system using a backpropagation algorithm. Four partial discharge (PD) electrode systems, namely, a free-moving particle, protrusion on the conductor, protrusion on the enclosure, and voids, were designed to simulate PD defects that can occur during the operation of eco-friendly gas-insulated switchgear. The PD signals were measured using an ultrahigh-frequency sensor as a nonconventional method based on IEC 62478. To identify the types of PD defects, the PD parameters of single PD pulses in the time and frequency domains and the phase-resolved partial discharge patterns were extracted, and a back-propagation algorithm in the artificial neural network was designed using a virtual instrument based on LabVIEW. The backpropagation algorithm proposed in this paper has an accuracy rate of over 90% for identifying the types of PD defects, and the result is expected to be used as a reference database for asset management and maintenance work for eco-friendly gas-insulated power equipment.

Dielectric Properties of Epoxy/Micro-sized Alumina Composite and of Epoxy/Micro-sized/Nano-sized Alumina Composite

  • Park, Jae-Jun
    • Transactions on Electrical and Electronic Materials
    • /
    • v.16 no.6
    • /
    • pp.338-341
    • /
    • 2015
  • Epoxy/micro-sized alumina composite was prepared, and the effects of alumina content on the dielectric properties were investigated in order to develop an insulation material for gas-insulated switchgears (GIS). Nano-sized alumina (average particle size: 30 nm) was also incorporated into the epoxy/micro-sized alumina composite. Dielectric tests were carried out in ASTM D 150, and capacitance (Cp) and dielectric loss (tanδ) were measured. The dielectric constant increased with increasing alumina content in the epoxy/micro-alumina system and the epoxy/micro-alumina/nano-alumina system. As 1,3-diglycidyl glyceryl ether (DGE) content increased, the dielectric constant decreased and dielectric loss increased. This ocurred as a result of the weak electric field enhancement due to homogeneous dispersion of micro- and nano-sized alumina particles in an epoxy composite.

A Study on the Elimination of Temporary overvoltage Due to Ferroresonance at Gas Insulated Switchgear (Gas 색연(絶綠) 개폐장치(開閉裝置)의 철공진(鐵共振) 제어대책(制御對策)에 관한 연구(硏究))

  • Kim, S.K.;Kim, T.S.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05b
    • /
    • pp.216-221
    • /
    • 2000
  • This paper describes the analysis results on the PT ferroresonance at 154 kV GIS (gas Insulated substation by EMTP(Electro- magnetic Transient Program). We had simulated the PT ferroresonance between a potential transformer(PT) and an open circuit breaker's grading capacitance. The ferroresonance leads to very large power frequency overvoltages on PT bus and subsequent insulation failure. The large power can be supplied to the PT by the high voltage on the opened circuit due to the grading capacitance and equivalent capacitance of the buses during the ferroresonance. The damping circuit connected on the secondary winding were considered in the model. The actual countermeasure include a saturable inductor and a resistor series-mounted, but the 2 ohms of damping resistance was used in the computationl model.

  • PDF

Analysis of Transient Overvoltages within a 345kV Korean Thermal Plant

  • Yeo, Sang-Min;Kim, Chul-Hwan
    • Journal of Electrical Engineering and Technology
    • /
    • v.7 no.3
    • /
    • pp.297-303
    • /
    • 2012
  • This paper presents the simulation results for the analysis of a lightning surge, switching transients and very fast transients within a thermal plant. The modeling of gas insulated substations (GIS) makes use of electrical equivalent circuits that are composed of lumped elements and distributed parameter lines. The system model also includes some generators, transformers, and low voltage circuits such as 24V DC rectifiers and control circuits. This paper shows the simulation results, via EMTP (Electro-Magnetic Transients Program), for three overvoltage types, such as transient overvoltages, switching transients, very fast transients and a lightning surge.

가스절연 개폐장치에서 전극 및 경사 유전율 고체 스페이서의 형상 변경

  • Ju, Heung-Jin;Go, Gwang-Cheol
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.11a
    • /
    • pp.230-230
    • /
    • 2009
  • 가스절연 개폐장치 (Gas Insulated Switchgear : GIS)의 고체 스페이서에 경사 기능성 재료 (Functionally Graded Material : FGM)가 적용될 때, 절연성능이 크게 향상된다. 본 논문에서는 FGM 스페이서가 적용된 GIS의 전극 및 스페이서의 형상을 변경하여 최대전계를 완화시켰다. 이를 위해 완전요인실험 (Full Factorial Design : FFD)과 결합된 반응표면법 (Response Surface Methodology : RSM)의 최적화기법을 이용하여, 전극 및 스페이서의 최적 형상을 설계하였다.

  • PDF

Reliability Assessment of Medium Voltage Gas Insulated Switchgear (배전용 가스개폐기 신뢰성 평가 연구)

  • Kwon, Tae-Ho;Kim, Dong-Myung;Lee, Do-Hoon
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.2089_2090
    • /
    • 2009
  • 본 논문은 한전에서 사용되는 25.8kV 가스 절연 부하개폐기(이하 개폐기)에 대해 장기과통전시험, 부하전류 개폐 및 접점마모시험, 가스 기밀재 가속열화시험을 통해 신뢰성을 평가하였다. 국내 개폐기의 신뢰성 및 수명에 대한 척도를 평가한 결과, 모든 시료가 $B_{10}$ 수명 20년 이상을 보증할 수 있는 것으로 나타났다.

  • PDF

Grounding System Design of GIS type AC Substation using Personal Computer (P.C.에 의한 GIS형 AC Substation의 접지계 설계)

  • Yim, Han-Suck;Kim, Wang
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.4 no.1
    • /
    • pp.46-53
    • /
    • 1990
  • GIS(Gas-Insulated Switchgear)형 옥내변전소에 있어서 접지계의 구성은 접지도체를 포설할 수 있는 면적이 협소하기 때문에 특별한 설계방법이 요구된다. 본 논문에서는 접지망의 전위해석과 축소형 변전소의 접지계 설계기법을 제시하였고, 아울러 컴퓨터 시뮬레이션을 위한 프로그램을 작성하고 그 시뮬레이션 결과를 측정치와 비교하여 프로그램의 타당성을 입증하였다.

  • PDF

UHF signals produced by motion of aluminium particles in GIS (GIS 내 알루미늄 파티클의 거동에 따른 UHF 신호발생 특성)

  • Yoon, Jin-Yeol;Park, Ki-Jun;Goo, Sun-Geun;Han, Sang-Ok
    • Proceedings of the KIEE Conference
    • /
    • 2000.11c
    • /
    • pp.525-527
    • /
    • 2000
  • Ultra high frequency (UHF) signals caused by the bouncing motion of aluminium particles in the 352 kV gas-insulated switchgear (GIS) test chamber were measured in order to investigate the signal pattern against the applied voltage phase and ultra sonic signals.

  • PDF