• Title/Summary/Keyword: Impedance locus

Search Result 18, Processing Time 0.021 seconds

Development of an Impedance Locus Model for a Protective Relay Dynamic Test with a Digital Simulator

  • Kim, Soo-Nam;Lee, Myoung-Soo;Lee, Jae-Gyu;Rhee, Sang-Bong;Kim, Kyu-Ho
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.2
    • /
    • pp.167-173
    • /
    • 2011
  • This paper presents a method for the development of the impedance locus to test the dynamic characteristics of protective relays. Specifically, using the proposed method, the impedance locus can comprise three impedance points, and the speed of impedance trajectory can be adjusted by frequency deviation. This paper is divided into two main sections. The first section deals with the configuration of impedance locus with voltage magnitude, total impedance magnitude, and impedance angle. The second section discusses the control of the locus speed with the means of the deviation between two frequencies. The proposed method is applied to two machine equivalent systems with offline simulation (i.e., PSCAD) and real-time simulation (i.e., real-time simulation environment) to demonstrate its effectiveness.

Development of Impedance Locus Model for Protective Relay Dynamic Test (보호 계전기 동특성 테스트를 위한 임피던스 궤적 모델 개발)

  • Kim, Su-Nam;Lee, Jae-Gyu;Lee, Myeong-Su;Yu, Seok-Gu
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.9
    • /
    • pp.451-459
    • /
    • 2002
  • This paper presents a method for modelling of the impedance locus in order to test the protective relay with dynamic. This paper has the two parts, the first part is the configuration of impedance locus with voltage magnitude, total impedance magnitude and angle. And the second part is the control of the locus speed with deviation of two frequencies. The proposed method is applied to two machine equivalent system with PSCAD/EMTDC to show its effectiveness.

Realtime Measurement of Impedance Locus using Impedance Spectroscopy: How Many and How Low Frequencies Are Required \ulcorner

  • T., Fukumoto;G. M., Eom;S., Ohba;N., Hoshimiya
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2004.10a
    • /
    • pp.1194-1197
    • /
    • 2004
  • High temporal-resolution and accurate measurement of skin impedance locus provides useful data for the identification of the physiological/psychological changes and also the identification of acupuncture point. An impedance spectroscopy method using digitally constructed current waveform consisting of many frequency components (multiples of 1Hz) was reported3. The time resolution of the method depends on the lowest frequency used in the waveform construction, and therefore, the measurement would be faster if the lowest frequency is the higher. However, it was not clear that how many and how low frequencies must be used for the estimation of the skin impedance parameters from which the impedance locus can be drawn. This study shows the relationship between the estimation error of the impedance parameters and the frequency coverage of the spectroscopy. The results of this study are expected to serve as the reference of the frequency selection in the impedance spectroscopy.

  • PDF

Application Analysis for Loss of Excitation Relay of Generator Protection (발전기 보호용 계자상실 계전기의 적용 분석)

  • Oh, Yong-Taek;Park, Chul-Won
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.63 no.4
    • /
    • pp.322-326
    • /
    • 2014
  • Recently, the LOE(loss of excitation) incidents are occurred in domestic synchronous generator frequently, the synchronous generator protection system has been much attention for the LOE protection of the incidents that threats synchronous generators and power systems. This paper was showed the characteristics and practices of distance relay that widely used LOE protection relaying in generator. Firstly, the operating characteristics and the impedance locus for LOE of the generator protection were introduced. Even if the conventional simulation program is used for modeling, but it is difficult to implement a LOE modeling and simulation of synchronous generator. So, the LOE relay operation data collected from thermal power plant and nuclear power plant in real fields were analyzed. By reviewing the applications of GE Mho relays, the reliability of LOE for synchronous generator protection in domestic were improved.

A Study on the Oscillation Region and the Variation of Negative Resistance in Transistor Oscillators (트란지스터 발진기의 발진영역과 부저항의 변화에 관한 연구)

  • 이종각
    • Journal of the Korean Institute of Telematics and Electronics
    • /
    • v.8 no.3
    • /
    • pp.15-26
    • /
    • 1971
  • The paper presents a new method for analyzing oscillation regions of transistor oscillators. In transistor feedback oscillators oscillation region appears as a circle in feedback impedance complex plane. When the resistive component of feedback impedance is fixed and the reactive component of feedback impedance is varied or vice versa, the locus of maximum negative output conductance becomes hyperbola. In transistor crystal oscillators oscillation region is determined by two circles which make real part and imaginary part of input impedance zero in load impedance complex plane. When the resistive compoment of load impedance is fixed and the reactive colnponent of load impedance is varied or vice versa, the loci of maximum or minimum resistive component of input impedance become straight lines.

  • PDF

An Algorithm of Predicting the Zone 3 Trip Time of Distance Relay by using PMU Data when Power Systems Face Cascaded Event on Transmission System (송전 계통의 광역정전 징후 시 PMU 취득 데이터를 이용한 거리계전기 Zone3 동작시간 예측 알고리증)

  • Kim, Jin-Hwan;Lim, Il-Hyung;Lee, Seung-Jae;Choi, Myeon-Song;Kim, Tae-Wan;Lim, Seong-Il;Kim, Sang-Tae
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.12
    • /
    • pp.2303-2310
    • /
    • 2009
  • Defense systems are needed to prevent catastrophic failures of a power grid due to cascaded events. Cascaded events can be attributed to improper operations of protective relays. Especially, it is the most dangerous problem that trips of backup relays by overload. In this paper, a new algorithm of predicting Zone 3 acting time of distance relay is proposed using the real time synchronized data from PMUs on the transmission system when the power system is danger. In the proposed, some part of the power system are outage when some unexpected fault in the power system, the algorithm will monitor the impedance locus of distance relay. At this time, if there is a big change of Impedance locus, the algorithm will calculate the Zone 3 acting time of the distance relay by the over load. In the case studies, the estimation and simulation network have been testified and analysed in Matlab Simulink.

A study of impedance relay operation and voltage instability caused by over load of neighborhood line at contingency of heavy load line (증조류 선로 고장시 인접선로 과부하에 의한 거리계전기 동작 및 전압불안정 현상 연구)

  • Yun, Ki-Seob;Lee, Hyoung-Han;Kim, Chang-Gon;Ahn, Bo-Soon
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.359-361
    • /
    • 2005
  • This paper presents the method of countermeasures before voltage collapse by load encroachment(impedance of load ability on R-X locus decrease toward zero point) and describes a study of impedance relay(zone-3) operation and voltage instability caused by over load of neighborhood line at contingency of heavy load line.

  • PDF

THE COMPLEX PERMEABILITY AND MATCHING FREQUENCY OF FERRITE MICROWAVE ABSORBER

  • Shin, Jae-Young;Oh, Jae-Hee
    • Journal of the Korean Magnetics Society
    • /
    • v.5 no.5
    • /
    • pp.800-804
    • /
    • 1995
  • The complex permeability dispersions and the microwave absorbing phenomena are investigated in ferrite microwave absorber. The complex permeability of NiZn ferrite, NiZnCo ferrite, and Y-type hexagonal ferrite were measured in 200MHz-14GHz range. Two types of resonances, the domain wall and the spin rotational resonance, were observed. With a ferrite particle with a diameter of about $1\;\mu\textrm{m}$, only spin rotational resonance were observed. The theoretical matching frequency is determined by plotting the measured complex permeability locus on the impedance matching solution map. One or two impedance matching phenomena are observed in the ferrite absorbers according to their complex permeability loci on the impedance matching solution map. The first matching frequency, found in the ferrite-rubber composites, which was higher than that of spin rotational resonance, increased with spin rotational resonance frequency.

  • PDF

Electrochemical Impedance Study for Selective Dissolution of a Cu-Zn Alloy

  • Hoshi, Y.;Tabei, K.;Shitanda, I.;Itagaki, M.
    • Corrosion Science and Technology
    • /
    • v.15 no.6
    • /
    • pp.311-313
    • /
    • 2016
  • The anodic dissolution behavior of copper and brass in an electrolyte solution of 0.5M NaCl containing 0.5 mM $NaHCO_3$ was investigated by electrochemical impedance spectroscopy. The Nyquist plots of the copper impedance described a small loop in the high-frequency range and a large locus in the low-frequency range. Additionally, the features of the impedance spectrum of the brass were similar to those of the copper. This indicates that the copper-enriched layer formed on the brass surface due to the selective dissolution of the zinc from the surface. In addition, the rest potential and the anodic polarization curve for each sample were measured in order to discuss the selective dissolution of the zinc from the brass surface.

Measurement and Explanation of DC/RF Power Loci of an Active Patch Antenna

  • Mcewan, Neil J.;Ali, Nazar T.;Mezher, Kahtan A.;El-Khazmi, Elmahdi A.;Abd-Alhameed, Raed A.
    • ETRI Journal
    • /
    • v.33 no.1
    • /
    • pp.6-12
    • /
    • 2011
  • A case study of an active transmitting patch antenna revealed a characteristic loop locus of DC power versus RF output power as drive frequency was varied, with an operational bandwidth substantially smaller than the impedance bandwidth of the radiator. An approximate simulation technique, based on separation of the output capacitance of the power transistor, yielded easily visualized plots of power dependence on internal load impedance, and a simple interpretation of the experimental results in terms of a near-resonance condition between the output capacitance and output packaging inductance.