• Title/Summary/Keyword: Hts Transformer

Search Result 123, Processing Time 0.023 seconds

AC Loss of the Double Pancake Winding by External Field (외부자계 인가시 더블팬케이크 권선에서 발생하는 교류손실)

  • Lee, Hee-Joon;Lee, Seung-Wook;Cha, Guee-Soo;Lee, Ji-Kwang
    • Proceedings of the KIEE Conference
    • /
    • 2001.04a
    • /
    • pp.99-101
    • /
    • 2001
  • Magnetization loss which is generated in HTS wire varies with the direction of the external magnetic field. This paper calculates the magnetization loss in an HTS transformer winding, where effects of the direction of magnetic field are considered. Kim model is used to consider the variation of the critical current with magnetic field and Brandt equation is used to calculate the loss by perpendicular magnetic field in transformer winding. Magnetization loss in an HTS transformer can be calculated more precisely with this paper.

  • PDF

Insulating Design and Test of 22.9kV Class Mini-Model Transformer Considering AC Loss (AC Loss를 고려한 22.9kV급 Mini-Model 변압기의 절연 설계 및 시험)

  • 백승명;정종만;곽동순;김해종;석복렬;김상현
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.8
    • /
    • pp.420-424
    • /
    • 2004
  • This paper presents experimental data from model windings with different arrangement of coil in order to provide information to design a 22.9kV class HTS transformer. Before experiment, the composite insulation of two different type of HTS transformers are investigated. The first basic of investigation is a breakdown characteristic of liquid nitrogen and flashover characteristic on the GFRP surface under ac and impulse, The second investigation is insulation design, manufacture and test of model windings. These include a AC withstand voltage test of 50 kV rms and a lighting impulse test of 150 kV at peak.

Simulated winding temperature distribution of HTS transformer cooled by sub-cooled liquid nitrogen

  • Han, J.H.;Choi, K.D.;Kim, T.Y.;Chang, T.;Kim, W.S.;Kim, S.H.;Hahn, S.Y.;Kim, S.R.
    • Progress in Superconductivity and Cryogenics
    • /
    • v.6 no.4
    • /
    • pp.51-54
    • /
    • 2004
  • A 1 MV A single phase high temperature superconducting (HTS) transformer was manufactured. In order to reduce AC loss generated in the HTS winding, winding was concentrically arranged. Operation temperature is set at 65K to increase the critical current and reduce the amount of HTS tape usage and the volume. The cryogenic system which consists of main cryostat with the windings and secondary cryostat with 2 GM coolers and cryopump on top and heat exchanger inside is also designed and the cooling performance is simulated with Fluent. Temperature distribution of the windings is investigated whether the windings are kept under designed operation temperature.

Magnetization Losses of the HTS Stacked Tapes at Various Gap between Tapes (고온초전도 적층선재에서의 층간 거리에 따른 자화손실)

  • 최명섭;박명진;차귀수;이지광
    • Proceedings of the Korea Institute of Applied Superconductivity and Cryogenics Conference
    • /
    • 2003.02a
    • /
    • pp.250-253
    • /
    • 2003
  • Rise of the current level at power applications, such as, transformer, motor and power cable, need for using stacked HTS tapes. In this paper, we measured losses of the stacked HTS tapes. Three different types of the stacks which were made of 2 tapes, 3 tapes and 4 tapes, were tested Perpendicular magnetic field was applied to the HTS stacks as the external magnetic field. Effects of the gap between HTS tapes were examined.

  • PDF

Conceptual Design and 3-D electromagnetic analysis of 1MVA HTS Transformer (1MVA 고온 초전도 변압기 개념설계 및 3차원 전자장 해석)

  • Park, Chan-Bae;Kim, Woo-Seok;Hahn, Song-Yap;Choi, Kyeong-Dal;Joo, Hyeong-Gil;Hong, Gye-Won
    • Proceedings of the KIEE Conference
    • /
    • 2002.07b
    • /
    • pp.943-945
    • /
    • 2002
  • This paper presents conceptual design and 3-D electromagnetic analysis of 1MVA transformer with BSCCO-2223 High Tc Superconducting (HTS) tapes. The rated voltages of each sides of the transformer are 22.9 kV and 6.6 kV, and double pancake windings were adopted. High voltage and Low voltage sides were composed of several double pancake windings. Four HTS tapes were wound in parallel for the windings of low voltage side and were transposed in order to distribute the currents equally in each conductor. The transformer core was designed as a shell type core made of laminated silicon steel plates and the core is separated with the windings by a cryostat with Fiberglass Reinforced Plastics(FRP). A sub-cooling system using $LN_2$ were designed to maintain the coolant temperature of 65K. Finally perpendicular components of magnetic field applied to tapes were calculated 0.24T in the rated operation using 3-D analysis. A real 1MVA HTS transformer will be manufactured in near future based on the design parameters presented in this paper.

  • PDF

Critical Current Characteristic of HTS Stacked Tapes in External Field (외부자계 인가 시 적층 고온초전도선재의 임계전류 특성)

  • Lee, Seung-Wook;Park, Myung-Jin;Sim, Jung-Wook;Cha, Guee-Soo;Lee, Ji-Kwang
    • Proceedings of the KIEE Conference
    • /
    • 2002.07b
    • /
    • pp.903-905
    • /
    • 2002
  • According to the improvement of the HTS wires performance, several types of HTS superconducting machines, such as, transformer, motors, current limiters, and transmission cables are being developed. Degradation of the critical current in HTS tape owing to external field is very important subject in developing the HTS machines. Considering that stacked HTS tapes are widely used to develop the large HTS machines, the critical current characteristics of stacked HTS tapes in external field need to be examined. In this paper, we present critical current characteristics of 4-stacked HTS tapes which are exposed to the external field. HTS tape with critical current of 4-stacked HTS tape. Test results prove that four times critical current of single HTS tape is smaller than critical current of stacked HTS tape in high external field.

  • PDF

10kVA high $T_c$ Superconducting Power Transformer with Double Pancake Windings (더블팬케이크 권선형 10kVA 고온초전도 변압기)

  • Lee, Hui-Jun;Cha, Gwi-Su;Lee, Ji-Gwang;Han, Song-Yeop;Ryu, Gyeong-U;Choe, Gyeong-Dang
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.50 no.2
    • /
    • pp.65-72
    • /
    • 2001
  • This paper presents the design and test results of a 10kVA single phase HTS transformer which is operating at 77K. Double pancake windings with BSCCO -2223 HTS tape and GFRP cryostat with room temperature bore are used in the transformer. Four double pan cake windings were used in pancake windings are connected in parallel to conduct the secondary current of 45.4A. the rated voltages of each winding are 440/220V. Numerical calculation using Finite Element Method was used to evaluated the performance of each arrangement. Considering the magnetizing reactance, leakage reactance, electrical insulation and the circulating current in low voltage winding which had two windings in parallel, HLLH arrangement was finally chosen. Estimation of the AC loss, magnetizing loss and self field loss, in the design stage, where effects of perpendicular field and parallel field are considered. Room temperature bore type cryostat has been constructed and its heat loss was measured.

  • PDF