• Title/Summary/Keyword: Horizontal tubes

Search Result 169, Processing Time 0.025 seconds

Effects of Hydrophilic Surface Treatment on Evaporation Heat Transfer at the Outside Wall of Horizontal Tubes (친수성 표면처리가 수평관 외벽의 증발열전달에 미치는 영향)

  • 박노성;황규대;강병하;정진택
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.5
    • /
    • pp.525-532
    • /
    • 2000
  • Evaporation heat transfer characteristics have been investigated experimentally when distilled water is sprayed on the outside wall of horizontal tubes in a evaporator. This problem is of particular interest in the design of evaporator of an absorption system. Hydrophilic surface treatment was employed to increase the wettability on copper tubes. The results indicate that evaporation heat transfer with hydrophilic tubes is shown to be 25-44% higher than that with bare tubes at evaporation pressure of 31.8 Torr(evaporation temperature$ 30^{\circ}C). Evaporation heat transfer rates of hydrophilic treatment tubes are improved substantially, comparing with those of conventional copper tubes in the wide range of operating parameters, such as water inlet temperatures, water mass flow rates and evaporation pressures.

  • PDF

Study on Extraction of the Center Point of Steam Generator Tubes (증기발생기 세관의 중심좌표추출에 대한 연구)

  • 조재완;김창회;서용칠;최영수;김승호
    • Proceedings of the IEEK Conference
    • /
    • 2002.06d
    • /
    • pp.263-266
    • /
    • 2002
  • This paper describes extraction procedure for the center coordinates of steam generator tubes of Youngkwang NPP #6, which are arrayed in triangular patterns. Steam generator tube images taken with wide field-of-view lens and low-light lamp mounted on a ccd camera tend to have low contrast, because steam generator is sealed and poorly illuminated. The extraction procedures consists of two steps. The first step is to process the region with superior contrast in entire image of steam generator tubes and to extract the center points. Using the extracted coordinates in the first step and the geometrical array characteristics of tubes lined up in regular triangle forms, the central points of the rest region with low contrast are estimated. The straight lines from center point of a tube to neighbour points in horizontal and 60, 120$^{\circ}$ degree directions are derived. The intersections of straight line In horizontal direction and slant line in regular triangle direction are selected as the center coordinates of steam generator tubes. The Chi-square interpolation method is used to determine the line's coefficients in horizontal and regular triangle direction.

  • PDF

Heat Transfer Enhancement Characteristics for Falling-Film Evaporation on Horizontal Enhanced Tubes with Aqueous LiBr Solution (LiBr 수용액을 이용한 수평관 유하액막 증발의 촉진관 전열향상 특성)

  • Kim, Dong Kwan;Kim, Moo Hwan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.22 no.9
    • /
    • pp.1267-1276
    • /
    • 1998
  • Falling-film evaporation experiments with aqueous lithium bromide (LiBr) solution were performed to investigate the heat transfer characteristics of enhanced copper tubes. Enhanced tubes (a knurled tube, a spirally grooved tube, and a tube coated with $20{\mu}m$ aluminum particles) and a bare tube were selected as test specimens. Averaged evaporation fluxes of water were obtained from horizontal tubes with various film Reynolds numbers, system pressures, LiBr concentrations and degrees of wall superheat. The enhanced performance of steam generation was compared between tubes with varying parameters. The knurled tube geometry showed the most excellent performance among the tubes tested. The specified enhanced tubes were more useful for generating steam on a low grade heat source such as waste heat.

Condensation Heat Transfer to Rivulets of Condensate on Horizontal tubes (관표면에서의 곡면응축막의 열전달)

  • Bae, Soon-Hoon;Choe, Young-Don
    • The Magazine of the Society of Air-Conditioning and Refrigerating Engineers of Korea
    • /
    • v.4 no.1
    • /
    • pp.18-22
    • /
    • 1975
  • A simple analysis has been made of the condensation of vapor onto rivulets of condensate which are formed by non-wetting narrow Taflon strips circumferencially located in a certain interval on horizontal tubes. Heat transfer to the rivulets increased over $50\%$ above that to the Nusselt uniform thickness film. Results are directly applicable to condenser tubes in large steam condensers.

  • PDF

Two-Phase Flow Distribution and Phase Separation Through Both Horizontal and Vertical Branches

  • Tae, Sang-Jin;Keumnam Cho
    • Journal of Mechanical Science and Technology
    • /
    • v.17 no.8
    • /
    • pp.1211-1218
    • /
    • 2003
  • The present study investigated two-phase flow distribution and phase separation of R-22 refrigerant through various types of branch tubes. The key experimental parameters were the orientation of inlet and branch tubes (horizontal and vertical), diameter ratio of branch tube to inlet tube (1 and 0.61), mass flux (200-500 kg/㎡s), and inlet quality (0.1-0.4). The predicted local pressure profile in the tube with junction was compared and generally agreed with the measured data. The local pressure profile within the pressure recovery region after the junction has to be carefully investigated for modeling the pressure drop through the branch. The equal flow distribution case can be found by adjusting the orientation of the inlet and branch tubes and the diameter ratio of the branch tube to the inlet tube. The T-junction with horizontal inlet and branch tubes showed the nearly equal phase distribution ratio. The quality at the branch tube varied from 0 to 1 as the orientation of the branch tube changed, while it varied within${\pm}$50% as the orientation of the inlet tube changed.

Experimental Investigation of the Combined Effects of Heat Exchanger Geometries on Nucleate Pool Boiling Heat Transfer in a Scaled IRWST (열교환기 형상이 축소한 IRWST 내부의 풀핵비등에 미치는 복합적인 영향에 대한 실험적 연구)

  • Kang, Myeong-Gie;Chun, Moon-Hyun
    • Nuclear Engineering and Technology
    • /
    • v.28 no.1
    • /
    • pp.1-16
    • /
    • 1996
  • In an effort to determine the combined effects of major parameters of heat exchanger tubes on the nucleate pool boiling heat transfer in the scaled in-containment refueling water storage tank (IRWST), a total of 1,966 data for q'quot; versus ${\Delta}T$ has been obtained using various combinations of tube diameters, surface roughness, and tube orientations. The experimental results show that (1) increased surface roughness enhances heat transfer for both horizontal and vertical tubes, (2) the two heat transfer mechanisms, i.e.,enhanced heat transfer for both horizontal and vertical tubes, (2) the two heat transfer mechanisms, i.e., enhanced heat transfer due to liquid agitation by bubbles generated and reduced heat transfer by the formation of large vapor slugs and bubble coalescence are different in two regions of low heat fluxes (q'quot; $\leq$50kW/$m^2)$ and high heat fluxes (q'quot; $\geq$50kW/$m^2)$ depending on the orientation of tubes and the degree of surface roughness, and (3) the heat transfer rate decreases as the tube diameter is increased for both horizontal and vertical tubes, but the effect of tube diameter on the nucleate pool boiling heat transfer for vertical tubes is greater than that for horizontal tubes. Two empirical heat transfer correlations for q'quot;, one for horizontal tubes and the other for vertical tubes, are obtained in terms of surface roughness $({\varepsilon})$ and tube diameter (D). In addition, a simple empirical correlation for nucleate pool boiling heat transfer coefficient $(h_b)$ is obtained as a function of heat flux (q'quot;) only.ucleate pool boiling heat transfer coefficient $(h_b)$ is obtained as a function of heat flux (q'quot;) only.

  • PDF

Experimental Study for Ice Formation around Two Horizontal Circular Tubes (수평 2열 원통관 주위의 동결형상에 관한 연구)

  • Yoon, J.I.;Kim, J.D.;Toyofumi, Kato;Oh, H.K.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.7 no.1
    • /
    • pp.89-97
    • /
    • 1995
  • Experimental study was performed for free convection and ice formation around two horizontal circular tubes which were placed vertically. Temperature and velocity distributions were visualized with real time holographic interferometry technique and tracer method. When water was cooled, super cooled region was formed around cooling pipe. It was found that flow induced by free convection always directed downwards when the coolant temperature was low, while it directed upwards when the coolant temperature was comparably high though it directed downwards initially. Flow phenomena with free convection were investigated in detail with varying cooling rate and length between cooling pipes. And growing process of dense ice was also investigated. Dendritic ice is suddenly formed within a supercooled region, and a dense ice layer begins to develop from the cooling wall.

  • PDF

Effects of Tube Diameter on Nucleate Pool Boiling Heat Transfer (튜브 직경이 풀핵비등 열전달에 미치는 영향)

  • Kang, Myeong-Gie
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.24 no.7
    • /
    • pp.930-937
    • /
    • 2000
  • A series of data sets for the heat transfer coefficient versus wall superheat has been obtained experimentally using various combinations of tube diameters ($9.7{\sim}25.5mm$), surface roughness ($15.1{\sim}60.9nm$), and tube orientations (horizontal and vertical) to obtain effects of tube diameters on nucleate pool boiling heat transfer for the saturated water at atmospheric pressure. In addition, the results are compared with the well known Cornwell and Houston's correlation for horizontal tubes to identify the deviation of the present experimental data from the correlation and the applicability of it to vertical tubes. The experimental results show that the heat transfer coefficient decreases as the tube diameter increases for both horizontal and vertical tubes and they are in good agreement with the Cornwell and Houston's correlation within ${\pm}20%$ scatter range.

Two-Phase Flow Distribution, Phase Separation and Pressure Drop in Multi-Microchannel Tubes (마이크로채널관 내 2상 유량분배, 상분리 및 압력강하)

  • Cho, Hong-Ki;Cho, Geum-Nam;Yoon, Baek;Kim, Young-Saeng;Kim, Jung-Hoon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.9
    • /
    • pp.828-837
    • /
    • 2004
  • The present study investigated two-phase flow distribution, phase separation and pressure drop in multi-microchannel tubes under adiabatic condition. The test section consisted of inlet and outlet headers with the inner diameter of 19.4㎜ and 15 parallel microchannel tubes. Each microchannel tube brazed to the inlet and outlet headers and had 8 rectangular ports with the hydraulic diameter of 1.32㎜. The key experimental parameters were orientation of header (horizontal and vertical), flow direction of refrigerant into the inlet header (in-line, parallel and cross flow) and inlet quality (0.1, 0.2 and 0.3). It was found that the orientation of the header had relatively large effect on the flow distribution and phase separation, while the inlet quality didn't affect much on them. The horizontal header showed the better flow distribution and phase separation characteristics than the vertical one. The parallel flow condition with the horizontal header showed the best performance for the flow distribution and phase separation characteristics under the test conditions. Two-phase pressure drops through the microchannel tubes with the horizontal header were higher than those of the microchennel tubes with the vertical header due to gravitational effect.

Experimental Investigation of Flow Boiling Heat Transfer of R-410A and R-134a in Horizontal Small Tubes

  • Pamitran, A.S.;Choi, Kwang-Il;Oh, Jong-Taek;Hrnjak, Pega
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1141-1146
    • /
    • 2009
  • Experimental investigation on two-phase flow boiling heat transfer of R-410A and R-134a in horizontal small tubes is reported. The pressure drop and local heat transfer coefficients were obtained over heat flux range of 5 to $40\;kW/m^2$, mass flux range of 70 to $600\;kg/m^2s$, saturation temperature range of 2 to $12^{\circ}C$, and quality up to 1.0 in test section with inner tube diameters of 3.0 and 0.5 mm, and lengths of 2000 and 330 mm, respectively. The section was heated uniformly by applying a direct electric current to the tubes. The effects of mass flux, heat flux, and inner tube diameter, on pressure drop and heat transfer coefficient are presented. The experimental results are compared against several existing correlations. A new boiling heat transfer coefficient correlation based on the superposition model for refrigerants in small tubes is developed.

  • PDF