• 제목/요약/키워드: High voltage switchgear

검색결과 79건 처리시간 0.037초

고전압 가스 차단기용 전자석 조작기에 대한 해석 (Analysis of New Type of Switchgear for High Voltage Gas Circuit Breaker)

  • 이승민;강종호;김래은;정현교
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.872-873
    • /
    • 2008
  • In this paper, a new type of switchgear, electro magnetic force driving actuator (EMFA), is developed and analyzed, applicable to high voltage gas circuit breaker (HGCB). Transient analysis is performed in order to obtain the dynamic characteristics of the EMFA. The distribution of static magnetic flux is obtained using the finite element method (FEM). The governing electric and kinematical equations are solved using the time difference method (TDM). Fabrication and experiments were performed in order to prove the applicability of HGCB for overall class. In comparing the experiment with simulated data, it is confirmed that analysis of the dynamic characteristics of EMFA is appropriate for design.

  • PDF

SPMSM을 이용한 '245kV 40kA GIS' 조작기 개발 (Development of drive mechanism for 245kV 40kA high-voltage Gas Insulated Switchgear(GIS) using SPMSM)

  • 정균하;서경보;김정배;서인영
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.980-981
    • /
    • 2008
  • Mechanical spring and hydraulic pressure operated mechanisms are applied in most of today's High Voltage Gas Insulated Switchgear(GIS)s. This paper proposes a new type of operation mechanism for GIS circuit breakers rated at 245kV and 40kA. The Motor-Direct-Drive-Mechanism (MDDM) has many advantages compared to conventional operating mechanisms. It has a very simple structure with only one moving part, low mechanical stress and audible noise. It also allows monitoring, operation speed control and self-diagnosis functions.

  • PDF

SPMSM을 이용한 245kV 40kA GIS 조작기 개발에 관한 연구 (A study on of drive mechanism for 245kV 40kA high-voltage Gas Insulated Switchgear(GIS) using SPMSM)

  • 정균하;오영진;여창호;서인영
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2007년도 하계학술대회 논문집
    • /
    • pp.114-116
    • /
    • 2007
  • Mechanical spring and hydraulic pressure operated mechanisms are applied in most of today's High Voltage Gas Insulated Switchgear(GIS)s. This paper proposes a new type of operation mechanism for GIS circuit breakers rated at 245kV and 40kA. The Motor-Direct-Drive-Mechanism (MDDM) has many advantages compared to conventional operating mechanisms. It has a very simple structure with only one moving part, low mechanical stress and audible noise. It also allows monitoring, operation speed control and self-diagnosis functions.

  • PDF

UHF Sensor를 이용한 SF6 절연 MV 개폐기의 부분방전 검출 시스템 (Partial Discharge Monitoring for $SF_6$ Insulated MV Switchgear using UHF sensors)

  • 이도훈;강원종;신양섭;김영근;오일성;김동명;권태호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.2040-2041
    • /
    • 2007
  • In this paper, the UHF PD(Partial Discharge) sensors for $SF_6$ insulated MV $SF_6$ switchgear have been proposed and related investigations have been performed in order to detect the PD which were produced inside the MV $SF_6$ switchgear. Firstly, the internal type UHF PD sensor based on spiral antenna theory has been developed. This type sensor is highly sensitive and has lowly effect on by on-site noise. Secondly, the external type UHF PD sensor was developed based on log periodic antenna concept. This type sensor is removable and detectable for operating switchgear. These sensors were designed and simulated using RF simulation tool. In order to verify the sensitivity of these sensors, we performed the on-site test using the mock-up switchgears including the artificial defects which were the protrusion on high voltage conductor, free moving metal particle and surface defect on insulator. These mock-up switchgear were installed on the test distribution line.

  • PDF

에폭시 수지를 이용한 전기 절연물의 기계적 해석 방법에 관한 연구 (The Study of Mechanical Analysis for Electric Insulator using Epoxy Resign)

  • 정대석;박창우;조정환;김정배
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 추계학술대회 논문집
    • /
    • pp.192-193
    • /
    • 2007
  • Epoxy resign is used to insulate electricity in the gas insulated switchgear. There were many research to find out characteristics of the epoxy resign. But there is a poor research for the mechanical investigations. In this paper, we made an experiment and evaluated mechanical properties with specimens of the epoxy resign. Using Spacer which is a part of high voltage switchgear, and we studied the structural analysis methods and made an overture a how to analysis in order to solve problems.

  • PDF

금속입자 오손시 $SF_6$가스의 절연파괴특성 (Breakdown Characteristics of $SF_6$ Gas under Particle Contaminated Conditions)

  • 김민규;문인욱;김익수;이형호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1995년도 추계학술대회 논문집 학회본부
    • /
    • pp.465-468
    • /
    • 1995
  • The gas-insulated switchgear(GIS) has made high-reliability, high-safety, compact substations possible by using $SF_6$ gas. They are likely to be further developed toward higher voltages and targer capacities, along with greater compactness and lower cost. Although $SF_6$ gas has excellent insulation performance, breakdown voltages are reduced by the conducting particles. Thus, extensive studies have been made on the breakdown characteristics of $SF_6$ gas in particle contaminated conditions. Experiments were carried out for fired particle and free particle in a coaxial electrode system with DC and AC voltages. This paper represents the experimental results of the processes involved in electrical breakdown in compressed $SF_6$ gas, where breakdown is initiated by conducting particles.

  • PDF

초고압 가스절연개폐기의 베이 컨트롤러 개발 및 성능시험 (The Development and the Performance Test of Bay Controller for the High-Voltage Gas Insulated Switchgear)

  • 우천희;이보인
    • 전기학회논문지P
    • /
    • 제59권2호
    • /
    • pp.179-184
    • /
    • 2010
  • The digital substation automation system has contributed hugely to increasing the stability of power systems by providing not only protection and control of power systems but diagnostic features alongside them. Digital substation automation systems in the scale of substations consist of integrated operation systems and intelligent electronic devices. The main intelligent electronic devices currently in use are digital protection relays and the bay controllers in Gas insulated switchgears. Proficiently accomplishing the coordination of protection within the power system as a means of ensuring reliability and contriving for the stability of power supply through connection of function, the application of bay controllers is crucial, which collectively manage the protection relay at the bay level in order to achieve both. In this research, the bay controllers to be used in high-voltage Gas insulated switchgear has been localized, and in particular, the logic function and editor required in order to minimize the complicated hardware-like cable connections in the local panel have been developed. In addition, to ensure the strength and reliability of the bay controller hardware developed herein, the type tests from KERI have been successfully completed.

초고압 절연 스페이서의 자동가압 겔화 성형 공정을 위한 경화 보압의 최적화 (Optimization of Curing Pressure for Automatic Pressure Gelation Molding Process of Ultra High Voltage Insulating Spacers )

  • 이찬용;조한구;이재형
    • 한국전기전자재료학회논문지
    • /
    • 제37권1호
    • /
    • pp.56-62
    • /
    • 2024
  • By introducing curing kinetics and chemo-rheology for the epoxy resin formulation for ultra-high voltage gas insulated switchgear (GIS) Insulating Spacers, a study was conducted to simulate the curing behavior, flow and warpage analysis for optimization of the molding process in automatic pressure gelation. The curing rate equation and chemo-rheology equation were set as fixed values for various factors and other physical property values, and the APG molding process conditions were entered into the Moldflow software to perform optimization numerical simulations of the three-phase insulating spacer. Changes in curing shrinkage according to pack pressure were observed under the optimized process conditions. As a result, it was confirmed that the residence time in the solid state was shortened due to the lowest curing reaction when the curing holding pressure was 3 bar, and the occurrence of deformation due to internal residual stress was minimized.

SiO2와 Al2O3를 충진재료로 사용하는 초고압 GIS용 에폭시 절연물 베리어의 전기적 및 기계적 특성에 관한 연구 (A Study on Electrical and Mechanical Properties of Epoxy Insulation Barrier for High Voltage GIS Using a Filler of SiO2 and Al2O3)

  • 서왕벽;배동호
    • 한국전기전자재료학회논문지
    • /
    • 제28권6호
    • /
    • pp.379-383
    • /
    • 2015
  • Some insulating materials are organized and analyzed with variables to obtain the optimized profile of encapsulated three phase of epoxy barrier which is applied to gas compartment and supporting conductors for high voltage GIS (gas insulated switchgear). The high voltage GIS is used in electrical power system and operating reliability. In this paper, optimization possibility of barrier shape including both electrical insulation performance and mechanical strength, premised on that condition minimizing volume and light weight should be kept for high voltage GIS, could be achieved by analysis simulation. As a result, filling material which is lower permittivity such as $SiO_2$ instead of $Al_2O_3$ properly to the epoxy material, can be improved to increase the electrical insulation performance and mechanical strength for an optimized profile barrier of a high voltage GIS.

특고압 인입공사 시공방법연구 (A Study of Construction method of installing High-Voltage Lead-in)

  • 오승철;박수홍
    • 한국전자통신학회논문지
    • /
    • 제6권1호
    • /
    • pp.129-134
    • /
    • 2011
  • 일상생활에 필요한 전력공급을 제공받기 위해서는 한전 책임분기점 전주에서 전기실 수변전설비까지 시공방법을 설계도면을 숙지하고 현장작업 조건을 충분히 파악하여 한전 한전책임분계점 위치를 한전측과 협의하여 결정하고 전주에 책임분계점(수전점)의 지중케이블 입상주을 설치하고 옥외관로터파기 및 맨홀을 설치하며 파상형경질폴리에틸렌 전선관(125C) 및 CNCV-W특고케이블을 포설하고 전기실 수배전반설치까지의 공사과정을 면밀히 분석 검토하여 시공한다. 공동주택 전력계통의 핵심적인 부분인 한전 책임분계점에서 부터 옥외관로공사, 특고압지중전선로 및 수배전반설치까지 실제 현장에서 직접 시공한 내용을 기초로 하여 공동주택의 특고압인입공사 및 수배전반 설치에 대한 시공방법의 내용을 제시 하였다.