Mechanical Fracture Characteristic of Epoxy Insulation Barrier for High Voltage GIS (초고압 GIS용 에폭시 절연물 배리어 파단 특성)

  • Suh, Wang Byuck
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.30 no.10
    • /
    • pp.641-645
    • /
    • 2017
  • In this study, an epoxy insulation barrier for high voltage GIS was developed using epoxy and a filler with a Young's modulus of 11 GPa. The material was investigated using a simulation of the principal stress, displacement, and safety factors while optimizing the profile shape. The simulation showed that thelarger Young's modulus of the $Al_2O_3$ filler compared to the $SiO_2$ in the epoxy insulation can contribute to an increase in resistance to mechanical fracturing for theoptimized profile barrier in high voltage GIS. In addition, the safety factor was improved by 10%. It can be concluded that the mechanical fracturing properties of the insulation barrier can be enhanced by increasing the content of the elastic filler, $Al_2O_3$, for high voltage GIS applications.

Analysis of Insulation Characteristics for High-voltage Motor Stator Winding using Insulation Diagnostic Test (절연진단법을 이용한 고전압전동기 고정자권선의 절연특성분석)

  • Oh, Bong-Keun;Kang, Hyun-Goo;Kim, Hyun-Il;Lim, Kee-Joe
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.06a
    • /
    • pp.404-405
    • /
    • 2009
  • Insulation diagnostic tests for high voltage motor stator winding were conducted to analyze the insulation characteristics. Test motors were manufactured same factory and year(1996). Insulation characteristics of moisture winding are different from those of deteriorative winding. Insulation resistance and disscipation factor test results are sensitive to moisture winding. AC current, disscipation factor tip-up and PD test results are sensitive to deteriorative winding. Also, Capacitance value for stator winding insulation material has characteristic of increasing in moisture winding.

  • PDF

Development and Evaluation of Epoxy VPI Insulation for High Voltage Rotating Stator Windings (고압회전기 권선용 에폭시 VPI 절연물의 개발과 평가)

  • Lee, Chang-Ryong;Choi, Yong-Chan
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.05d
    • /
    • pp.38-42
    • /
    • 2003
  • The use of VPI impregnated mica tape as high voltage insulation for large rotating electric machines requires a careful balance of processes and materials to obtain the desired electrical, mechanical and thermal characteristics. The stator insulation systems such as epoxy bonded high voltage mica tape have been produced for many years. One such system employing an epoxy and anhydride impregnating resin developed by Hyundai Heavy Industries, Co. (hereafter, HHI), to satisfy customer requests for an epoxy bonded insulation system. HHI applies the following electrical and thermal evaluations such as dielectric breakdown, voltage endurance, dissipation factor vs. temperature, isothermal weight loss, and so on. A detailed laboratory evaluation can describe specific physical limitations for an insulation system and permit development of long-term operation guidelines that permit full utilization of the proposed system. HHI has found these evaluations very helpful in qualifying insulation system for the repair of both large motors and generators.

  • PDF

Analysis of Insulation Condition in High Voltage Motor Stator Windings Following Cleaning and Insulation Reinforcement (세척과 절연보강에 따른 고압전동기 고정자 권선의 절연상태 분석)

  • Kim, Hee-Dong
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.25 no.6
    • /
    • pp.474-480
    • /
    • 2012
  • Diagnostic tests were performed on two high voltage(HV) motor stator windings. These tests included the measurement of insulation resistance, polarization index, AC current, dissipation factor($tan{\delta}$) and partial discharge(PD) magnitude. Surface contamination of HV motor stator windings has an effect on the AC current and $tan{\delta}$. When the stator windings were finished cleaning and insulation reinforcement, the increase rate of AC current(${\Delta}I$) and dissipation factor(${\Delta}tan{\delta}$) were very small compared to those before cleaning. However, the PD magnitude remained the same. These tests show that cleaning and insulation reinforcement of HV motor stator windings can reduce the insulation failure.

Development of Optimum Shape Forming Technology of Angle Ring and Cap for 154kV transformer Insulation (154kV급 변압기절연물 앵글링과 캡의 최적성형 기술 개발)

  • Suh, Wang-Byuck;Kim, Jong-Won;Jang, Sung-Ju;Ryu, Jung-Soo;Bae, Dong-Ho
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.30-30
    • /
    • 2010
  • The Angle Ring and Cap which is called pressboard are settled at primary and secondary coil winding of 154 kV transformer that can reduce effectively distance of insulation. As it has not manufactured pressboard of Angle Ring and Cap for high voltage grade, insulation components industry especially high voltage transformer has not participate in a competition with worldwide yet. That's why is difficult to make an specialized shape of insulation components of high voltage grade. At first, it is very important to make an utility of deformation manufacturing for high voltage transformer insulation components by itself. Therefore it has finally completed to make an deformation manufacturing utility using an special analysis tools. In this paper, developed insulation components was investigates in tensile strength is introduced.

  • PDF

Insulation Characteristics of PET Films for $SF_6$ EHV VT Winding ($SF_6$ EHV VT 권선 절연지의 절연특성)

  • 김정달;박재윤;정장근;김종석;하현진;이용길
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.14 no.5
    • /
    • pp.391-396
    • /
    • 2001
  • The purpose of this study is to investigate the effect of hole or crack on the Insulation characteristics of a PET films for EHV(Extra High Voltage) VT winding. The hole or the crack in the PET films was made and the insulation characteristics of them were measured. Ad an experimental result, it was shown hat he PDIV(Partial Discharge Inception Voltage) and the BDV(Breakdown Voltage) of the PET films with hole or crack were lower than those without them, and were markedly dependent on their position and temperature. Therefore, the hole and the crack affected to insulation characteristics of PET films for SF$_{6}$EHV(Extra High Voltage) VT Winding.g.

  • PDF

A Study on the Image Processing for Effective Insulation Material Degradation Testing (효과적인 절연재료 열화검사를 위한 영상처리에 관한 연구)

  • 정기봉;오무송;김태성
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.05a
    • /
    • pp.230-233
    • /
    • 1999
  • Because Insulation material is play an important part for normal work of electricity equipment, the study is advanced, but as the voltage of electricity system is raising, we required that new lnsulation material. They have excellent specific against high stress, namely the study of insulation increase and prevention diagnosis of insulation degradation of Epoxy or XLPE and so on. In this thesis. I utilize image processing technique for effective inspection of insulation material degradation.

  • PDF

A Study on Electrical and Mechanical Properties of Epoxy Insulation Barrier for High Voltage GIS Using a Filler of SiO2 and Al2O3 (SiO2와 Al2O3를 충진재료로 사용하는 초고압 GIS용 에폭시 절연물 베리어의 전기적 및 기계적 특성에 관한 연구)

  • Suh, Wang-Byuck;Bae, Dong-Ho
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.28 no.6
    • /
    • pp.379-383
    • /
    • 2015
  • Some insulating materials are organized and analyzed with variables to obtain the optimized profile of encapsulated three phase of epoxy barrier which is applied to gas compartment and supporting conductors for high voltage GIS (gas insulated switchgear). The high voltage GIS is used in electrical power system and operating reliability. In this paper, optimization possibility of barrier shape including both electrical insulation performance and mechanical strength, premised on that condition minimizing volume and light weight should be kept for high voltage GIS, could be achieved by analysis simulation. As a result, filling material which is lower permittivity such as $SiO_2$ instead of $Al_2O_3$ properly to the epoxy material, can be improved to increase the electrical insulation performance and mechanical strength for an optimized profile barrier of a high voltage GIS.

Characteristics of Insulation Failure in High Voltage Motor Stator Windings (고압전동기 고정자 권선의 절연파괴 특성)

  • Kim, Hee-Dong;Kim, Kyeong-Yeol;Park, Deok-Hyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.124-124
    • /
    • 2010
  • Diagnostic tests were performed on six high voltage motors. These tests included ac current, dissipation factor(tan6) and partial discharge(PD) magnitude. The rewind of motor stator insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. No. 1 and No.2 motors(4.16 kV) failed near rated voltage of 12.3 kV and 14.2 kV, respectively. The breakdown voltage of No.3 and No.4 motors(6.6 kV) was 17.6 kV and 17.8 kV, respectively. These motors are higher that expected for good quality coils in 6.6 kV class motors.

  • PDF

Development of Optimum Shape Forming Technology of Angle Ring and Cap for 154 kV Transformer Insulation (154 kV급 변압기 절연물 앵글링과 캡의 최적성형 기술 개발)

  • Suh, Wang-Byuck;Kim, Jong-Won;Ryu, Jung-Soo;Bae, Dong-Ho
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.23 no.11
    • /
    • pp.880-885
    • /
    • 2010
  • The Angle Ring and Cap which is called pressboard are settled at the primary and secondary coil winding of 154 kV transformer that can reduce effectively distance of insulation. As it has not manufactured pressboard of Angle Ring and Cap for high voltage grade, insulation components industry especially high voltage transformer has not participate in a competition with worldwide yet. That's why is difficult to make an specialized shape of insulation components of high voltage grade. Therefore it has finally completed to make an deformation manufacturing utility using an bellowed special analysis tools. This study that uses various analysis program determining optimum shape about insulation of Angle Ring and Cap which is related life of high voltage transformer. In addition to develop forming equipment with an specialized five steps pressing. That is also based on the mechanical strength evaluation and test, it is investigated optimized processing components.