Partial Discharge Electromagnetic Wave Penetration Characteristics Throughout Transformer Winding (전자기파 부분방전 신호의 권선 투과 특성)

  • Ju, Hyung-Jun;Han, Ki-Son;Yoon, Jin-Yul
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.23 no.10
    • /
    • pp.809-813
    • /
    • 2010
  • Frequency domain measurement of propagation loss for ultra high frequency (UHF) partial discharge in the winding of power transformer using a spectrum analyzer and pulse generator is presented. We compared the performance of the method using a network analyzer with and without a winding. Using a network analyzer simplifies the measurement and offers better dynamic range and frequency range. It also provides precise propagation loss within the winding in frequency domain at UHF range. We applied this method to measure UHF propagation loss of transformer mock-up, modeled 154 kV 20 MVA power in KEPCO substation.

A Study on the Development of PD Simulation Pulse Generator for Evaluation of GIS Diagnosis System (GIS 진단시스템의 평가를 위한 PD 모의 펄스발생기 개발에 관한 연구)

  • Kim, Sungju;Chang, Sughun;Cho, Kook-hee
    • Journal of the Korean Society of Safety
    • /
    • v.33 no.2
    • /
    • pp.21-27
    • /
    • 2018
  • The expansion and stable operation of electric power facilities are important factors with development of industrial facilities in modern society. In high-voltage equipment such as GIS, the insulation characteristics may be deterioated by environment-friendly gas adaption and miniaturization. There is also the possibility of accidents due to insulation breakdown due to the deterioration of power facilities. Therefore, it is necessary to extend the diagnosis system to continuously monitor the danger signals of these power equipment and to prevent accidents. Most of the internal defects in the GIS system are conductive particles, floating electrode defects, protrusion defects, and the like. In this case, a partial discharge phenomenon is accompanied. These partial discharge signals occur irregularly and various noise signals are included in the field, so it is difficult to evaluate the reliability in the development of the diagnostic system. In this paper, a study was made on equipment capable of generating a partial discharge simulated signal that can be adjusted in size and frequency to be applied to a diagnostic device by electromagnetic wave detection method. The PD simulated pulse generator consists of a user interface module, a high-voltage charging module, a pulse forming circuit, a voltage sensor and an embedded controller. In order to simulate the partial discharge phenomenon similar to the actual GIS, a discharge cell was designed and fabricated. The application of the prototype pulse generator to the commercialized PD diagnosis module confirmed that it can be used to evaluate the performance of the diagnostic device. It can be used for the development of GIS diagnosis system and performance verification for reliability evaluation.

The Analysis of VHF/UHF PD and 3d-PD Pattern (3d-PD 패턴과 VHF/UHF PD 신호의 고찰)

  • Lim, Jang-Seob;Park, Yong-Sik;Park, Byoung-Ha;Han, Sok-Kyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.05b
    • /
    • pp.75-78
    • /
    • 2001
  • Recently, the HFPD measurement testing is widely used in partial discharge measurement of HV machines because HFPD measurement testing receives less influence of external noise and has a merit of good sensitivity. Also HFPD testing is able to offer the judgement standard of degradation level of HV machine and can detect discharge signals in live-line. Therefore it is very useful method compare to previous conventional PD testing method and effective diagnosis method in power transformer that requires live-line diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF

Spectrum Analysis of VHF/UHF PD in Simulated Transformer (모의 변압기의 VHF/UHF PD 스펙트럼 분석)

  • Kim, Duck-Keun;Kim, Jong-Seo;Lim, Yong-Bae;Lim, Jang-Seob;Moon, Chae-Ju
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.50-54
    • /
    • 2000
  • Recently, the HFPD measurement testing is widely used in partial discharge measurement of HV machines because HFPD measurement testing receives less influence of external noise and has a merit of good sensitivity. Also HFPD testing is able to offer the judgement standard of degradation level of HV machine and can detect discharge signals in live-line. Therefore it is very useful method compare to previous conventional PD testing method and effective diagnosis method in power transformer that requires live-line diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF

Recognition of PD Sources in Air by STFT and Stochastic Parameters (STFT 및 통계적 처리에 의한 공기 중 부분방전원 식별)

  • 이강원;박성희;강성화;임기조
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.17 no.1
    • /
    • pp.101-106
    • /
    • 2004
  • The phenomenon of PD(Partial Discharge) is accompanied by electromagnetic wave which can be detected by UHF(Ultra High Frequency) antenna. The signals obtaining from UHF antenna are very high rapid pulse and have wide band frequency responses. The distribution of PRPD(Phase Resolved Partial Discharge) which consisted of those pulse train can show distinct characteristics of PD sources. But it is not sufficient to discriminate among PD sources. This paper suggests that the stochastic parameters formed by preprocessing of STFT(Short Time Fourier Transform) are good tools for differentiate from PD sources. The stochastic parameters are CC(Cross Correlation) mean value, CC standard deviation, CC skewness, CC kurtosis.

Defect Diagnosis of Cable Insulating Materials by Partial Discharge Statistical Analysis

  • Shin, Jong-Yeol;Park, Hee-Doo;Lee, Jong-Yong;Hong, Jin-Woong
    • Transactions on Electrical and Electronic Materials
    • /
    • v.11 no.1
    • /
    • pp.42-47
    • /
    • 2010
  • Polymer insulating materials such as cross linked polyethylene (XLPE) are employed in electric cables used for extra high voltage. These materials can degrade due to chemical, mechanical and electric stress, possibly caused by voids, the presence of extrinsic materials and protrusions. Therefore, this study measured discharge patterns, discharge phase angle, quantity and occurrence frequency as well as changes in XLPE under different temperatures and applied voltages. To quantitatively analyze the irregular partial discharge patterns measured, the discharge patterns were examined using a statistical program. A three layer sample was fabricated, wherein the upper and lower layers were composed of non-void XLPE, while the middle layer was composed of an air void and copper particles. After heating to room temperature and $50^{\circ}C$ and $80^{\circ}C$ in silicone oil, partial discharge characteristics were studied by increasing the voltage from the inception voltage to the breakdown voltage. Partial discharge statistical analysis showed that when the K-means clustering was carried out at 9 kV to determine the void discharge characteristics, the amount discharged at low temperatures was small but when the temperature was increased to $80^{\circ}C$, the discharge amount increased to be 5.7 times more than that at room temperature because electric charge injection became easier. An analysis of the kurtosis and the skewness confirmed that positive and negative polarity had counterclockwise and clockwise clustering distribution, respectively. When 5 kV was applied to copper particles, the K-means was conducted as the temperature changed from $50^{\circ}C$ to $80^{\circ}C$. The amount of charge at a positive polarity increased 20.3% and the amount of charge at a negative polarity increased 54.9%. The clustering distribution of a positive polarity and negative polarity showed a straight line in the kurtosis and skewness analyses.

Propagation Characteristics of Ultra High Frequency Partial Discharge Signals in Power Transformer (전력용변압기에서 UHF 부분방전 신호의 전파 특성)

  • Yoon, Jin-Yul;Han, Ki-Son;Ju, Hyung-Jun;Goo, Sun-Geun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.23 no.10
    • /
    • pp.798-803
    • /
    • 2010
  • This paper describes the characteristics of electromagnetic wave propagation in power transformer. A transformer which is similar to 154 kV single phase on-site transformer unit was provided for the purpose of the experiment. The 12 dielectric windows on the transformer enclosure to install UHF (ultra high frequency) sensors and the full scale mock ups of winding and the core were also equipped in the transformer. Every sensors to be installed to the transformer was tested and verified whether they show same characteristics or not before the experiment. A discharge gap which was used as a PD (partial discharge) source moved to several necessary locations in the transformer to simulate dielectric defects. Propagation times of electromagnetic wave signal from PD source to sensors decided by the routes of both reflection phenomenon and diffraction phenomenon were compared each other. The experimental results showed propagation route of the PD signal makes an effect on the frequency spectrum of front part of the signal and the magnitude of the signal and propagation time of the signal when the signal is captured on the sensor.

A Study on the Detection of Acoustic Signal Produced by Partial Discharges in Insulation Oil and its Positioning (부분방전에 의한 음향신호의 검출과 위치추정에 관한 연구)

  • Kil, Gyung-Suk;Park, Dae-Won;Kim, Il-Kwon;Choi, Su-Yeon;Park, Chan-Yong
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.20 no.10
    • /
    • pp.907-911
    • /
    • 2007
  • This paper dealt with the frequency spectrum analysis of acoustic signal produced by partial discharge (PD) in insulation oil and the positioning of PD occurrence to apply in diagnosis of oil insulated transformers. Three types of electrode system ; the needle-plane, the plane-plane, and the wire-wire structure were assembled to simulate partial discharges in oil insulated transformers. A low-noise amplifier and a decoupling circuit were designed to detect acoustic signal with high sensitivity The frequency spectrum of the acoustic signal were 50 kHz ${\sim}$ 260 kHz in the needle-plane, 50 kHz ${\sim}$ 250 kHz in the plane-plane, and 45 kHz${\sim}$195 kHz in the wire-wire electrode system. Their peak frequencies were 145 kHz, 130 kHz and 114 kHz, respectively The position of PD occurrence was calculated by the time difference of arrival (TOA) using three acoustic emission (AE) sensors, and we could find the position within the error of 1 % in the experimental apparatus.

Analysis of Partial Discharge Signal Propagation Characteristics in GIS using FEM (FEM을 이용한 GIS내 부분방전 신호의 전파특성 해석)

  • Kim Jae-Chul;Lee Do-Hoon;Song Seung-Yeop;Kim Kwang-Whoa
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.11
    • /
    • pp.624-629
    • /
    • 2004
  • The UHF electromagnetic waves excited by PD pulses propagate along the GIS busbar not only TEM mode, but also TE and TM mode. Generally the waves detected by the UHF sensors are those of high order modes and such waves can only propagate higher than cut-off frequency. In this paper, the cut-off frequency of 362[kV] GIS for each modes is computed and the electromagnetic field of each propagation modes is simulated by FEM(Finite Element Method) program. Frequency band of each TEmn/TMmn modes was determinated by simulation results and was discussed optimal position of UHF sensor from this results.

A Study on Development of High Voltage Mica Capacitors (고전압 마이카 커패시터 개발에 관한 연구)

  • Yun, Eui-Jung;Choi, Cheal-Soon;Kim, Jae-Wook;Lee, Dong-Hyuk
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.7
    • /
    • pp.1229-1234
    • /
    • 2008
  • In this work, ultra high-voltage (17 - 50 kV AC), reliable 80 pF mica capacitors for partial discharge system application were investigated. Mica was used as the dielectric of the capacitors. Using the conservative design rule, over 3 individual $50\;{\mu}m$ thick mica sheets with a size of 30mm{\times}35mm were used with lead foils to form a parallel capacitor element and 20 mica sheets were interleaved with lead foils to form a series stack of parallel capacitor element to meet the requirements of the capacitors. The dimensions of the fabricated 80 pF capacitors for 17 kV AC and 50 kV AC were $90\;mm{\times}90\;mm$ and $95\;mm{\times}180\;mm$, respectively. The high-frequency characteristics of the capacitance (C) and dissipation factor (D) of the developed capacitors were measured using a capacitance meter. The developed capacitors exhibited C of 79.5 - 87.5 pF, had D of 0.001% over the frequency ranges of 150 kHz to 50 MHz, had a self-resonant frequency of 65 MHz, and showed results comparable to those measured for the capacitors prepared recently by $Adwel^{Tm}$. The developed capacitors also showed excellent characteristics for thermal shock test and temperature cycling test.