• 제목/요약/키워드: High frequency partial discharge

검색결과 153건 처리시간 0.026초

가스절연개폐장치용 부분방전 감시 시스템을 위한 초광대역 극초단파 신호처리장치 개발 (Development of ultra-high frequency (UHF) ultra-wide bandwidth signal processing unit for UHF partial-discharge monitoring system for gas-insulated switchgears)

  • 최재옥;김영노;이영상;강창원;박기준;구선근;윤진열;구자윤
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 C
    • /
    • pp.1963-1966
    • /
    • 2004
  • An ultra wide band ultra-high frequency (UHF) signal processing module was designed for on-line UHF partial discharge (PD) monitoring systems for gas-insulated switchgears (GIS). Major advantage of the unit is an improved PD detection sensitivity through minimizing the effect of surrounding interference signals. The detection sensitivity of the unit was <-60 dBm that is sufficient to detect UHF PD signals as low as 1 pC. Precise detection of PD occurred in the GIS, due to internal defects, is possible by using the signal processing unit.

  • PDF

고주파 부분방전(HFPD)의 Pulse Analysis Map에 의한 GIS 결함 판별에 관한 연구 (A Study on the defect identification of GIS by Pulse Analysis Map(PA Map) using High Frequency Partial Discharge(HFPD) Detection)

  • 정현재;김지홍;김진기;고흥열;구자윤;김정태
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.143-144
    • /
    • 2006
  • Since one decade. the detection of High frequency Partial Discharge has been proposed as one of the effective method for the diagnosis of the power component under service in power grids. As a tool for this detection. UHF sensor based on the antenna technology has been commercialized for mainly GIS due to its advantages. However, regarding the recognition of the vital defects introducible into the GIS. different types of softwares have been proposed and employed without any convincing probability of identification. In this regards, our work leads us to suggest a novel method named "PA Map" to identify the defects inside the GIS based on the HFPD detection by use of HFCT sensor which is designed according to our patent.

  • PDF

GIS 부분방전 검출용 극초단파 초광대역 센서 개발 (The development of ultra-high frequency ultra-wide bandwidth sensor for Partial Discharge monitoring in Gas Insulated Switchgears)

  • 김영노;최재옥;이영상;강창원;박기준;구선근;윤진열
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.113-116
    • /
    • 2004
  • We developed internal and external type sensor to measure ultra-high frequency (UHF) partial discharge (PD) in 170 kV gas-insulated switchgears (GIS). We also manufactured a PD-generator to verify and measure the detection sensitivity of those sensors. We measured the output power of the UHF PD sensors induced by PDs of 5 pC using the PD-generator. We measured UHF propagation loss of an 170 kV GIS for optimal arrangement of the sensors. We used swept UHF signal from a network analyzer into the GIS to measure the loss of various components of the GIS.

  • PDF

가스절연개폐장치용 부분방전 감시 시스템을 위한 초광대역 극초단파 신호처리장치 개발 (Development of ultra-high frequency (UHF) ultra-wide bandwidth signal processing unit for UHF partial-discharge monitoring system for gas-insulated switchgears)

  • 최재옥;김영노;이영상;강창원;박기준;구선근;윤진열
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.128-131
    • /
    • 2004
  • An ultra wide band ultra-high frequency (UHF) signal processing module was designed for on-line UHF partial discharge (PD) monitoring systems for gas-insulated switchgears (GIS). Major advantage of the unit is an improved PD detection sensitivity through minimizing the effect of surrounding interference signals. The detection sensitivity of the unit was <-60 dBm that is sufficient to detect UHF PD signals as low as 1 pC. Precise detection of PD occurred in the GIS, due to internal defects, is possible by using the signal processing unit.

  • PDF

Features Extraction and Mechanism Analysis of Partial Discharge Development under Protrusion Defect

  • Dong, Yu-Lin;Tang, Ju;Zeng, Fu-Ping;Liu, Min
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권1호
    • /
    • pp.344-354
    • /
    • 2015
  • In order to study the development of partial discharge (PD) under typical protrusion defects in gas-insulated switchgear, we applied step voltages on the defect and obtained the ${\varphi}-u$ and ${\varphi}-n$ spectrograms of ultra-high frequency (UHF) PD signals in various PD stages. Furthermore, we extracted seven kinds of features to characterize the degree of deterioration of insulation and analyzed their values, variation trends, and change rates. These characteristics were inconsistent with the development of PD. Hence, the differences of these features could describe the severity of PD. In addition, these characteristics could provide integrated characteristics regarding PD development and improve the reliability of PD severity assessment because these characteristics were extracted from different angles. To explain the variation laws of these seven kinds of parameters, we analyzed the relevant physical mechanism by considering the microphysical process of PD formation and development as well as the distortion effect generated by the space charges on the initial field. The relevant physical mechanism effectively allocated PD severity among these features for assessment, and the effectiveness and reliability of using these features to assess PD severity were proved by testing a large number of PD samples.

인가전압에 따른 모의변압기의 HFPD 특성분석 (HFPD Characteristic Analysis of Simulated Transformer According To Applied Voltage)

  • 김덕근;임영삼;임장섭;문채주;이진
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.1957-1959
    • /
    • 2000
  • The PD measurement method is very useful to detect insulation degradation. Recently, the HFPD(High Frequency Partial Discharge) measurement testing is widely used in partial discharge measurement of HV machines because HFPD measurement testing receives less influence of external noise and has a merit of good sensitivity. Therefore it is very useful method compare to previous conventional PD testing method and effective diagnosis method in power transformer that requires in-service diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In this study, simulated transformer is manufactured and HFPD occurred from simulated transformer is measured with broad band antenna and active-line RF measurement system in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages. Also the PD pattern which was measured with EMC analyzer and RF measurement system is compared.

  • PDF

Application of SA-SVM Incremental Algorithm in GIS PD Pattern Recognition

  • Tang, Ju;Zhuo, Ran;Wang, DiBo;Wu, JianRong;Zhang, XiaoXing
    • Journal of Electrical Engineering and Technology
    • /
    • 제11권1호
    • /
    • pp.192-199
    • /
    • 2016
  • With changes in insulated defects, the environment, and so on, new partial discharge (PD) data are highly different from the original samples. It leads to a decrease in on-line recognition rate. The UHF signal and pulse current signal of four kinds of typical artificial defect models in gas insulated switchgear (GIS) are obtained simultaneously by experiment. The relationship map of ultra-high frequency (UHF) cumulative energy and its corresponding apparent discharge of four kinds of typical artificial defect models are plotted. UHF cumulative energy and its corresponding apparent discharge are used as inputs. The support vector machine (SVM) incremental method is constructed. Examples show that the PD SVM incremental method based on simulated annealing (SA) effectively speeds up the data update rate and improves the adaptability of the classifier compared with the original method, in that the total sample is constituted by the old and new data. The PD SVM incremental method is a better pattern recognition technology for PD on-line monitoring.

Application of Joint Electro-Chemical Detection for Gas Insulated Switchgear Fault Diagnosis

  • Li, Liping;Tang, Ju;Liu, Yilu
    • Journal of Electrical Engineering and Technology
    • /
    • 제10권4호
    • /
    • pp.1765-1772
    • /
    • 2015
  • The integrity of the gas insulated switchgear (GIS) is vital to the safety of an entire power grid. However, there are some limitations on the techniques of detecting and diagnosing partial discharge (PD) induced by insulation defects in GIS. This paper proposes a joint electro-chemical detection method to resolve the problems of incomplete PD data source and also investigates a new unique fault diagnosis method to enhance the reliability of data processing. By employing ultra-high frequency method for online monitoring and the chemical method for detecting SF6 decomposition offline, the acquired data can form a more complete interpretation of PD signals. By utilizing DS evidence theory, the diagnostic results with tests on the four typical defects show the validity of the new fault diagnosis system. With higher accuracy and lower computation cost, the present research provides a promising way to make a more accurate decision in practical application.

A Study on the Pattern Recognition Rate of Partial Discharge in GIS using an Artificial Neural Network

  • Kang Yoon-Sik;Lee Chang-Joon;Kang Won-Jong;Lee Hee-Cheol;Park Jong-Wha
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • 제5C권2호
    • /
    • pp.63-66
    • /
    • 2005
  • This paper describes analysis and pattern recognition techniques for Partial Discharge(PD) signals in Gas Insulated Switchgears (GIS). Detection of PD signals is one of the most important factors in the predictive maintenance of GIS. One of the methods of detection is electro magnetic wave detection within the Ultra High Frequency (UHF) band (300MHz $\~$ 3GHz). In this paper, PD activity simulation is generated using three types of artificial defects, which were detected by a UHF PD sensor installed in the GIS. The detected PD signals were performed on three-dimensional phi-q-n analysis. Finally, parameters were calculated and an Artificial Neural Network (ANN) was applied for PD pattern recognition. As a result, it was possible to discriminate and classify the defects.

온라인 부분방전 감시 시스템 (On-Line System for Partial Monitoring Discharge)

  • 최용성;황종선;이경섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.2114-2115
    • /
    • 2008
  • We consider the relation between on-line monitoring and diagnostics on the one hand and high-voltage (HV) withstand and partial discharge (PD) on-site testing on the other. HV testing supplies the basic data (fingerprints) for diagnostics. In case of warnings by on-line diagnostic systems, off-line withstand and PD testing delivers the best possible information about defects and enables the classification of the risk. Frequency tuned resonant (ACRF) test systems are best adapted to on-site conditions. They can be simply combined with PD measuring equipment. The available ACRF test systems and their application to electric power equipment -from cable systems to power transformers is described.