• Title/Summary/Keyword: Hemispherical grounding simulator

Search Result 4, Processing Time 0.018 seconds

A Simulator for Potential Distribution Analysis

  • Kil, Gyung-Suk;Gil, Hyong-Jun;Park, Dae-Won
    • Journal of Electrical Engineering and Technology
    • /
    • v.7 no.2
    • /
    • pp.225-229
    • /
    • 2012
  • This paper proposes a reduced-scale simulator that can replace numerical analytic methods for the estimation of potential distribution caused by ground faults in various grounding systems. The simulator consists of a hemispherical electrolytic tank, a three-dimensional potential probe, a grounding electrode, and a data acquisition module. The potential distribution is measured using a potentiometer with a position-tracing function when a test current flows to the grounding electrode. Using the simulator, we could clearly analyze the potential distribution for a reduced- scale model by one-eightieth of the buried depth and length of the grounding rod and grounding grid. Once both the shape of the grounding electrode and the fault current are known, the actual potential distribution can be estimated.

The Potential Interference between Ground Rod and Counterpoise (봉상 접지전극-수평매설 접지전극 상호간의 전위간섭)

  • Lee, Bok-Hee;Lee, Su-Bong;Jeong, Dong-Cheol
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2006.05a
    • /
    • pp.351-354
    • /
    • 2006
  • This paper deals with the potential interferences between ground rod and counterpoise. The ground potential rise and coefficient of potential interference were measured by using the hemispherical water tank grounding simulator and calculated from CDEGS program as functions of the configuration and size of grounding electrodes and the distance between grounding electrodes. The ground potential un and potential interference coefficient strongly depend on the distance between grounding electrodes, the arrangement and size of grounding electrodes.

  • PDF

Analysis of Risk Voltage for Grounding Electrode by Injection of Earth Leakage Current

  • Gil, Hyoung-Jun;Kim, Dong-Woo;Kim, Dong-Ook;Lee, Ki-Yeon;Moon, Hyun-Wook;Kim, Hyang-Kon;Kil, Gyung-Suk
    • International Journal of Safety
    • /
    • v.8 no.2
    • /
    • pp.9-14
    • /
    • 2009
  • This paper describes analysis of risk voltage for grounding electrode where earth leakage current is injected. To assess risk voltage of grounding electrode, the grounding simulator and CDEGS program were used to obtain measured data and theoretical results of this study. The grounding simulator was composed of a hemispherical water tank, AC power supply, a movable potentiometer, and test grounding electrodes. The shapes of grounding electrode model was ground rod. The potential rise was measured by grounding simulator, and the touch and step voltages were computed by CDEGS program. As a consequence, the potential rise of ground rod abruptly decreases with increasing the distance from the grounding electrode to the point to be tested. The touch voltage above the ground rod was low, but the step voltage was high. The measured results were compared with the computer calculated data and were known in good agreement.

Evaluations on the Potential Interferences between Ground Rods (봉상 접지전극 상호간의 전위간섭에 대한 평가)

  • Lee, Bok-Hee;Lee, Su-Bong;Lee, Tae-Hyung;Jung, Hyun-Uk;Kil, Hyung-Jun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.5
    • /
    • pp.92-98
    • /
    • 2006
  • This paper deals with the potential interferences between ground rods. To propose a method for reducing the potential interference caused by grounding electrodes, the theoretical analysis and the reduced scale model tests, which we related to the measurement and computation of ground potential rise and potential interference caused by actual-sized grounding electrodes where current is injected, were carried out. The ground potential rise and potential interference coefficients were measured by using the hemispherical water tank grounding simulator and calculated by CDEGS software as a function of the distance between grounding electrodes. The ground potential rises and potential interference coefficients strongly depend on the distance between grounding electrodes, and the measured results were compared with the computer calculated data and were known in good agreement.