• 제목/요약/키워드: Helical coil type heat exchanger

검색결과 7건 처리시간 0.041초

경사진 헬리컬 코일 열교환기의 열전달 특성에 관한 연구 (Heat Transfer Characteristics of Inclined Helical Coil Type Heat Exchanger)

  • 손창효;전민주;장승일;오후규
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제31권6호
    • /
    • pp.707-714
    • /
    • 2007
  • The heat transfer coefficient and Pressure drop during gas cooling process of $CO_2$ (R-744) in inclined helical coil copper tubes were investigated experimentally. The main components of the refrigerant loop are a receiver. a variable-speed pump. a mass flow meter, a pre-heater and a inclined helical coil type gas cooler (test section). The test section consists of a smooth copper tube of 2.45mm inner diameter. The refrigerant mass fluxes were varied from 200 to $600[kg/m^2s]$ and the inlet Pressures of gas cooler were 7.5 to 10.0 [MPa]. The heat transfer coefficients of $CO_2$ in the inclined helical coil tubes increases with the increase of mass flux and gas cooling pressure of $CO_2$. The pressure drop of $CO_2$ in the gas cooler shows a relatively good agreement with those Predicted by Ito's correlation developed for single-phase in a helical coil tube. The local heat transfer coefficient of $CO_2$ agrees well with the correlation by Pitla et al. However, at the region near pseudo-critical temperature. the experiments indicate higher values than the Pitla et al. correlation. Therefore. various experiments in the inclined helical coil tubes have to be conducted and it is necessary to develop the reliable and accurate prediction determining the heat transfer and pressure drop of $CO_2$ in the inclined helical coil tubes.

내경 4.55 mm의 경사진 헬리컬 코일형 열교환기내 이산화탄소의 열전달 특성에 관한 연구 (Heat Transfer Characteristics of Carbon Dioxide in a Inclined Helical Coil Type Heat Exchanger with Inner Diameter Tube of 4.55 mm)

  • 손창효
    • 한국가스학회지
    • /
    • 제11권3호
    • /
    • pp.1-6
    • /
    • 2007
  • 본 연구에서는 경사진 헬리컬 코일형 동관내 이산화탄소의 증발 열전달 계수와 압력강하를 실험적으로 조사하였다. 냉매 순환루프의 주요구성품은 수액기, 변속펌프, 질량유량계, 예열기, 경사진 헬리컬 코일형 가스냉각기(시험부)로 구성된다. 시험부는 내경 4.55 mm의 평활 동관으로 이루어져 있다. 냉매질량 유속은 $200kg/m^2s$에서 $600kg/m^2s$까지 변화시켰고, 가스냉각기의 입구압력은 7.5 MPa에서 10.0 MPa까지이다. 경사진 헬리컬 코일관내 이산화탄소의 열전달 계수는 질량유속과 냉각압력의 증가와 함께 따라 증가하였다. 이산화탄소의 압력강하는 헬리컬 코일관내 단상 상관식인 Ito식과 좋은 일치를 보였고, 이산화탄소의 국소 열전달 계수는 Pilta 등이 제안한 상관식과 좋은 일치를 보였다. 하지만, 유사임계 온도 영역부근에서는 실험데이터가 더 높게 나타났다.

  • PDF

경사진 헬리컬 코일형 가스냉각기의 관형상에 따른 $CO_2$ 냉각 열전달 특성 (Cooling Heat Transfer Characteristics of $CO_2$ on Tube Geometry of Inclined Helical Coil Type Gas Coolers)

  • 손창효;오후규
    • 설비공학논문집
    • /
    • 제19권9호
    • /
    • pp.640-646
    • /
    • 2007
  • The cooling heat transfer coefficient of $CO_2$ (R-744) for tube and coil diameter (CD), inclined angle of tube and coil pitch of inclined helical coil type copper tubes were investigated experimentally. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and a inclined helical coil type gas cooler (test section). The test section consists of a smooth copper tube of 2.45 and 4.55 mm inner diameter (ID). The refrigerant mass flukes were varied from 200 to 800 [$kg/m^2s$] and the inlet pressures of gas cooler were 7.5 to 10.0 [MPa]. The heat transfer coefficients of $CO_2$ in inclined helical coil tube with 2.45 mm ID are $5{\sim}10.3%$ higher than those of 4.55 mm. The heat transfer coefficients of 41.35 mm CD are $8{\sim}32.4%$ higher than those of 26.75 mm CD. Comparison between $45^{\circ}\;and\;90^{\circ}$ of coil angle, the heat transfer coefficients of $45^{\circ}$ are higher than those of $90^{\circ}$. For coil pitch of gas cooler, the heat transfer coefficients of inclined helical coil gas cooler with coil pitch of 5 mm are similar to those of 10 and 15 mm.

헬리컬 코일형 가스냉각기 내 CO2의 냉각 열전달 특성 (Cooling Heat Transfer Characteristics of CO2 in Helical Coil Type Gas Coolers)

  • 손창효;전민주;오후규
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제31권6호
    • /
    • pp.699-706
    • /
    • 2007
  • The cooling heat transfer coefficient and pressure drop of $CO_2$(R-744) in helical coil copper tubes were investigated experimentally The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter. a pre-heater and a inclined helical coil type gas cooler (test section). The test section consists of a smooth copper tube of 2.45 and 4.55mm inner diameter The refrigerant mass fluxes were varied from 200 to $600 [kg/m^2s]$ and the inlet pressures of 9as cooler were 7.5 to 10.0 [MPa]. The heat transfer coefficients of $CO_2$ in helical coil tubes increase with the increase of mass flux and gas cooling pressure of $CO_2$. The pressure drop of $CO_2$ in the gas cooler shows a relatively food agreement with those Predicted by Ito's correlation developed for single-phase in helical coil tubes. Though a few correlation available with the data. the local heat transfer coefficient of $CO_2$ agrees well with those presented by Pitla et al. among the predictions. However at the region near pseudo-critical temperature. the experiment data indicate higher values than the Pitla et al. correlation.

나선형 튜브 열교환 방식의 포화 상태 액체질소의 비등열전달 특성에 대한 실험적 연구 (Experimental Research of Characteristic of Pool Boiling Heat Transfer of Saturated Liquid Nitrogen with Helical Coil Type Heat Exchanger)

  • 서만수;이지성;김정한;강선일
    • 한국추진공학회지
    • /
    • 제24권3호
    • /
    • pp.59-70
    • /
    • 2020
  • 본 논문에서는 기존 적층형 배관의 총 열전달 계수 경험식을 활용할 때 발생하는 한계점을 해결하고자, 외부 총 열전달 계수의 강제 대류 열전달 계수 항을 독립적으로 도출하는 간소화된 모델링을 제안하고, 이를 극저온 환경의 실험 결과로 확인하였다. 액체 산소 냉각 나선형 열교환기가 액체 질소와 열교환하는 실험 장치를 구성하고 열교환기의 열전달량을 계측하여, 외부 총 열전달 계수를 도출하였다. 측정된 외부 총 열전달 계수가 모델링으로 예측 곡선과 일치함을 확인하였다.

CO2 가스쿨러용 콤팩트열교환기 개발에 관한 연구(1) -다중관식 헬리컬 코일형 가스냉각기내 CO2의 열유량과 압력강하- (Experimental Study on Compact type CO2 Gas Cooler(1) - Heat Flowrate and Pressure Drop in a Multi-Tube-In-Tube Helical Coil Type Gas Cooler -)

  • 오후규;손창효
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제34권1호
    • /
    • pp.30-36
    • /
    • 2010
  • 다중관식 헬리컬 코일형 가스냉각기내 $CO_2$의 열유량과 압력강하에 대해서 실험적으로 조사하였다. $CO_2$와 냉각수의 유량은 각각 0.06~0.075kg/s이고, 가스냉각기의 냉각압력은 8~10 MPa이다. $CO_2$의 열유량은 냉각수 질량유량, $CO_2$의 질량유량과 냉각압력에 비례하여 증가한다. $CO_2$의 압력강하는 냉각수와 $CO_2$의 질량유량이 감소할수록 감소하지만, $CO_2$의 냉각압력이 증가할수록 감소한다. 다중관식 헬리컬 코일형 가스냉각기내 $CO_2$의 열유량과 압력강하는 각각 이중관식 가스냉각기보다 상당히 높게 또는 낮게 나타났다. 따라서 다중관식 헬리컬 코일형 가스냉각기에 $CO_2$를 적용하는 경우에는 가스냉각기의 고효율화, 고성능화, 컴팩트화가 가능할 것이다.

상부 코일히터를 갖춘 나선재킷형 태양열 축열조의 성능예측을 위한 CFD 해석모델 개발 및 검증 (Computational Fluid Dynamics Model for Solar Thermal Storage Tanks with Helical Jacket Heater and Upper Spiral Coil Heater)

  • 백승만;종일명;남진현;정재동;홍희기
    • 대한기계학회논문집B
    • /
    • 제37권4호
    • /
    • pp.331-341
    • /
    • 2013
  • 태양열 온수급탕 시스템에서는 태양열 에너지가 집열판에서 획득되고 열매체로 전달되어 최종적으로 온수의 형태로 축열조에 저장된다. 본 연구에서는 상부 코일히터를 갖춘 나선재킷형 축열조의 축열성능 특성을 정확하게 해석할 수 있는 전산유체역학 모델을 개발하였다. 본 연구에서 고려한 축열조는 벽면에 열매체의 나선유로가 형성된 맨틀형 축열조의 일종으로 시스템 설계 단순화, 저유량 운전, 성층화 촉진 등의 장점을 지닌다. 또한 축열조 내부에 추가적인 코일히터가 장착되어 축열성능과 성층화의 추가적인 향상을 도모할 수 있다. 본 연구에서 개발된 해석모델의 검증은 실제 태양열 온수급탕 시스템의 실증실험 결과와 비교를 통하여 수행되었으며, 온수의 온도변화, 열매체의 온도변화, 성층화 온도분포의 측면에서 잘 일치하는 결과를 얻었다.