• 제목/요약/키워드: Heating operation mode

검색결과 67건 처리시간 0.027초

냉방주체 운전모드에서 동시냉난방 열펌프 성능향상에 관한 실험적 연구 (Experimental Study on the Performance Improvement of a Simultaneous Heating and Cooling Heat Pump in the Cooling-main Operating Mode)

  • 정현준;주영주;강훈;김용찬;최종민
    • 설비공학논문집
    • /
    • 제20권5호
    • /
    • pp.314-320
    • /
    • 2008
  • The cooling load in winter is significant in buildings and hotels because of the usage of office equipments and the improved wall insulation. Hence, a multi~heat pump is required to cover heating and cooling simultaneously for each indoor unit. In this study, the operating characteristics and performance of a simultaneous heating and cooling heat pump in the cooling-main operating mode were investigated experimentally. The system adopted a variable speed compressor using R410A with four indoor units and one outdoor unit. In the cooling-main mode, the heating capacity decreased due to reduction of flow rate to the indoor unit under heating mode operation. The EEV opening was adjusted to increase flow rate to the indoor unit under heating mode operation. The total capacity and COP in the cooling-main mode increased by 20.5% and 29.2%, respectively, compared with those in the cooling-only mode.

열펌프 시스템의 난방 운전 시 최적 성능 제어에 관한 연구 (A Study on the Optimal Performance Control of Heat Pump System for Heating Mode Operation)

  • 유근중;이일환;이길봉;김민수
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2006년도 하계학술발표대회 논문집
    • /
    • pp.669-674
    • /
    • 2006
  • The optimal control of heat pump performance for heating mode operation was investigated. Fuzzy logic was applied to control the heating performance of heat pump system and superheat at compressor discharge was taken as a control variable. Regression model was adapted to determine the optimal points where COP is maximized. Optimization of fuzzy rule table was investigated to improve operation performance of heat pump system. Experiments were carried out using original fuzzy table and the modified fuzzy rule table for heating mode operation of heat pump system. The results show that control performance of heat pump system with the modified fuzzy rule table was better than that with the original rule table.

  • PDF

현장타설말뚝형 에너지 파일의 시공형태별 지중 열교환량에 관한 연구 (The Effect of Construction Methods on Geothermal Exchange Rates of Cast-in-place Energy Piles)

  • 박용부;남유진;심영종;손정락
    • 토지주택연구
    • /
    • 제3권2호
    • /
    • pp.169-175
    • /
    • 2012
  • 최근, 지열 냉난방 시스템의 초기 공사비를 절감하기 위해 연구되고 있는 에너지 파일의 열교환량을 산정하기 위해 2종류(부속연결형, 슬링키형)의 현장타설말뚝형(PRD, 시공심도 4.5m, 직경 1,200mm) 에너지 파일을 시험시공하고 수치 시뮬레이션에 의해 효율을 상호 비교하였다. 상호 비교결과에 의하면 지중 교환량은 운전시작과 함께 채열에 의한 지중온도의 저하에 의해 점점 감소하였고 부속연결형의 평균 열원수의 온도차는 난방운전에서 $0.37^{\circ}C$, 냉방운전에서 $0.34^{\circ}C$로 나타났다. 또, 부속연결형의 난방운전시 열교환량 231.4W/m보다 냉방운전의 방열량은 252.2W/m로서 9% 높았고 슬링키형은 난방 기간 평균 열교환량이 168.0W/m로 부속연결형에 비해 약 27% 낮은 열교환량을 얻었다.

지중온도 경사를 이용한 효율적 지중에너지 이용 방안에 관한 연구 (A Study on Effective Energy Use of the Open Type Ground Heat Exchanger Using Underground Temperature Gradient)

  • 류형규;정민호;이병석;류효준;최현준;최항석
    • 설비공학논문집
    • /
    • 제26권9호
    • /
    • pp.401-408
    • /
    • 2014
  • This paper proposes an optimum operation method for open type ground heat exchangers. A series of TRTs and artificial heating/cooling operations were carried out while monitoring temperature in the hole of SCW. The ground temperature naturally increases with depth, but a switch between the cooling/heating mode results in a change in the distribution of ground temperature. The effect of the mode change was evaluated by performing LMTD and COMSOL multiphysics analysis for a reduced model with the depth of 150 m. As a result, in the cooling mode, the upstream operation is more efficient than the downstream operation and reduces EWT by $2.26^{\circ}C$. On the other hand, in the heating mode, the downstream operation is advantageous over the upstream operation and increases EWT by $3.19^{\circ}C$. The merit of the optimum operation will be enhanced for the typical dimension of SCW with a depth of 400~500 m. In the future, an open type ground heat exchanger system adopting the optimum operation with variation in the ground temperature will be used in practice.

PWM 방식과 인버터 방식을 사용한 시스템 에어컨의 성능평가에 대한 실험적 연구(난방저온 특성) (Experimental Study on Performance Evaluation of System A/C using PWM or Inverter Method (Heating Characteristics at Low Temperature Conditions))

  • 김대훈;전용호;권영철;이윤수;문제명;홍주태
    • 설비공학논문집
    • /
    • 제15권7호
    • /
    • pp.551-556
    • /
    • 2003
  • The present study concerns an experiment on the heating characteristics of a system air-conditioner (A/C) using PWM method or inverter method at low temperature con-ditions. The compressors used are digital scroll type and BLDC inverter type. Under the low outside temperature condition, -5$^{\circ}C$, -1$0^{\circ}C$, -15$^{\circ}C$, heating capacities and COPs are mea-sured by the psychometric calorimeter using air enthalpy method. Also, outlet air temperatures at heating operation mode are measured at -5$^{\circ}C$, -1$0^{\circ}C$ and -15$^{\circ}C$. Experimental results show that COPs of the system A/C using a PWM method are more effective than those of the inverter method at heating operation mode. Although the heater is on, COPs of PWM method are similar to those of BLDC inverter method. Moreover, the heating capacities of PWM method at -5$^{\circ}C$, -1$0^{\circ}C$ and -15$^{\circ}C$ are larger about 10~20% and outlet air tempe-rature at -15$^{\circ}C$ is larger about 10%, compared to the inverter method.

동시냉난방 열펌프 시스템의 운전모드별 성능특성에 관한 수치적 연구 (Numerical Study on the Performance Characteristics of a Simultaneous Heating and Cooling Heat Pump System at each Operation Mode)

  • 주영주;정현준;강훈;최종민;이무연;김용찬
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.370-375
    • /
    • 2007
  • The cooling load in winter season is significant in many commercial buildings and hotels because of the usage of office equipments and high efficiency of wall insulation. The development of a multi-heat pump that can cover heating and cooling simultaneously for each indoor unit is required. In this numerical study, a 4-room simultaneous heating and cooling heat pump system was modeled and its performance was calculated at each operating mode. Also, performance analysis was compared with experimental results.

  • PDF

다수의 히트펌프로 구성된 냉난방시스템에서 하절기 히트펌프의 최적운전에 관한 연구 (A Study on Optimal Operation of Summer Season Cooling System with Numbers of Heat Pumps)

  • 신관우
    • 전기학회논문지P
    • /
    • 제55권1호
    • /
    • pp.35-40
    • /
    • 2006
  • Heat-pump system has a special feature that provides heating operation in winter season and cooling operation in summer season with a single system. It also has a merit that absorbs and makes use of wastewater heat, terrestrial heat, and heat energy from the air. Because heat-pump system uses midnight electric power, it decreases power peak load and is very economical as a result. By using the property that energy source is converted to low temperature when losing the heat, high temperature energy source is used to provide heating water and low temperature energy source is used to provide cooling water simultaneously in summer season. This study made up a heat-pump system with 4 air heat sources and a water heat source and implemented the optimal operation algorithm that works with numbers of heat pumps to operate them efficiently. With the heat-pump system, we applied it to cooling and heating operation in summer season operation mode in a real building.

한랭지(몽골) 지열 히트펌프 시스템의 난방 성능 분석 (Heating Performance of Geothermal Heat Pump System Applied in Cold Climate Region(Mongolia))

  • 손병후;최재호;민경천
    • 설비공학논문집
    • /
    • 제27권1호
    • /
    • pp.31-38
    • /
    • 2015
  • Geothermal heat pump (GHP) systems have become an efficient alternative to conventional cooling and heating methods due to their higher energy using efficiency. These systems use the ground as a heat source in heating mode operation and a heat sink in cooling mode operation. The aim of this study is to evaluate the heating performance of the GHP system for a residential building ($420m^2$) in Ulaanbaatar, Mongolia. In order to demonstrate the feasibility of a sustainable performance of this system, we installed the water-to-water geothermal heat pump with ten vertical ground heat exchangers and measured operation parameters from October 19, 2013 to March 26, 2014. The results showed that the entering source temperature of brine from the ground heat exchangers was in a range of the design target temperature of $-10^{\circ}C$ for heating. For total values of the representative results, the ground heat exchangers extracted heat of 53.51 MWh from the ground. In addition, the GHP system supplied heat of 83.55 MWh to the building and consumed power of 30.27 MWh. Consequently, the average heating seasonal performance factor ($SPF_h$) of the overall system was evaluated to be 2.76 during the measurement period of the heating season.

저온수2단흡수냉난방기의 개발 (Development of Single effect/Double lift Absorption Chiller & Heater for a District Heating Net work)

  • 구기동;김상호;류진상;이재영;서종철;장훈
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.668-672
    • /
    • 2009
  • This is to report the result of Development of Single effect/Double lift absorption chiller & heater which is used in the district heating net work. The heating cycle was newly developed to make the secondary hot water from evaporator and the cycle change-over function was added for the heating to the cooling mode and the cooling to the heating mode. Finally, it was assured through the site trial operation that the outlet temperature of primary hot water can be produced lower than $68^{\circ}C$ when the outlet temperature of secondary hot water is $60^{\circ}C$.

  • PDF

냉각탑을 이용한 축열식 히트펌프시스템의 성능측정에 관한 연구 (A study on performance test of water heat storage type heat-pump system using cooling tower heat source)

  • 이상훈;박효식;한우용;김욱중
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.1099-1104
    • /
    • 2008
  • Recent year, mean energy consumptions of a people are higher than other country. And international oil price became over 120 dollar. This energy environment as well as energy war. Maybe, the Meteorological Administration is going to enforce scorching heatwave special report system from that come summer. Besides, 2008 summer, maximum demand power is expected by 64,240,000kW. The electric power equipment reserve rate appeared in to keep 12.5% level. Chilled water storage system witch is one of electric load administration system. Heat pump system used cooling tower heat recovery is advantage that use is possible to summer in small a public bath building. In this paper, we suggest that heat pump system by heat recovery using cooling tower when it is heating operation of ambient air temperature. To apply cooling tower heat recovery heat pump to chilled water heat storage type and achieved performance evaluation about operation. As a result, performance of heat pump system that about 121% in cooling mode, 138% in heating mode higher than KEPCO standard. And heating operation possible to ambient air temperature about $23^{\circ}C$, which of appear cooling tower outlet temperature about $13^{\circ}C$.

  • PDF