• 제목/요약/키워드: Heat pump with thermal storage

검색결과 66건 처리시간 0.025초

열펌프-잠열축열 시스템의 온실 난방 특성 연구 (Greenhouse Heating Characteristics of Heat Pump-Latent Heat Storage System)

  • 강연구;송현갑
    • Journal of Biosystems Engineering
    • /
    • 제25권5호
    • /
    • pp.379-384
    • /
    • 2000
  • In order to use the natural thermal energy as much as possible for greenhouse heating, the air-air heat pump system involved PCM(phase change material) latent heat storage system was composed, and three types of greenhouse heating system(greenhouse system, greenhouse-PCM latent heat storage system, greenhouse-PCM latent heat storage-heat pump system) were recomposed from the greenhouse heating units to analyze the heating characteristics. The results could be concluded as follows; 1) In the greenhouse heated by the heat pump under the solar radiation of 406.39W/$m^2$, the maximum PCM temperature in the latent heat storage system was 24$^{\circ}C$ and the accumulated thermal energy stored in PCM mass of 816kg during the daytime was 100,320kJ. In the greenhouse without heat pump under the maximum solar radiation of 452.83W/$m^2$, the maximum PCM temperature in the latent heat storage system was 22$^{\circ}C$ and the accumulated thermal energy stored during the daytime was 52.250kJ. 2) In the greenhouse-PCM system without heat pump the heat stored in soil layers from the surface to 30cm of the soil depth was 450㎉/$m^2$. 3) In all of the greenhouse heating systems, the difference between the air temperature in greenhouse and the ambient temperature was about 20~23$^{\circ}C$ in the daytime. In the greenhouse without heat pump and PCM latent heat storage system the difference between the ambient temperature and the air temperature in the greenhouse was about 6~7$^{\circ}C$ in the nighttime, in the greenhouse with only PCM latent heat storage system the temperature difference about 7~13$^{\circ}C$ in the nighttime and in the greenhouse with the heat pump and PCM latent heat storage system about 9~14$^{\circ}C$ in the nighttime.

  • PDF

부하 대응 제어방식을 적용한 축열식 히트펌프시스템의 성능 해석 (A Performance Analysis on a Heat pump with Thermal Storage Adopting Load Response Control Method)

  • 김동준;강병하;장영수
    • 설비공학논문집
    • /
    • 제30권3호
    • /
    • pp.130-142
    • /
    • 2018
  • We use heat pumps with thermal storage system to reduce peak usage of electric power during winters and summers. A heat pump stores thermal energy in a thermal storage tank during the night, to meet load requirements during the day. This system stabilizes the supply and demand of electric power; moreover by utilizing the inexpensive midnight electric power, thus making it cost effective. In this study, we propose a system wherein the thermal storage tank and heat pump are modeled using the TRNSYS, whereas the control simulations are performed by (i) conventional control methods (i.e., thermal storage priority method and heat pump priority method); (ii) region control method, which operates at the optimal part load ratio of the heat pump; (iii) load response control method, which minimizes operating cost responding to load; and (iv) dynamic programming method, which runs the system by following the minimum cost path. We observed that the electricity cost using the region control method, load response control approach, and dynamic programing method was lower compared to using conventional control techniques. According to the annual simulation results, the electricity cost utilizing the load response control method is 43% and 4.4% lower than those obtained by the conventional techniques. We can note that the result related to the power cost was similar to that obtained by the dynamic programming method based on the load prediction. We can, therefore, conclude that the load response control method turned out to be more advantageous when compared to the conventional techniques regarding power consumption and electricity costs.

Hybrid thermal seasonal storage and solar assisted geothermal heat pump systems for greenhouses

  • Ataei, Abtin;Hemmatabady, Hoofar;Nobakht, Seyed Yahya
    • Advances in Energy Research
    • /
    • 제4권1호
    • /
    • pp.87-106
    • /
    • 2016
  • In this research, optimum design of the combined solar collector, geothermal heat pump and thermal seasonal storage system for heating and cooling a sample greenhouse is studied. In order to optimize the system from technical point of view some new control strategies and functions resulting from important TRNSYS output diagrams are presented. Temperatures of ground, rock bed storage, outlet ground heat exchanger fluid and entering fluid to the evaporator specify our strategies. Optimal heat storage is done with maximum efficiency and minimum loss. Mean seasonal heating and cooling COPs of 4.92 and 7.14 are achieved in series mode as there is no need to start the heat pump sometimes. Furthermore, optimal parallel operation of the storage and the heat pump is studied by applying the same control strategies. Although the aforementioned system has higher mean seasonal heating and cooling COPs (4.96 and 7.18 respectively) and lower initial cost, it requires higher amounts of auxiliary energy either. Soil temperature around ground heat exchanger will also increase up to $1.5^{\circ}C$ after 2 years of operation as a result of seasonal storage. At the end, the optimum combined system is chosen by trade-off between technical and economic issues.

열펌프-잠열축열 시스템 온실에서 토양의 열저장 및 방열 특성 (Thermal Energy Storage and Release Characteristics of the Soil in the Greenhouse Equipped with Heat Pump and Latent Heat Storage System)

  • 노정근;송현갑
    • Journal of Biosystems Engineering
    • /
    • 제27권1호
    • /
    • pp.39-44
    • /
    • 2002
  • In order to obtain the information of bio-environment control, the thermal characteristics of soil in the greenhouse heated by the heat pump and latent heat storage system were experimentally analyzed. The experimental systems were composed of the greenhouse with a heat pump and a latent heat storage system (system I), the greenhouse with a heat pump (system II), the greenhouse with a latent heat storage system (system III), and the greenhouse without auxiliary heating system (system IV). The thermal characteristics experimentally analyzed in each system were temperature of soil layers, soil heat storage and release, soil heat capacity and soil heat storage ratio. The results could be summarized as follows. 1. Time to reach the highest temperature at 20cm deep in soil layers of the crop routs in case of system I was shown to be delayed by 6 hours in comparison to the time of the highest temperature at the soil surface. 2. In the clear winter days, the stored heat capacity values fur the system I and the system II were shown to be 22.3% and 11.0% higher than the released heat capacity respectively, and the stored heat capacity values for the system III and the system IV were shown to be 6.2% and 29.6% lower than the released heat capacity respectively This confirms that the system I provided the best heat storage effect. j. The heat quantity values stored or released were shown to be highest at 5 cm depth of soil layers. And it was reduced with increasing of depth of soil layers until 20 cm and was not changed under the soil layer of 20 cm depth. 4. The heat absorption rates of soil, the ratio between supplied and stored heat energy, fur both the system I and system II were lower than 23%.

원수열원 히트펌프 축열시스템의 동절기 성능분석 (Winter Season Performance Characteristics of Raw Water-Source Heat Pump System with a Thermal Storage Tank)

  • 조용;이동근
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2011년도 춘계학술대회 초록집
    • /
    • pp.202-202
    • /
    • 2011
  • Performance of the raw water-source heat pump system with a thermal storage tank has been analyzed in winter season. The raw water is transferred through the multi-regional water supply system from Han river. Raw water is large temperature difference resource compared with groundwater. Although the raw water temperature drops to $0.6^{\circ}C$ due to the heavy snowfall and the severe cold in late January and early February, 2010, the system has been normally operated without any trouble this winter. The unit COP and system COP considered all pump power consumption were estimated based on the second-by-second data of the all sensors. The monthly averaged unit COP and system COP are 3.37 and 2.76 respectively with $1.4^{\circ}C$ of raw water in January, 3.55 and 2.89 with $1.6^{\circ}C$ raw water in February, 3.82 and 3.15 with $5.4^{\circ}C$ raw water in March. The performance of the system are increased with raw water temperature, and the COPs are higher than the water-to-air heat pump system using relatively high temperature raw water from Daecheong reservoir because the water-to-water system was operated on the full load condition and was stopped when the thermal storage tank was full of the high temperature water.

  • PDF

축열조를 채용한 수평형 지열원 히트펌프 온실 난방 시스템에 관한 연구 (A Study on the Horizontal Ground Source Beat Pump Greenhouse Heating System with Thermal Storage Tank)

  • 박용정;김경훈
    • 에너지공학
    • /
    • 제15권3호
    • /
    • pp.194-201
    • /
    • 2006
  • 온실은 작물의 성장조건을 맞추기 위해서 야간 및 추운 날에는 난방을 해야 한다. 지열원 히트펌프 시스템은 냉난방 시스템에서 두드러진 관심을 보이고 있다. 축열조를 채용한 수평형 지열원 히트펌프 시스템을 온실에 적용하여 성능특성을 조사하였다. 그리고 축열조를 채용한 이유를 자세하게 설명하였다. 축열조는 지열원 히트펌프 시스템의 난방능력보다 큰 난방부하를 대응할 수 있다. 연구 결과, 시스템전체의 성능계수는 2.69로 나타났다.

태양열과 재열기를 사용한 VI heat pump의 성능 특성에 관한 연구 (Heating Performance Characteristics of Heat Pump with VI cycle using Re-Heater and Solar-Assisted)

  • 이진국;최광환
    • 한국태양에너지학회 논문집
    • /
    • 제35권6호
    • /
    • pp.25-33
    • /
    • 2015
  • In this study, heating performance of the air-cooled heat pump with vapor-injection (VI) cycles, re-heater and solar heat storage tank was investigated experimentally. Devices used in the experiment were comprised of a VI compressor, re-heater, economizer, variable evaporator, flat-plate solar collector for hot water, thermal storage tank, etc. As working fluid, refrigerant R410A for heat pump and propylene glycol (PG) for solar collector were used. In this experiment, heating performance was compared by three cycles, A, B and C. In case of Cycle B, heat exchange was conducted between VI suction refrigerant and inlet refrigerant of condenser by re-heater (Re-heater in Fig. 3, No. 3) (Cycle B), and Cycle A was not use re-heater on the same operating conditions. In case of Cycle C, outlet refrigerant from evaporator go to thermal storage tank for getting a thermal energy from solar thermal storage tank while re-heater also used. As a result, Cycle C reached the target temperature of water in a shorter time than Cycle B and Cycle A. In addition, it was founded that, as for the coefficient of heating performance($COP_h$), the performance in Cycle C was improved by 13.6% higher than the performance of Cycle B shown the average $COP_h$ of 3.0 and by 18.9% higher than the performance of Cycle A shown the average $COP_h$ of 2.86. From this results, It was confirmed that the performance of heat pump system with refrigerant re-heater and VI cycle can be improved by applying solar thermal energy as an auxiliary heat source.

축열식 지열원 히트펌프 시스템의 냉방기간 실증운전 결과 및 운영비용 분석 (Empirical Results and Operational Cost Analysis of Geothermal Heat Pump System using Thermal Energy Storage in Cooling Season)

  • 김득원;이동원;허재혁;김민휘
    • 설비공학논문집
    • /
    • 제30권4호
    • /
    • pp.167-174
    • /
    • 2018
  • The geothermal heat pump systems were installed for heating and cooling of public buildings in Jincheon Eco-friendly Energy town. The heat pump system was operated at night to save on operational costs, and the cold heat was stored in thermal energy storage (TES). In this study, the performance of geothermal heat pump systems with the TES during the summer season was analyzed, and the operational costs with and without the TES were compared. The electric chiller model was used to simulate a heat pump applied without the TES system. Electric rates of each system were measured to calculate operational costs. When the TES is used in the air conditioning system, the electric load (30.4 MWh) calculated in the daytime can move to off-peak load time, and the operational cost is reduced by 36~54%.

지하수 유동 영향에 따른 지하수 이용 열펌프 시스템의 대수층 온도 변화 예측 모델링 (Simulation of aquifer temperature variation in a groundwater source heat pump system with the effect of groundwater flow)

  • 심병완;송윤호
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2005년도 춘계학술대회
    • /
    • pp.701-704
    • /
    • 2005
  • Aquifer Thermal Energy Storage (ATES) can be a cost-effective and renewable geothermal energy source, depending on site-specific and thermohydraulic conditions. To design an effective ATES system having influenced by groundwater movement, understanding of thermo hydraulic processes is necessary. The heat transfer phenomena for an aquifer heat storage are simulated using FEFLOW with the scenario of heat pump operation with pumping and waste water reinjection in a two layered confined aquifer model. Temperature distribution of the aquifer model is generated, and hydraulic heads and temperature variations are monitored at the both wells during 365 days. The average groundwater velocities are determined with two hydraulic gradient sets according to boundary conditions, and the effect of groundwater flow are shown at the generated thermal distributions of three different depth slices. The generated temperature contour lines at the hydraulic gradient of 0.00 1 are shaped circular, and the center is moved less than 5m to the groundwater flow direction in 365 days simulation period. However at the hydraulic gradient of 0.01, the contour center of the temperature are moved to the end of boundary at each slice and the largest movement is at bottom slice. By the analysis of thermal interference data between two wells the efficiency of the heat pump system model is validated, and the variation of heads is monitored at injection, pumping and no operation mode.

  • PDF

열펌프와 잠열축열을 이용한 온실 난방시스템의 열특성과 시뮬레이션 모델개발 (Thermal Energy Characteristics and Simulation Model Development for Greenhouse Heating System with Heat Pump and Latent Heat Storage)

  • 노정근;송현갑
    • Journal of Biosystems Engineering
    • /
    • 제26권6호
    • /
    • pp.553-562
    • /
    • 2001
  • The greenhouse heating system with heat pump and latent heat storage was built for development of simulation model and validation. The computer simulation model for the system to predict temperature of air, soil surface and cover film in the greenhouse were developed and its validity was justified by actual data. From the analysis of experimentally measured and the simulation output, following results were obtained. 1. The expected values of inside air temperature for the greenhouse with a heat pump and a latent heat storage system were very much close to the experimental values at the error range of 1.0$\^{C}$. 2. The expected values of soil surface temperature fur the geenhouse with a heat pump and a latent heat storage system were very much close to the experimental values at the error range of 1.0$\^{C}$. 3. The expected values of thermal energy flow fur the greenhouse with a heat pump and a latent heat storage system were very much close to the experimental values at the error range of 167.2kJ/m$^2$h. 4. Heat lass value of day time was found to be larger than that of night time as much as 1.11 time. 5. At day time. the inside air temperature was shown to be higher than the set point of 7.0$\^{C}$. At night time, the inside air temperature was controlled in order to maintain higher temperatures than the set point.

  • PDF