• 제목/요약/키워드: Heat Load Simulation

검색결과 251건 처리시간 0.03초

Analysis of Economics through Control Method of Heat Source Equipment in Seasonal Air conditioning Building

  • Park, Yool;Kim, Samuel;Jung, Soon-Sung
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제11권4호
    • /
    • pp.209-217
    • /
    • 2003
  • The term “energy saving is economical” is appropriate for the national view point and for design and assessment of one system, but not appropriate when choosing the system by comparing alternative systems in the early design step. Sometimes, non-energy saving system is more economical than energy saving system because of the price of electricity, gas or oil, which are used for operating the air conditioning system. Therefore, when designing a system, we should consider the efficient alternatives through economic assessment of energy saving method. However, research on non-operating number control of the system is not sufficient because it is more common to use operating number control of the system for most economic assessment of air conditioning systems. For this reason, this research can provide the economic operating number control method as basic design data. The data obtained through analysis of life cycle cost based on amount of yearly energy use, are produced by system simulation of HASP/ACLD/8501 and HASP/ACSS/8502 for six alternative heating$.$cooling systems based on seasonal air conditioning system, which is widely used for medium and large size office buildings in Busan.

국내 여름철 기후조건에서 DOAS와 TABS 통합시스템 냉방운전시 실내온열환경 및 운전특성 평가 (Evaluation on the Indoor Thermal Environment and Cooling Operation Characteristics of Thermally Activated Building System integrated with Dedicated Outdoor Air System during Cooling Operation in Hot and Humid Climate of Seoul)

  • 이윤선;이겨레;정웅준;임재한
    • 대한건축학회논문집:계획계
    • /
    • 제34권11호
    • /
    • pp.45-55
    • /
    • 2018
  • To reduce the energy consumption of HVAC system in buildings, thermally activated building system(TABS) has been applied to low energy building because of energy efficient performance and reduction of peak load. DOAS coupled with a parallel sensible cooling could be promising because TABS handles sensible heat load only. The purpose of this study was to evaluate the indoor thermal environment and cooling operation characteristic of TABS with dedicated outdoor air system(DOAS) in Korea climate. Indoor thermal environment and operation characteristic of TABS integrated with DOAS are investigated at different TABS operation schedules and climate conditions by simulation tests. The result shows that the DOAS is more suitable for hot and humid climates. And also it show that the potential of intermittent operation of TABS.

지하공동구내 가연성케이블의 열화접촉으로 인한 화재위험성 예측평가 (Study on the Fire Risk Prediction Assessment due to Deterioration contact of combustible cables in Underground Common Utility Tunnels)

  • Ko, Jaesun
    • 한국재난정보학회 논문집
    • /
    • 제11권1호
    • /
    • pp.135-147
    • /
    • 2015
  • 최근 지하공동구(Underground Common Utility Tunnels)는 도시민이 일상생활을 영위하는데 필요한 전기, 통신, 상수도, 도시 가스, 하수도뿐만 아니라 냉난방시설, 진공 집진관, 정보처리케이블 등의 시설물을 2종 이상 공동으로 수용하기 위한 지하시설물로서 국가의 중추기능을 담당하는 시설이지만, 화재 사고시 신속한 대처가 힘들고 각종 케이블 연소시 발생하는 유독가스 및 연기에 의해 공동구 내에 진입하여 진압하기가 힘들다. 따라서 화재발생시 막대한 재산피해 및 통신두절 등 국가의 중추신경이 마비됨은 물론 시민불편사항을 초래하게 된다. 따라서 본 논문은 지금까지 발생 되어온 국내,외 공동구 화재사례에서 화재발생의 주요원인으로 전기공사로 인한 합선 및 가연성케이블에 의한 열화접촉으로 화재가 발생하는 것이 대다수를 차지하고 있음에 착안하여 실제 공동구 모형을 제작하고 화재를 재현함으로서 과학적으로 화재의 성상을 분석하는데 그 목적이 있다. 화재실험은 지하공동구 내에 정온식 감지선형 감지기(Line type fixed temperature detector), 방화문(Fire door), 연결살수설비(Connection deluge set), 및 환기설비를 설치하고, 송 배전케이블은 일정구간 내화(Fireproof)도료로 도장하며, 난방관은 내화 피복된 상태에서 실험하였다. 그 결과 Type II의 경우 최고온도가 $932^{\circ}C$로 측정되었고, 일정한 온도에서 정온식감지선형감지기가 화재위치를 정확하게 수신반에 표시되었다. 그리고 Type III의 경우인 송 배전케이블은 일정구간 내화도료로 도장한 것은 내화성능이 없는 것으로 나타났고, 내화피복(Fireproof covered)된 난방관은 약 30분 정도의 내화성능이 있는 것으로 나타났다. 또한 화재뮬레이션 결과는 실물화재시험시의 화재하중(Fire load)을 입력하여 실시한 결과로서 최고온도가 $943^{\circ}C$로 실물화재실험시의 $932^{\circ}C$와 거의 일치 하였다. 따라서 공동구 화재하중만으로 화재시뮬레이션을 실시하여 화재성상에 대한 예측이 가능한 것으로 판단되며 시뮬레이션으로 얻은 열방출률(Heat release rate), 연기층의 높이, 산소(O2), 일산화탄소(CO), 이산화탄소(CO2)의 농도 등의 결과 값들은 실제 화재실험시의 값으로 적용시킬 수 있는 것으로 판단된다. 향후 본 연구에서 구축한 국내 지하공동구 화재사고에 대한 실험자료 및 매년 지속적으로 화재사례들을 분석하여 축적하고 법 규정 및 관리 메뉴얼 등을 보완함으로써 국내 지하공동구 화재사고에 대한 보다 신뢰성 있는 정보를 제공해 줄 수 있을 것이며, 효과적이고 체계적으로 지하공동구의 신설 및 유지 관리 보수에 기여할 것으로 기대된다.

WELDING-INDUCED BUCKLING INSTABILITIES IN THIN PLATES

  • Han, Myoung-Soo;Tsai, Chon-Liang
    • 대한용접접합학회:학술대회논문집
    • /
    • 대한용접접합학회 2002년도 Proceedings of the International Welding/Joining Conference-Korea
    • /
    • pp.661-667
    • /
    • 2002
  • Welding-induced buckling distortion is one of the most problematic concerns in both design and fabrication of welded thin-plate structures. This paper deals with experimental and numerical results of the welding-induced longitudinal and/or buckling distortion occurring in welding of 6mm-thick AH36 high strength steel plates. Effects of the heat input and the plate size on the distortion were experimentally evaluated for square plates. Bead-on-plate welding was performed with the submerged arc welding process along the middle line of plate specimens. Experimental results showed that the longitudinal distortion made a single curvature in the plate, and the distortion magnitude along the weld centerline was proportional to the heat input and the plate size. The experimental results were used to examine the validity of the numerical simulation procedure for welding-induced distortion where the longitudinal distortion mode and magnitude were numerically quantified. Three-dimensional, large deformation, welding simulations were performed for selected weld models. Numerical results of the distortion mode and magnitude were in a good agreement with experimental ones. Depending on the presence of halting the distortion growth during the cooling cycle of welding, the condition discriminating buckling distortion from longitudinal distortion was established. Eigenvalue analyses were performed to check the buckling instability of tested plates with different sizes subjected to different heat inputs. The perturbation load pattern for the analysis was extracted from longitudinal inherent strain distributions. Critical buckling curve from the eigenvalue analyses revealed that the buckling instability is manifested when plate size or heat input increases.

  • PDF

설비공학 분야의 최근 연구 동향: 2014년 학회지 논문에 대한 종합적 고찰 (Recent Progress in Air-Conditioning and Refrigeration Research: A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2014)

  • 이대영;김사량;김현정;김동선;박준석;임병찬
    • 설비공학논문집
    • /
    • 제27권7호
    • /
    • pp.380-394
    • /
    • 2015
  • This article reviews the papers published in the Korean Journal of Air-Conditioning and Refrigeration Engineering during 2014. It is intended to understand the status of current research in the areas of heating, cooling, ventilation, sanitation, and indoor environments of buildings and plant facilities. Conclusions are as follows. (1) The research works on the thermal and fluid engineering have been reviewed as groups of heat and mass transfer, cooling and heating, and air-conditioning, the flow inside building rooms, and smoke control on fire. Research issues dealing with duct and pipe were reduced, but flows inside building rooms, and smoke controls were newly added in thermal and fluid engineering research area. (2) Research works on heat transfer area have been reviewed in the categories of heat transfer characteristics, pool boiling and condensing heat transfer and industrial heat exchangers. Researches on heat transfer characteristics included the results for thermal contact resistance measurement of metal interface, a fan coil with an oval-type heat exchanger, fouling characteristics of plate heat exchangers, effect of rib pitch in a two wall divergent channel, semi-empirical analysis in vertical mesoscale tubes, an integrated drying machine, microscale surface wrinkles, brazed plate heat exchangers, numerical analysis in printed circuit heat exchanger. In the area of pool boiling and condensing, non-uniform air flow, PCM applied thermal storage wall system, a new wavy cylindrical shape capsule, and HFC32/HFC152a mixtures on enhanced tubes, were actively studied. In the area of industrial heat exchangers, researches on solar water storage tank, effective design on the inserting part of refrigerator door gasket, impact of different boundary conditions in generating g-function, various construction of SCW type ground heat exchanger and a heat pump for closed cooling water heat recovery were performed. (3) In the field of refrigeration, various studies were carried out in the categories of refrigeration cycle, alternative refrigeration and modelling and controls including energy recoveries from industrial boilers and vehicles, improvement of dehumidification systems, novel defrost systems, fault diagnosis and optimum controls for heat pump systems. It is particularly notable that a substantial number of studies were dedicated for the development of air-conditioning and power recovery systems for electric vehicles in this year. (4) In building mechanical system research fields, seventeen studies were reported for achieving effective design of the mechanical systems, and also for maximizing the energy efficiency of buildings. The topics of the studies included energy performance, HVAC system, ventilation, and renewable energies, piping in the buildings. Proposed designs, performance performance tests using numerical methods and experiments provide useful information and key data which can improve the energy efficiency of the buildings. (5) The field of architectural environment was mostly focused on indoor environment and building energy. The main researches of indoor environment were related to the evaluation of work noise in tunnel construction and the simulation and development of a light-shelf system. The subjects of building energy were worked on the energy saving of office building applied with window blind and phase change material(PCM), a method of existing building energy simulation using energy audit data, the estimation of thermal consumption unit of apartment building and its case studies, dynamic window performance, a writing method of energy consumption report and energy estimation of apartment building using district heating system. The remained studies were related to the improvement of architectural engineering education system for plant engineering industry, estimating cooling and heating degree days for variable base temperature, a prediction method of underground temperature, the comfort control algorithm of car air conditioner, the smoke control performance evaluation of high-rise building, evaluation of thermal energy systems of bio safety laboratory and a development of measuring device of solar heat gain coefficient of fenestration system.

교육용 건물의 GHP 냉/난방 부하의 고조파 특성에 관한 연구 (A Study on the Harmonic Characteristics of GHP Cooling/Heating Load in an Institutional Building)

  • 김경철;오경훈;이규진
    • 조명전기설비학회논문지
    • /
    • 제23권4호
    • /
    • pp.29-38
    • /
    • 2009
  • GHP(Gas Heating Pump) 시스템은 가스 엔진으로 구동되는 압축기로 구성되는 효율적인 냉/난방기이고, 학교나 사무용 빌딩에 널리 쓰이고 있다. GHP는 느린 응답, 큰 시정수와 시간에 따라 변하는 시스템으로 제어하기가 어렵다. 이들 비선형 부하는 고조파 전류를 발생시키고, 전력계통의 정현파 전압을 왜곡시킨다. 고조파 측정 결과로 고조파는 시간에 따라 변하는 특성이 관측되었다. 시간에 따라 변하는 고조파를 해결하기 위해서 쓰이는 가장 보편적인 방법은 누적확률을 사용하는 것이다. 본 논문에서는 GHP부하의 고조파 특성, IEC 61000-3-2에 의한 고조파 평가와 사례연구 시스템의 고조파 시뮬레이션 및 고조파 필터 적용을 심도있게 다루고자 하였다.

전도 냉각형 10kJ 고온 초전도 에너지 저장장치의 열 부하 특성 해석 (Heat load characteristic analysis of conduction cooled 10kJ HTS SMES)

  • 김광민;김아롱;김진근;박해용;박민원;유인근;김석호;심기덕
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.2219_2220
    • /
    • 2009
  • The characteristics of the Superconducting Magnetic Energy Storage (SMES) system are faster response, longer life time, more economical, and environment friendly than other Uninterruptible Power Supply (UPS) using battery. Fast charge and discharge time of SMES system can provide powerful performance of improving power quality in the grid. In order to demonstrate the effectiveness of SMES, the authors make a 10kJ SMES system for connection with RTDS (Real Time Digital Simulator). Because the characteristics of superconducting magnet are very important in SMES system, the necessary items such as thermal characteristic, mechanical stress and protection circuit should be considered. In this paper, the authors experimented thermal characteristics of the 10kJ SMES system. The experiment was accomplished using a simulation coils made of aluminium. It has same dimension of the 10kJ class HTS SMES coil. The coil was cooled with GM (Gifford -McMahon) cryocooler through the OFHC (Oxgen Free High thermal Conductivity) conduction bar. The test results of cool down and heat loads characteristics of the simulation coils are described in detail.

  • PDF

A Novel High Precision Electromagnetic Suspension for Long-Stroke Movement and Its Performance Evaluation

  • Lee, Ki-Chang;Moon, Seokhwan;Ha, Hyunuk;Park, Byoung-Gun;Kim, Ji-Won;Baek, Jun-Young;Lee, Min-Cheol
    • Journal of Electrical Engineering and Technology
    • /
    • 제9권2호
    • /
    • pp.514-522
    • /
    • 2014
  • A new type of high precision electromagnetic suspension (EMS) which can support heavy tray along long stroke rail is proposed in this paper. Compared with the conventional EMS, the suggested moving-core typed EMS has the levitation electromagnets (EMs) on the fixed rail. This scheme has high load capability caused by iron-core and enables simple tray structure. Also it does not have precision degradation caused by heat generation from EMs, which is a drawback of conventional EMS. With these merits, the proposed EMS can be an optimal contactless linear bearing in next generation flat panel display (FPD) manufacturing process if the ability of long stroke movement is proved. So a special Section Switching Algorithm (SSA) is derived from the resultant force and moment equations of the levitated tray which enables long stroke movement of the tray. In order to verify the feasibility of the suggested SSA, a simple test-setup of the EMS with 2 Section-changes is made up and servo-controlled in the simulation and experiment. The simulation shows the perfect changeover the EMs, and the experiment shows overall control performance of under ${\pm}40{\mu}m$ gap deviations. These results reveal that the newly suggested contactless linear bearing can simultaneously achieve high load capability and precision gap control as well as long stroke.

삼중효용 LiBr/물 흡수식 냉방기의 사이클 시뮬레이션 (Cycle simulation of a triple effect LiBr/water absorption chiller)

  • 조광운;정시영;정은수
    • 설비공학논문집
    • /
    • 제10권1호
    • /
    • pp.79-87
    • /
    • 1998
  • Basic design of a 50USRT(175㎾) triple effect absorption chiller driven by hot gas has been carried out for both parallel and series flow cycles. Parallel flow cycle showed higher COP, however, the temperature in the generator was also higher than that in series flow cycle. Dynamic operation behavior of a parallel flow system at off-design conditions, such as the change in heat transfer medium temperature or the construction change of the system components, has been investigated in detail. It was found that the cooling capacity was seriously decreased by reducing hot gas flow rate and UA-value in the high temperature generator. However, the system COP was improved, because thermal load in the system components was reduced. The COP and the cooling capacity was found to be improved as cooling water temperature decreased or chilled water temperature increased. The optimum ratio of solution distribution could be suggested by considering the COP, the cooling capacity and the highest temperature in the system, which is critical for corrosion.

  • PDF

태양열을 이용한 일이중 겸용 흡수식 냉온수기 동적성능 모사연구 (A Study of Dynamic Simulation of a Hybrid Absorption Chiller Utilizing Solar Power)

  • 신영기;서정아;우성민;김효상
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2009년도 하계학술발표대회 논문집
    • /
    • pp.967-972
    • /
    • 2009
  • A dynamic model has been developed to investigate the operability of a single and double-effect solar energy assisted parallel type absorption chiller. In the study, main components and fluid transport mechanism were modeled. And solar radiation and the solar collector also were also modeled along with its control design. The model was run for the single mode with solar energy supply only and the solar/gas driving double effect mode. From the simulation results, it was found that the present configuration of the chiller is not capable of regulating solution flow rates according to variable solar energy input. And the issues of the excessive circulation flowrate and the mismatch between available solar power and cooling load discourages the use of the single mode, but the dual use of gas and solar power is recommendable in view of controllability and enhanced COP.

  • PDF