전산실에서의 고조파 분석 (Analysis of the Harmonics on the Power Line in the Computer Room)

  • 노덕남;어익수
    • 한국산학기술학회논문지
    • /
    • 제13권12호
    • /
    • pp.6052-6059
    • /
    • 2012
  • 본 논문에서는 전산실 파워라인의 고조파 문제를 다룬다. 전산실 UPS의 부하 측 각 상의 전압 및 전류는 한국전력공사 전기공급 약관의 규제치 전압 왜형률 5%와 전류 왜형률 5%, 그리고 KS C 4310 의 무정전 전원장치인 UPS의 출력측 고조파 전류 한도 5% 이하를 만족시켜야 한다. 그러나 측정 결과 전압 왜형률은 0.86%로 한국전력공사 규제치에 부합하나, 전류 왜형률은 34.98%로 한국전력공사 규제치인 5%를 초과하여 부적합하였다. 이에 대한 대책으로 AC필터를 설치한 결과 전류 왜형률이 15.22%로, 기준 값 이내에는 미치지 못하였으나 본래의 34.98%에서 절반에 가까운 수준에는 근접 하는 효과가 있었다.

Circulating Current Harmonics Suppression for Modular Multilevel Converters Based on Repetitive Control

  • Li, Binbin;Xu, Dandan;Xu, Dianguo
    • Journal of Power Electronics
    • /
    • 제14권6호
    • /
    • pp.1100-1108
    • /
    • 2014
  • Modular multilevel converters (MMCs) have emerged as the most promising topology for high and medium voltage applications for the coming years. However, one particular negative characteristic of MMCs is the existence of circulating current, which contains a dc component and a series of low-frequency even-order ac harmonics. If not suppressed, these ac harmonics will distort the arm currents, increase the power loses, and cause higher current stresses on the semiconductor devices. Repetitive control (RC) is well known due to its distinctive capabilities in tracking periodic signals and eliminating periodic errors. In this paper, a novel circulating current control scheme base on RC is proposed to effectively track the dc component and to restrain the low-frequency ac harmonics. The integrating function is inherently embedded in the RC controller. Therefore, the proposed circulating current control only parallels the RC controller with a proportional controller. Thus, conflicts between the RC controller and the traditional proportional integral (PI) controller can be avoided. The design methodologies of the RC controller and a stability analysis are also introduced. The validity of the proposed circulating current control approach has been verified by simulation and experimental results based on a three-phase MMC downscaled prototype.

시간에 따라 변하는 고속철 부하의 고조파 측정, 평가 및 시뮬레이션에 관한 연구 (A Study on the Time-varying Harmonics Measurement, Assessment and Simulation of the High Speed Electric Train Loads)

  • 김경철;진성은;이일무;왕용필;곽노홍;전영수;박상호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 A
    • /
    • pp.78-80
    • /
    • 2006
  • High speed electric trains have nonlinear loads including converters and inverters for the control synchronous motors. Harmonic field measurements have shown that the harmonic contents of a waveform varies with time. Direct application of the harmonic assessment to the snapshot measurements would result in ambiguous conclusions depending on which instant is sampled. A cumulative probabilistic approach is the most commonly used method to solve time varying harmonics. This paper provides an in depth analysis on harmonics field measurement of the high speed electric train loads, harmonics assessment by the international harmonic standards IEC 61000-3-6 and IEEE Std. 519-1992, and harmonics simulation using EDSA program for the case study.

  • PDF

전기로 부하의 고조파 측정, 평가 및 동조필터 적용에 관한 연구 (A Study on the Harmonics Measurement, Assessment and Resonant Filter Application of the Electric Arc Furnace Loads)

  • 김경철;진성은;이주홍
    • 조명전기설비학회논문지
    • /
    • 제20권6호
    • /
    • pp.35-42
    • /
    • 2006
  • 규모가 큰 제철소는 전기로를 포함한 비선형 부하를 가지고 있다. 이들 비선형 부하는 고조파 전류를 발생 시키고, 전력 계통의 전압을 왜곡시킨다. 본 논문에서는 전기로 부하의 고조파 현장 측정, 고조파 저감을 위해 수용가 모선에 동조 필터 적용과 국제 고조파 관리 기준인 IEC 61000-3-6과 IEEE Std. 519에 의한 고조파 평가를 심도 있게 분석한다. 고조파 해석 프로그램인 EDSA는 사례연구에 시뮬레이션 도구로 사용되었다.

가정용 연료전지 시스템의 계통연계 시 수용가 및 배전계통에서의 고조파 영향 평가 (An Assessment on Harmonics Effect in Customer and the Distributed Power System during Grid Connection of Residential Fuel Cell System)

  • 박찬엄;정진수;한운기
    • 전기학회논문지
    • /
    • 제60권6호
    • /
    • pp.1280-1285
    • /
    • 2011
  • Recently, due to the use of fossil fuels for electric power production, carbon emissions increased excessively. Thereby, in order to replace fossil fuels, many studies about fossil fuels such as solar and fuel cell energy source are progressing. Fuel cell system has high energy conversion efficiency. Also, fuel cell system is environmentally friendly system because the carbon emission is almost not occur. Therefore, the fuel cell system is considered as the core technology of in the fields of the future energy and environmental. Fuel cell system has an effect on distribution power system because another power source of other than large power plants. So, fuel cell system can be degradation reason of power quality in the power system. In this paper, we constructed the system for an assessment on harmonics effect. The system is composed with power source, harmonics generation and linear load, fuel cell system. we also performed assessment on harmonics effect in customer and the distributed power system during grid connection of residential fuel cell system. An assessment cases are divided into three. A Case 1 is state that residential load and fuel system are connected to grid, Case 2 is state that residential load and harmonics load are connected to grid, and Case 3 is state that all loads are connected to grid. As a output of fuel cell system is increase, analysis results based on assessment system showed that power quality became more aggravation as effect of harmonics.

전기설비의 고조파 진단을 위한 전력품질 측정시스템의 개발 (Development of Power Quality Measurement System for Harmonics Diagnosis of Electrical Equipment)

  • 유재근;이상익;전정채
    • 조명전기설비학회논문지
    • /
    • 제17권6호
    • /
    • pp.130-137
    • /
    • 2003
  • 고조파에 의한 전력품질저하로 인해 전기설비의 성능저하, 소음, 진동 등의 장해현상이 발생한다. 또한 앞으로 에너지 이용 효율을 높이기 위한 대책으로 반도체 회로를 사용하는 에너지 절약장치가 널리 보급되고, 전동기 속도 제어장치, 에너지 저장장치 등 에너지 변환장치의 사용이 증가될 전망이어서 고조파의 발생은 필연적이며 그 문제점은 심각하게 대두될 것이다. 이러한 고조파에 의한 장애를 해결하기 위해서는 전압, 전류, 전력, 역률, 고조파 차수별 성분 및 고조파 총합 왜형률 등의 정확한 전력품질을 측정하고 분석할 필요가 있다. 본 연구에서는 이러한 고조파 관련 전력품질을 측정하고 분석할 수 있는 저가형 측정시스템을 개발하였으며 3상 4선식 계통에서 전력품질을 측정하고 분석함으로써 그 성능을 입증하였다.

시간에 따라 변하는 전기로 부하의 고조파 측정, 평가 및 시뮬레이션에 관한 연구 (A Study on the Time-varying Harmonics Measurement, Assessment and Simulation of the Electric Arc Furnace Loads)

  • 김경철;진성은;이주홍;전영수
    • 조명전기설비학회논문지
    • /
    • 제20권5호
    • /
    • pp.9-17
    • /
    • 2006
  • 규모가 큰 제철소는 전기로와 같은 비선형 부하를 가지고 있다. 고조파 측정 결과로 고조파는 시간에 따라 변하는 특성이 관측되었다. 순시치 측정에 의한 고조파 평가는 측정 순간에 따라 고조파가 다를 수 있으므로 모호한 결과를 초래할 수 있다. 시간에 따라 변하는 고조파를 해결하기 위해 쓰이는 가장 보편적인 방법은 누적확률을 사용하는 것이다. 고조파 시뮬레이션은 사례연구 시스템의 전압 및 전류 왜곡을 평가하기 위해 이용되었다. 본 논문에서는 전기로 부하의 고조파 현장 측정, 국제 고조파 관리 기준인 IEC 61000-3-6과 IEEE Std. 519에 의한 고조파 평가, 시간에 따라 변하는 고조파의 시뮬레이션을 심도 있게 다루고자 한다. 고조파 해석 프로그램인 EDSA는 사례 연구에 시뮬레이션 도구로 사용되었다.

중성선 영상고조파 저감용 특수 Reactor 최적설계 연구 (An Analysis and Optimum Design of o Neutral Line Harmonics Eliminating Reactor)

  • 신판석;정교범;김한들;김철
    • 조명전기설비학회논문지
    • /
    • 제20권5호
    • /
    • pp.33-41
    • /
    • 2006
  • 관례의 전력계통에서는 스위칭 컨트롤러, 반도체 전력변환 설비, 사무 자동화 기기, PC 등으로 인하여 중성선에 많은 양의 영상 고조파가 발생하게 된다. 이러한 중성선 영상 고조파 전류를 줄이기 위하여 리액터의 일종인 NHER (Neutral-line Harmonics Eliminating Reactor)를 설계하고 해석하는 연구를 수행하였다. C++프로그램을 활용하여 NHER의 설계프로그램을 개발하였고, 설계프로그램을 확인하기 위해 380/220[V], 200[A]의 모델을 적용하여 설계 및 해석하였다. 최적화 설계 결과 철손이 26[%] 저감되었고, 특히 9 고조파는 다른 고조파에 비하여 크게 감소하였다. NHER을 설계할 때에는 실제 적용되는 부하의 영상고조파나 효율 등을 고려하면 더 좋은 결과가 나올 것이다.

전압 플리커 및 고조파 보상을 위한 배전용 STATCON의 제어알고리즘 개발 (Development of Control Algorithm of D-STATCON(Distribution STATic-CONden: Compensations of Voltage Flicker and Harmonics)

  • 전영수;오관일;이기선;추진부
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 C
    • /
    • pp.1282-1286
    • /
    • 1999
  • This paper presents the DQ transfomation and space vector modulation method to develop a control algorithm of distribution STATCON(STATic CONdenser) for line voltage regulation, dc link voltage regulation and harmonics compensation. The Performance analysis of a PI with ramp comparision and synchronous reference frame current controller is carried out. Based on these analysis, the control performances are desirable to compensate the harmonics and to regulate de link and line voltage of Distribution line.

  • PDF

시간고조파를 함유하는 전력량의 측정 및 해석 (The Measurement and Analysis of the Electric Power Energy with Time Harmonics)

  • 장석명;박영태;정연호;이현구;서진호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1995년도 추계학술대회 논문집 학회본부
    • /
    • pp.43-45
    • /
    • 1995
  • In accordance with the development of switching devices, the voltage and current signal have involved the time harmonics. But most power meter is designed to operate in sinusoidal signal. Therefore, this paper evaluate the operating state and characteristic of power meter under the voltage and current included the time harmonics, analysing the results which are obtained by means of theorical analysis and an experiment of several instruments for power measuring.

  • PDF