• Title/Summary/Keyword: HV power lines

Search Result 3, Processing Time 0.016 seconds

Measurement and Modeling of Personal Exposure to the Electric and Magnetic Fields in the Vicinity of High Voltage Power Lines

  • Tourab, Wafa;Babouri, Abdesselam
    • Safety and Health at Work
    • /
    • v.7 no.2
    • /
    • pp.102-110
    • /
    • 2016
  • Background: This work presents an experimental and modeling study of the electromagnetic environment in the vicinity of a high voltage substation located in eastern Algeria (Annaba city) specified with a very high population density. The effects of electromagnetic fields emanating from the coupled multi-lines high voltage power systems (MLHV) on the health of the workers and people living in proximity of substations has been analyzed. Methods: Experimental Measurements for the Multi-lines power system proposed have been conducted in the free space under the high voltage lines. Field's intensities were measured using a referenced and calibrated electromagnetic field meter PMM8053B for the levels 0 m, 1 m, 1.5 m and 1.8 m witch present the sensitive's parts as organs and major functions (head, heart, pelvis and feet) of the human body. Results: The measurement results were validated by numerical simulation using the finite element method and these results are compared with the limit values of the international standards. Conclusion: We project to set own national standards for exposure to electromagnetic fields, in order to achieve a regional database that will be at the disposal of partners concerned to ensure safety of people and mainly workers inside high voltage electrical substations.

Fault Location of Underground Cables Using Travelling Wave (반사파를 이용한 지중케이블의 고장점 탐지연구)

  • Sun, J.H.;Kang, D.S.;Ryoo, H.S.
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.1972-1974
    • /
    • 2000
  • In this paper, we made an experiment on fault location of underground cables with travelling wave. The 5C2V coaxial cables of 100, 200m length, connected with discharge gap, are used for simplifying model cable lines of power cable. And 100KHz -2MHz CT and HV probe are installed at one side of the ends. We made travelling pulse in discharge gab and then pulse travelled along the cable to the both ends. Therefore, it is detected in CT and HV probe. Measuring the time difference of the pulse start and arrival, we were able to obtain the distance of pulse travelling. Consequently, our experimental results show the possibility to detect fault location of underground cables with travelling wave.

  • PDF

A Study on the Adaptive Single Pole Auto-Reclosure Techniques for Transmission Lines Based on Discrete Fourier Transform (DFT를 이용한 송전선로 적응적 단상재폐로 방안에 관한 연구)

  • Radojevic, Zoran;Kang, Seung-Ho;Park, Jang-Soo
    • Proceedings of the KIEE Conference
    • /
    • 2002.07a
    • /
    • pp.166-168
    • /
    • 2002
  • This paper presents a new numerical algorithm suitable for defining recloser reclaims time and blocking automatic reclosing during permanent faults on overhead lines. It is based on terminal voltage input data processing. The decision if it is safe or not to reclose is determined from the voltage signal of faulted and tripped line phase using Total Harmonic Distortion factor calculated by Discrete Fourier Transform. The algorithm was successfully tested using signals recorded on the real power system. The tests demonstrate the ability of presented algorithm to determine the secondary arc extinction time and to block unsuccessful automatic reclosing of HV lines with permanent fault.

  • PDF