이종 복합 메카니즘 HIF 기구의 충격저감시스템 해석 (Analysis of Isolation System in Distinct Multi-mechanism HIF Device)

  • 최의중;김효준
    • 한국정밀공학회지
    • /
    • 제22권2호
    • /
    • pp.53-59
    • /
    • 2005
  • In this study, the isolation system for multi-mechanism HIF (high impulsive force) device has been investigated. For this purpose, parameter optimization process has been performed based on the simplified isolation system model under constraints of moving displacement and transmitted force. The design parameters for multi-mechanism HIF device have been derived with respect to HIF system I and HIF system II, respectively. In order to implement the dynamic absorbing system, the dual stage hydro-pneumatic damper and magnetorheological damper with semi-active control scheme are considered. Finally, the performance of the designed prototype isolation system has been evaluated by experimental works under actual operating conditions.

지지부 동특성을 고려한 HIF 시스템의 충격력 예측 (Transmitted Force Estimation of Prototype HIF System Considering Flexibility of Mount System)

  • 김효준;최의중
    • 한국정밀공학회지
    • /
    • 제22권4호
    • /
    • pp.107-112
    • /
    • 2005
  • In this study, the dynamic analysis is performed fur predicting the transmitted force to flexible human body induced by prototype HIF(High Impulsive force) device operation, which is partially assembled by major parts. A beam-mass model and a shear-structure model are used for the flexible mount structure and their dynamic behavior are investigated by experimental results under rigid/flexible mount conditions using a general purpose device. From the test result of prototype device in rigid mount condition, the transmitted force to human body which can not be measured directly, is estimated based on the proved mount structure model.

웨이브렛 계수를 이용한 고저항 지락고장 감시데이터 산출방법 연구 (A Study on the Developing Method of HIF Monitoring Data using Wavelet Coefficient)

  • 정영범;정연하;김길신;이병성;배승철
    • 전기학회논문지
    • /
    • 제62권2호
    • /
    • pp.155-163
    • /
    • 2013
  • As the increasing HIF(High Impedance Fault) with the arc cannot be easily detected for the low fault current magnitude compared to actual load in distribution line. However, the arcing current shows that the magnitude varies with time and the signal is asymmetric. In addition, discontinuous changes occur at starting point of arc. Considering these characteristics, wavelet transformation of actual current data shows difference between before and after the fault. Althogh raw data(detail coefficient) of wavelet transform may not be directly applied to HIF detection logic in a device, there are several developing methods of HIF monitoring data using the original wavelet coefficients. In this paper, a simple and effective developing methods of HIF monitoring data were analized by using the signal data through an actual HIF experiment to apply them to economic devices. The methods using the sumation of the wavelet coefficient squares in one cycle of the fundamental frequency as the energies of the wavelet coefficeits and the sumation of the absolute values were compared. Besides, the improved method which less occupies H/W resouces and can be applied to field detection devices was proposed. and also Verification of this HIF detection method through field test on distribution system in KEPCO power testing center was performed.

스마트 그리드 배전계통에서 인공신경회로망을 이용한 DSP 기반 실시간 고장 판단 방법론 기초 연구 (DSP based Real-Time Fault Determination Methodology using Artificial Neural Network in Smart Grid Distribution System)

  • 김진언;이유림;최정우;노병훈;고윤석
    • 한국전자통신학회논문지
    • /
    • 제18권5호
    • /
    • pp.817-826
    • /
    • 2023
  • 본 논문에서는 스마트 그리드 배전 계통에서 선로상의 고장으로부터 계통을 보호하기 위한 인공 신경 회로망을 기반으로 하는 고장 판단 방법론을 제안하였다. 제안된 방법론에서는 먼저 전류 실효값 크기를 기반으로 일반 고장 여부를 판단하고 다음, 정상 전류로 판단되는 경우 인공 신경 회로망을 기반으로 하는 normal/HIF classifier를 이용하여 고 임피던스 지락 고장 여부를 판단하도록 설계하였다. 반복적인 DSP 모듈 기반 알고리즘 검증 시험들 중에서, 실효 값 크기가 최소 동작전류보다 작은 정상 전류 파형 시험인 경우에 normal/HIF classifier가 전류 파형을 정상상태로 인식하여 부 동작하였으며, 반면에, 저 임피던스 고장의 경우는 고장 상태로 인식하여 정해진 절차에 따라 재폐로 동작을 보임으로써 제안된 방법론의 유효성을 확인할 수 있었다.

A Novel Algorithm for Fault Classification in Transmission Lines Using a Combined Adaptive Network and Fuzzy Inference System

  • Yeo, Sang-Min;Kim, Chun-Hwan
    • KIEE International Transactions on Power Engineering
    • /
    • 제3A권4호
    • /
    • pp.191-197
    • /
    • 2003
  • Accurate detection and classification of faults on transmission lines is vitally important. In this respect, many different types of faults occur, such as inter alia low impedance faults (LIF) and high impedance faults (HIF). The latter in particular pose difficulties for the commonly employed conventional overcurrent and distance relays, and if undetected, can cause damage to expensive equipment, threaten life and cause fire hazards. Although HIFs are far less common than LIFs, it is imperative that any protection device should be able to satisfactorily deal with both HIFs and LIFs. Because of the randomness and asymmetric characteristics of HIFs, their modeling is difficult and numerous papers relating to various HIF models have been published. In this paper, the model of HIFs in transmission lines is accomplished using the characteristics of a ZnO arrester, which is then implemented within the overall transmission system model based on the electromagnetic transients program (EMTP). This paper proposes an algorithm for fault detection and classification for both LIFs and HIFs using Adaptive Network-based Fuzzy Inference System (ANFIS). The inputs into ANFIS are current signals only based on Root-Mean-Square (RMS) values of 3-phase currents and zero sequence current. The performance of the proposed algorithm is tested on a typical 154 kV Korean transmission line system under various fault conditions. Test results demonstrate that the ANFIS can detect and classify faults including LIFs and HIFs accurately within half a cycle.

웨이브렛 변환과 신경망 학습을 이용한 고저항 지락사고 검출에 관한 연구 (A Syudy on the Detection of High Impedance Faults using Wavelet Transforms and Neural Network)

  • 홍대승;배영철;전상영;임화영
    • 한국정보통신학회:학술대회논문집
    • /
    • 한국해양정보통신학회 2000년도 추계종합학술대회
    • /
    • pp.459-462
    • /
    • 2000
  • The analysis of distribution line faults is essential to the proper protection of power system. A high impedance fault(HIF) dose not make enough current to cause conventional protective device operating. so it is well hon that undesirable operating conditions and certain types of faults on electric distribution feeders cannot be detected by using conventional protection system. In this paper, we prove that the nature of the high impedance faults is indeed a deterministic chaos, not a random motion Algorithms for estimating Lyapunov spectrum and the largest Lyapunov exponent are applied to various fault currents detections in order to evaluate the orbital instability peculiar to deterministic chaos dynamically, and fractal dimensions of fault currents which represent geometrical self-similarity are calculated. Wavelet transform analysis is applied the time-scale information to fault signal. Time-scale representation of high impedance faults can detect easily and localize correctly the fault waveform.

  • PDF

웨이브릿 변환과 신경망 학습을 이용한 고저항 지락사고 검출에 관한 연구 (A Study on High Impedance Fault Detection using Wavelet Transform and Neural-Network)

  • 홍대승;유창완;고재호;임화영
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 B
    • /
    • pp.856-858
    • /
    • 1999
  • The analysis of distribution line faults is essential to the proper protection of power system. A high impedance fault(HIF) dose not make enough current to cause conventional protective device. It is well known that undesirable operating conditions and certain types of faults on electric distribution feeders cannot be detected by using conventional Protection system. This paper describes an algorithm using neural network for pattern recognition and detection of high impedance faults. Wavelet transform analysis gives the time-scale information. Time-scale representation of high impedance faults can detect easily and localize correctly the fault waveform.

  • PDF

Analysis of Optimal Dynamic Absorbing System considering Human Behavior induced by Transmitted Force

  • Kim, Hyo-Jun;Choe, Eui-Jung
    • International Journal of Precision Engineering and Manufacturing
    • /
    • 제4권6호
    • /
    • pp.38-43
    • /
    • 2003
  • In this study, the optimal dynamic absorbing system for the gas operated HIF (high implusive force) device has been investigated. For this purpose, firstly, the dynamic behavior of human body induced by impulsive disturbances has been analyzed through a series of experimental works using the devised test setup. The characteristics of linear impulse has been compared under some conditions of support system. In order to design the optimal dynamic absorbing system, the parameter optimization process has been performed based on the simplified isolation system model under constraints of moving displacement and transmitted force. Finally, the performance of the designed dynamic absorbing system has been evaluated by simulation in the actual operating condition.

Neuro-fuzzy network을 이용한 고장 검출 및 판별 알고리즘에 관한 연구 (A Novel Algorithm for Fault Classification in Transmission Lines using a Combined Adaptive Network-based Fuzzy Inference System)

  • 여상민;김철환;채영무;최재덕
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 하계학술대회 논문집 A
    • /
    • pp.252-254
    • /
    • 2001
  • Accurate detection and classification of faults on transmission lines is vitally important. High impedance faults(HIF) in particular pose difficulties for the commonly employed conventional overcurrent and distance relays, and if not detected, can cause damage to expensive equipment, threaten life and cause fire hazards. Although HIFs are far less common than LIFs, it is imperative that any protection device should be able to satisfactorily deal with both HIFs and LIFs. This paper proposes an algorithm for fault detection and classification for both LIFs and HIFs using Adaptive Network-based Fuzzy Inference System(ANFIS). The performance of the proposed algorithm is tested on a typical 154[kV] Korean transmission line system under various fault conditions. Test results show that the ANFIS can detect and classify faults including (LIFs and HIFs) accurately within half a cycle.

  • PDF

웨이브릿 변환과 카오스 특성을 이용한 고저항 지락사고 검출에 관한 연구 (A Study on High Impedance Fault Detection using Wavelet Transform and Chaos Properties)

  • 홍대승;임화영
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 D
    • /
    • pp.2525-2527
    • /
    • 2000
  • The analysis of distribution line faults is essential to the proper protection of power system. A high impedance fault(HIF) dose not make enough current to cause conventional protective device operating, so it is well known that undesirable operating conditions and certain types of faults on electric distribution feeders cannot be detected by using conventional protection system. In this paper, we prove that the nature of the high impedance faults is indeed a deterministic chaos, not a random motion. Algorithms for estimating Lyapunov spectrum and the largest Lyapunov exponent are applied to various fault currents detections in order to evaluate the orbital instability peculiar to deterministic chaos dynamically, and fractal dimensions of fault currents which represent geometrical self-similarity are calculated. Wavelet transform analysis is applied the time-scale information to fault signal. Time-scale representation of high impedance faults can detect easily and localize correctly the fault waveform.