• Title/Summary/Keyword: Grounding grid

Search Result 67, Processing Time 0.022 seconds

축소모델 기법을 이용한 대규모 접지계의 특성분석 (Characteristic Analysis elf Large Grounding system by Using Reduced Scale Model Method)

  • 장석훈;이재복;명성호;조연규;김점식
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제53권3호
    • /
    • pp.162-167
    • /
    • 2004
  • The scale model grounding systems to study the behavior of grounding system in uniform soils have been designed and fabricated. Constructional details and instrumentation have been discussed. To verify the accuracy of the results obtained from the experimental tests, they have been compared with computer calculation results. Also, in order to assess the effectiveness of bonding two grounding systems, grounding grid conductors which were downsized as a scale factor of 100:1 were analyzed by using the scale model method. A profile of GPR(Grounding Potential Rise) of each case was measured. The scale model grounding system presented in this paper can be valuable tool to analyze the ground potential profile and ground resistance of practical grounding system.

컴퓨터 프로그램을 이용한 접지설계 (Grounding Grid Design Using Computer Program)

  • 최종기;안용호;정길조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 일렉트렛트 및 응용기술
    • /
    • pp.165-169
    • /
    • 2002
  • Grounding grid design of substation and power generating plant has been conducted based on IEEE Std 80 or 665, which provides simple formula to estimate grounding performance such as grounding resistance, max. step and touch voltage. Although these formula are applicable for many situations, they contains many assumptions and consequent limits of application. This paper shows the limits of IEEE formula and the virtue of estimating grounding performance of grid using numerical method or computer program.

  • PDF

전력용 변전소에 설치된 메쉬 접지망의 고주파 임피던스 계산 (High Frequency Impedance Calculation of Grounding Meshes Installed at Power Substations)

  • 한풍;최창혁
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1578-1582
    • /
    • 1998
  • The ground potential rise generated by the switching surge or lightning stroke may be dangerous to personnel and cause damage to electronic control parts. For a first step to the transient performance analysis. high frequency impedances of grounding grids have been calculated and discussed. Grounding grids include 7 square grids from $10m{\times}10m$ to $80m{\times}80m$. The high frequency current was injected into the center and a corner of the grounding grid. The calculation results indicate that the impedance of the grounding grid is significantly influenced by frequency and the point of injection of the current. and the effective radius of a large grounding grid may be represented in $15{\sim}20m$.

  • PDF

보조접지그리드의 시설에 의한 대지표면전위경도의 저감 (Reduction of the the Ground Surface Potential Gradients by Installing Auxiliary Grounding Grids)

  • 이승칠;엄주홍;이복희;김효진
    • 조명전기설비학회논문지
    • /
    • 제16권2호
    • /
    • pp.121-129
    • /
    • 2002
  • 본 논문에서는 효과적인 접지그리드 설치기법에 대하여 기술하였으며, 낙뢰나 지락고장서지, 개폐서지 등으로 부터 인체의 감전보호나 컴퓨터를 비롯한 전기·전자기기의 보호를 위한 접지그리드의 시설 및 배치방법에 따른 실험적인 평가를 수행하였다. 접지그리드의 배치에 따른 대지표면전위경도의 분석과 위험전압으로 작용하는 대지 표면전위상승의 억제에 주안점을 두고 실험용 모델접지전극을 시설한 후 임 펄스전류를 인가하였다. 기존의 등간격 접지그리드의 결점을 보완하기 위해 접지그리드에 경사를 가지는 보조접지그리드를 시설하였으며, 보조접지그리드를 시설한 접지시스템에서는 인체나 전기·전자기기에 위험전압으로 작용하는 대지표면전위경도를 최대 50%이상 완화시키는 효과를 얻었다.

접지그리드의 접지임피던스의 주파수 의존성 (Frequency Dependence of Impedance of the Grounding Grid)

  • 이복희;이동문;엄주홍;김교운
    • 조명전기설비학회논문지
    • /
    • 제17권5호
    • /
    • pp.22-28
    • /
    • 2003
  • 본 논문에서는 접지임피던스의 주파수 의존성에 대하여 기술하였다. 사용중인 접지시스템의 과도응답특성을 평가기법을 제안하기 위하여 가변주파수 인버터와 대역통과 필터를 사용하여 인가전류의 주파수를 가변시키면서 접지임피던스를 측정하였다. 20[Hz]∼2.1[kHz] 범위의 주파수에서 접지임피던스의 크기와 위상을 분석한 결과 접지임피던스는 인가전류의 주파수가 증가함에 따라 증가하는 경향을 나타내었다. 22.9[kV] 변전실 접지시스템에서 인가전류의 주파수가 2[kHz]일 때 측정한 접지임피던스는60[Hz]일 때 보다 거의 3배 정도 증가하였다. 접지시스템의 주파수 의존성은 접지도체의 인덕턴스에 의해 나타나는 리액턴스 성분에 기인하는 것으로 나타났다. 따라서 뇌서지 보호용 접지시스템에서는 인덕턴스를 줄이는 방향으로 접지그리드의 형태와 규모를 결정하는 것이 필수적이다.

Investigation of Large-scale Transmission Tower Grounding Grid with High Amplitude and Uniform Flowing Impulse Current

  • Yang, Shuai;Huang, Jiarui;Wei, Shaodong;Zhou, Wenjun
    • Journal of Electrical Engineering and Technology
    • /
    • 제13권5호
    • /
    • pp.2050-2058
    • /
    • 2018
  • Impulse characteristic of transmission tower grounding grid is needed for lightning protection of transmission line. This paper describes an outdoor experimental test facility established for large-scale grounding grid of transmission tower, made up of four impulse current generators and a circle current return electrode. The amplitude of impulse current is up to 100 kA. The results of the CDEGS simulation and GPR measurement reveal the uniform current distribution in the test arrangement. An impulse test for a square electrode with extended conductors is carried out in condition of three current waveforms with different amplitude. Based on the electrical network model and iterative algorithm method, a calculation model is proposed to simulate the impulse characteristic of large-scale grounding grid considering soil ionization. The curve of impulse resistance against the current amplitude shows the soil ionization both from the simulation and test. Deviation between the simulation and test result is less than 15%.

대형접지전극시스템 접지임피던스의 측정 (Measurement of Grounding Impedances in Large-scale Grounding Electrode Systems)

  • 이경훈;최종혁;최영철;이규선;이복희
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2008년도 추계학술대회 논문집
    • /
    • pp.193-196
    • /
    • 2008
  • In these days, large structures are constructed and bonded with ground grid Because the distances between mesh and auxiliary electrodes are not enough in downtown areas, it is very difficult to measure the ground resistance of large scale grounding electrode systems. Actually the auxiliary electrodes for test are installed in grounding grid. This paper present the experimental results of ground resistance and impedance according to the location of auxiliary electrode. As a result, we get much lower resistances and impedances than real values the auxiliary electrodes are placed in the ground grid. In case that the auxiliary electrodes are located in the ground grid the resistances are very low and reactance only is inductive component.

  • PDF

반구형 접지모의시스템을 이용한 접지전극의 형상에 따른 대지전위상승의 분석 (The Analysis of Ground Potential Rise for Shapes of Grounding Electrode Using Hemispherical Grounding Simulation System)

  • 길형준;최충석;이복희
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권7호
    • /
    • pp.319-325
    • /
    • 2005
  • In order to analyze ground potential rise of grounding system installed in buildings, the hemispherical grounding simulation system has been designed and fabricated as substantial and economical measures. Ground potential rise(GPR) has been measured and analyzed for shapes of grounding electrode using the system in real time. The system is apparatus to have a free reduced scale for conductor size and laying depth of a full scale grounding system and is constructed so that a shape of equipotential surface is nearly identified a free reduced scale with a real scale when a current flows through grounding electrode. The system was composed of a hemispherical water tank, AC Power supply, a movable potentiometer, and test grounding electrodes. The test grounding electrodes were fabricated through reducing grounding electrode installed in real buildings such as rod type, mesh grid type. When a mesh grid type was associated with a rod type, GPR was the lowest value. The proposed results would be applicable to evaluate GPR in the grounding systems. and the analytical data can be used 0 stabilize the electrical installations and prevent the electrical disasters.

접지계의 경년변화 특성에 관한 연구 (A Study on the Secular Change Characteristics of Grounding Systems)

  • 김재이
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권5호
    • /
    • pp.224-226
    • /
    • 2005
  • In this paper, the secular changes of buried grounding electrodes was investigated; the electrodes are such facilities as grounding grid, grounding connector, grounding terminal and grounding rod etc.. The corrosiveness of removed substation grounding electrodes after commercial operation more than 50 years was measured and its conductivity deterioration trend was analyzed. The measuring results using three experimental methods were compared, finally the consideration for safe and economic grounding design were shown. As the result, it shows the maintenance necessity of grounding systems.

Distribution of Potential Rise as a Function of Shape of Grounding Electrodes

  • Gil, Hyoung-Jun;Choi, Chung-Seog;Kim, Hyang-Kon
    • 조명전기설비학회논문지
    • /
    • 제21권4호
    • /
    • pp.73-79
    • /
    • 2007
  • In order to analyze the potential rise of grounding systems installed in buildings, a hemispherical grounding simulation system was studied. Potential rise was measured and analyzed regarding the shape and distance of the grounding electrodes by using this system. The system was composed of a hemispherical water tank, AC power supply, a movable potentiometer, and test grounding electrodes. The potential rise was measured in real time by the horizontal moving probe of be potentiometer. The test grounding electrodes were fabricated through reducing the grounding electrode installed in real buildings such as the ground rod, grounding grid and so on. The potential rise was displayed in a two-dimensional profile and was analyzed regarding the shapes of the ground electrodes. The potential rise of the grounding grid combined with a ground rod was the lowest of every grounding electrode tested. The proposed results can be applicable to evaluating ground potential rise in grounding systems, and the analytical data can be used to stabilize the electrical installations and prevent electrical disasters.