• 제목/요약/키워드: Grounding electrode

검색결과 154건 처리시간 0.029초

수분 함유량에 따른 모래의 지중방전 특성 분석 (Analysis of soil discharge characteristics in sand with water content)

  • 이복희;김회구;박건훈;이규선;안창환
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2008년도 춘계학술대회 논문집
    • /
    • pp.436-439
    • /
    • 2008
  • It has been known that the value of soil resistance drops when a high impulse curennt is injected into a grounding electrode. In this paper, impulse generator is used to investigate the dry soil and wet soil characteristics in cylinderical test cell. The impulse resistances and breakdown characteristics were discussed based on its voltage and current traces. As a result, sand resistances are decreased with increasing the applied currents. It was thought that a decrease in resistance of dry sand with increasing current is due to both thermal and ionization processes. On the other hand, in case there is no water presence in the soil, the reduction in resistance as the currents are of dry sand increased is mainly due to the ionization process.

  • PDF

다양한 측정방법을 적용한 대지의 전기적 구조해석 (Electrical Structure Analysis of Ground using Various Methods for Resistivity Measurement)

  • 조성철;이태형;엄주홍;이복희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 제37회 하계학술대회 논문집 C
    • /
    • pp.1492-1493
    • /
    • 2006
  • Wenner 4-probe arrangement is used most widely by the method to measure soil resistivity and the measured data with the Wenner method are apparent resistivities of the soil. Therefore, the soil structure can be analyzed easily from the measured apparent resistivity, but the real soil resistivity is difficult to know correctly at a particular depth or at a specific location on earth surface. This paper introduces a method that can be used to decide the suitable burial depth and the electrode scale of a grounding rod effectively using soil structure analysis equipment based on the dipole-dipole method.

  • PDF

대형 봉상 접지전극의 뇌 임펄스 특성 (Lightning impulse characteristics of large-scale ground rods)

  • 이복희;장근철;이동문;정동철;이승칠;안창환;정용기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1849-1851
    • /
    • 2003
  • To obtain a low ground resistance in high resistivity soil, long vertical ground rods are often used. However, if the lightning current or fault current with high frequency flow into the grounding system, the ground impedance is significantly increased because of the inductive behavior. This paper presents how the impulse current works on the long vertical ground electrodes. The different shape of current was impressed between ground rods and auxiliary electrode by using impulse generator and the ground impedance was calculated from the ground potential rise.

  • PDF

접지극 형상에 따른 가로등 주변의 전위분포 (Potential Distribution near Street Linght according to the Grounding Electrode)

  • 이복희;백영환;정동철;안창환;심판섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.1453-1454
    • /
    • 2007
  • A street light is an electrical equipment to improve the traffic safety and the security for people in night. However, many accidents due to electric shock have happened in recent, people were interested in the safety of electrical facilities. And people want to know the danger by touch and step voltages. When the electric power lines fall down on the ground, the fault current flows to ground rod and the potential near the ground rod is increased to induce the high touch and step voltages. In this paper, we installed different ground rods with a street light and investigated the electrical potential according to ground methods and the types of ground rod. Finally, we examined the electrical facilities with the experimental result and present the improved technical data for the safety from electric shock

  • PDF

토양의 주파수의존성을 고려한 정보통신설비용 수평접지전극의 과도전위상승 분석 (Analysis of Transient Potential Rises of Horizontal Ground Electrodes Considering the Frequency-Dependent of Soil)

  • 안창환
    • 전자공학회논문지
    • /
    • 제53권2호
    • /
    • pp.147-153
    • /
    • 2016
  • 정보통신설비의 피뢰설계는 정보통신기기 동작의 신뢰성을 향상시키기 위해서 매우 중요한 요소이다. 특히, 뇌격전류에 의한 접지전극의 과도전위상승은 전원설비 및 정보통신기기의 절연내력의 기초 자료가 되기 때문에 정확한 해석이 요구된다. 접지전극의 과도전위상승은 접지임피던스로부터 계산되어지며, 접지임피던스는 접지전극의 형상과 토양의 주파수의존성에 크게 의존적이다. 토양의 주파수의존성은 인가된 전계에 의한 토양의 유전체 특성을 해석할 수 있는 디바이식을 적용하였다. 또한 접지임피던스로부터 과도전위상승을 계산하는 방법을 제시하였다. 디바이식을 적용한 과도전위상승 결과를 분석하기 위해서 전송선로 모델과 대지저항률이 일정한 경우에 대해서 각각 시뮬레이션을 수행하였다. 수평접지전극은 30 m이며, 표준 뇌격전류파형에 대해서 대지저항률이 10, 100, $1000{\Omega}{\cdot}m$에 대해서 각각 분석하였다. 그 결과 디바이식을 적용하여 계산된 수평접지 전극의 과도전위상승이 다른 모델의 경우보다 더 낮게 나타났다.

수중에 잠긴 접지전극주변에서 이온화에 의한 전위저감 및 에너지 방출의 평가 (Evaluation of the potential reduction and energy dispersion caused by ionization phenomena at the submerged ground rod)

  • 안상덕;최종혁;박건훈;양순만;이복희;안창환
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2008년도 추계학술대회 논문집
    • /
    • pp.337-340
    • /
    • 2008
  • When high surge voltage invaded into the ground rod contacted with ground water, the ionization phenomena are happened in the water. Although some researchers have surveyed the ionization phenomena in soil, they have just analyzed the variation of the ground resistance. The most important role of the ground rod is to elect human beings from potential rise and to dissipate energy to the earth safely. In this wort we presented the method evaluating the potential reduction and energy dispersion. Also we analyzed theses factors as a function of charging voltages at the water resistivity of $50\;{\Omega}{\cdot}m$ using the Matlab Program. As a result the ground rod potential was reduced to 38 kV by ionization just below breakdown voltage. The energy more than half of the total injected energy was dispersed through the grounding electrode caused due to ionization.

  • PDF

수평으로 매설된 도선의 접지임피던스의 주파수의존성을 계산하는 기법 (A Method of Computing the Frequency-Dependent Ground Impedance of Horizontally-buried Wires)

  • 조성철;이복희
    • 전기학회논문지
    • /
    • 제65권5호
    • /
    • pp.745-752
    • /
    • 2016
  • The parameters of Debye's equation were applied to analyze the frequency-dependent ground impedance of horizontally-buried wires. We present a new method, based on Debye's equation, of analyzing the effect of polarization on frequency-dependent ground impedance. The frequency-dependent ground impedances of a horizontally-buried wire are directly measured and calculated by applying sinusoidal current in the frequency range of 100 Hz to 10 MHz. Also, the results obtained in this work were compared with the data calculated from empirical equations and commercial programs. A new methodology using the delta-gap source model is proposed in order to calculate frequency-dependent ground impedance when the ground current is injected at the middle-point of the horizontal ground electrode. The high frequency ground impedance of horizontal electrodes longer than 30 m is larger or equal to its low frequency ground resistance. Consequently, the frequency-dependent ground impedance simulated with the proposed method is in agreement with the experimental data, and the validity of the computational simulation approach is confirmed.

Analysis of Soil Ionization Behaviors under Impulse Currents

  • Lee, Bok-Hee;Park, Geon-Hun;Kim, Hoe-Gu;Lee, Kyu-Sun
    • Journal of Electrical Engineering and Technology
    • /
    • 제4권1호
    • /
    • pp.98-105
    • /
    • 2009
  • This paper presents the characteristics of soil ionization for different water contents, and the parameters associated with the dynamic properties of a simple model grounding system subject to lightning impulse currents. The laboratory experiments for this study were carried out based on factors affecting the soil resistivities. The soil resistivities are adjusted with water contents in the range from 2 to 8% by weight. A test cell with a spherical electrode buried in the middle of the hemispherical container was used. As a result, the electric field intensity $E_c$ initiating ionization is decreased with the reduction of soil resistivities. Also, as the water content increased, the pre-ionization resistance $R_1$ and the post-ionization resistance $R_2$ became lower with increasing current amplitude. The time-lag to ionization $t_1$ and the time-lag to the second current peak $t_2$ at high applied voltages were significantly shorter than those of low applied voltages. It was found that the soil ionization behaviors are highly dependent on the water content and the applied voltage amplitude.

Performance Evaluation of Early Streamer Emission Lightning Air Terminal

  • Choi, Sang-Won;Her, Yong
    • International Journal of Safety
    • /
    • 제5권2호
    • /
    • pp.18-23
    • /
    • 2006
  • Studies have claimed that ESE (Early Streamer Emission) air terminals offer a vastly increased zone of protection over that of traditional lightning rods (Franklin rods) by causing the emission of an upward streamer/leader: The upward streamer/leader will propagate towards the tip of the downward leader at an early stage in the attachment process.. This paper shows the results of a performance evaluation test of a particular type of the ESE air terminal (called "ElecHippo") with a simple rod tested at the Korea Electrotechnology Research Institute (KERI). The corona emission current of the ElecHippo made by Yong-Jin Enterprise Corp. has also been measured at the Occupational Safety & Health Research Institute (OSHRI). The results show that the ElecHippo meets the French standard of NFC 17-102-1995. The results also verify the ESE performance by measuring the ion emission current generated in the discharge electrode gap as a function of the capacitance and inductance of the equipped devices. Finally, we propose a new method for grounding the system to reduce the lightning damage by combining the ESE air terminal, the early discharge earth plate, the lightning strike recorder and the surge protection device.

탄소블록과 동봉의 접지임피던스 비교 분석 (Comparative Analysis on Ground Impedance for a Carbon Block and a Copper Rod)

  • 서재석;박희철;길경석;오재근
    • 한국전기전자재료학회논문지
    • /
    • 제26권6호
    • /
    • pp.472-477
    • /
    • 2013
  • This paper carried out the comparative analysis on ground impedance of a carbon block and a copper rod. Two types of grounding electrode were compared ; a carbon block (L : 1 m, ${\Phi}$ : 245 mm) buried at a depth of 0.8 m and a three-linked copper rod (L : 1 m, ${\Phi}$ : 10 mm) of equilateral triangles with 1 m spacing. Ground impedance depending on applied current source was evaluated by the application of a sine wave current with 60 Hz ~ 3.5 MHz, a fast-rise pulse with rising time of 200 ns, a standard lightning impulse of $8/20{\mu}s$ and a 600 Hz square wave. Ground impedance for both electrodes were almost the same value below 100 kHz, and increased rapidly afterwards. The maximum ground impedance appeared $400{\Omega}$ at around 1.5 MHz. Ground impedance of the carbon block was lower at the square wave and was higher at fast-rise pulse than that of the copper rod. Also, ground impedance as ages showed no difference for the last 8 months. From the results, it is likely that ground performance for both electrodes shows no difference against commercial frequency and lightning impulse current, while the copper rod shows better performance against a fast-rise pulse with rise-time of a few hundred ns.