Analysis of Touch Voltage and Step Voltage using a Potential Distribution Characteristic (전위분포특성을 이용한 접촉전압과 보폭전압의 분석)

  • Lee, Bok-Hee;Jung, Hyun-Uk;Choi, Jong-Hyuk;Cho, Sung-Cheol;Beak, Young-Hwan;Lee, Kyu-Sun;Ahn, Chang-Hwan
    • Proceedings of the KIEE Conference
    • /
    • 2006.07c
    • /
    • pp.1474-1475
    • /
    • 2006
  • This paper describes touch and step voltage in the reinforced concrete and steel poles. Ground surface potential rises were measured as a function of the separation between pole and ground rod. Touch and step voltage are calculated on the basis of the distribution of ground surface potential rises. As a result, touch and step voltages strongly depend on the position of installation of ground rod.

  • PDF

Effects of the Length of Down Conductors on Transient Ground Impedances (인하도선의 길이가 과도접지임피던스에 미치는 영항)

  • Lee, Bok-Hee;Lee, Su-Bong;Jeong, Dong-Cheol
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.4
    • /
    • pp.72-77
    • /
    • 2006
  • This paper presents the transient impedance behaviors according to the length of down conductors of grounding systems to lightning impulse currents. The potential rise and effective impulse ground impedance of the deeply-driven ground rod and grounding grid subjected to the impulse currents were measured and analyzed as a function of the rise time of impulse currents and lengths of down conductor. The transient ground impedances strongly depend on the configuration and size of grounding electrodes, the waveform of impulse currents and the length of down conductors, and the installation methods reducing the inductance of down conductors are an important factor to decrease the transient ground impedances.

Study for shielded enclosure and rod grounding electrode (쉴딩차폐와 봉상접지에 관한 연구)

  • Kim, Ju-Chan;Kim, Sung-Sam;Choi, Jong-Gyu;Lee, Chung-Sik;Koh, Hee-Seog
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2006.05a
    • /
    • pp.414-417
    • /
    • 2006
  • Especially, the case which the facilities have been shielded in the building. In this case there must be suitable grounding system, and this case must be considered sufficiently to the one part of the design at the design. in addition there must be an electric leakage defense system and The case to be a criterion signal ground system. Rod type grounding electrodes is applied much and we studied the relation that rod type grounding method and shielding room as newly grounding object. in this paper, shield room is the object(target) to be established newly additionally, we try to describe about the flow of a grounding technology concept change and a ground facilities.

  • PDF

The Flashover Characteristics of Test Electrodes against Clearance of Air Insulation for 765kV Transmission Line (765kV급 송전선로 공기절연거리 설정을 위한 시험전극의 섬락전압 특성)

  • Kim, Y.T.;Kim, Y.B.;Lee, H.H.;Kim, J.M.;Kim, J.B.
    • Proceedings of the KIEE Conference
    • /
    • 1995.07c
    • /
    • pp.1337-1340
    • /
    • 1995
  • For the purpose of rational design of air insulation, it is need to experiment with similar to real shape test object and conform the characterisics. But basic distances of air insulation of transmission line, tower, etc. can be acquired from flashover characteristic of rod-rod, rod-plane electrodes. In this paper, before field test of 765kV transmission line for determination of distances of phase to ground insulation, we execute lightning, switching impulse test with test electrod(rod-rod, rod-plane) against clearances of air insulation. Each tests use up-down method and consist of 30 times flashover test. Flashover data treatment program and air correction program following IEC 60-1(1987) standard were completely builted.

  • PDF

The Hammer Energy Delivered to the Drilling Rod in the SPT 1 (표준관입시험시 롯드에 전달되는 해머의 낙하에너지 평가 1)

  • 조성민;정종홍;김동수;이우진
    • Proceedings of the Korean Geotechical Society Conference
    • /
    • 2001.03a
    • /
    • pp.469-476
    • /
    • 2001
  • The Ν-value in the standard penetration test(SPT) is affected by the magnitude of the rod penetration energy transmitted from the falling hammer as well as the geotechnical characteristics of the ground. Understanding of the striking energy efficiency in the SPT equipment is getting important for that reason. The energy efficiencies of the doughnut hammer with the hydraulic lift system and the automatic trip hammer system were investigated through field tests using the instrumented rod and wave-signal acquisition systems including the pile driving analyzer(PDA) . The rod energy ratio, ΕR$\_$r/ was defined as the ratio of the energy delivered to the drilling rod to the potential free-fall energy of the hammer. It appears that the type of the hammer and lift/drop system had a strong influence on the energy transfer mechanism and ΕR$\_$r/ also varies according to the energy instrumentation system and the analysis methods.

  • PDF

Analysis of the Grounding Impedance of a Ground Rod Considering the Frequency-Dependent Resistivity and Relative Permittivity of Soil (토양의 저항률 및 비유전율의 주파수의존성을 고려한 접지봉의 접지임피던스의 해석)

  • Ahn, Chang-Hwan;Choi, Jong-Hyuk;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.1
    • /
    • pp.54-60
    • /
    • 2012
  • When the transient current with high frequency components such as lightning surges are injected the grounding electrodes, the performance of grounding electrodes should be evaluated as grounding impedance. It is restricted to analyze the grounding impedance by measurement approach since the grounding impedance is very different with the shape and size of grounding electrodes, resistivity and relative permittivity of soil and the frequency component of the injected current. So a variety of simulation approaches have been developed. Typically, the soil resistivity measured with low frequency and relative permittivity between 1 and 80 are used for simulation of the grounding impedance. However, the resistivity and relative permittivity of soil are changed with frequency of injected current. In this paper, the frequency-dependent resistivity and relative permittivity of soil are measured and these parameters are reflected in the simulation of the grounding impedance of a ground rod. The simulated results are compared with the measured results. As a result, the simulated results with frequency-dependent soil parameters show capacitive aspect like measured results in the frequency of lower than 100[kHz] and they are more consistent with the measured results in wide frequency range.

Examinations on the Reasonable Measuring Methods of the Soil Resistivity for Design of Grounding System (접지시스템의 설계를 위한 대지저항률의 합리적인 측정방법 고찰)

  • Lee, Bok-Hee;Kim, Ki-Bok;Lee, Seung-Hoon;Choi, Jong-Hyuk
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.6
    • /
    • pp.35-41
    • /
    • 2011
  • In order to design effectively the grounding system, it is very important to determine the optimum soil resistivity at the desired location of the connection to earth. This paper deals with the reasonable methods of measuring the soil resistivity where grounding electrodes are buried. The soil resistivity at three test sites with different resistivity of soil were measured as functions of the spacing between the test probes in the Wenner's four-point method and the length of test ground rod in the three-point method. In the case of the three-point method, the length of test ground rod of 2-10[m] in length was appropriate in two-layered soil structure. In the length range of 2-10[m], the results measured by the three-point method using the test ground rod with the length corresponding to the spacing between the test probes of the Wenner's four-point method are in good agreement with the data obtained from the Wenner's four-point method.

Analysis of Risk Voltage for Grounding Electrode by Injection of Earth Leakage Current

  • Gil, Hyoung-Jun;Kim, Dong-Woo;Kim, Dong-Ook;Lee, Ki-Yeon;Moon, Hyun-Wook;Kim, Hyang-Kon;Kil, Gyung-Suk
    • International Journal of Safety
    • /
    • v.8 no.2
    • /
    • pp.9-14
    • /
    • 2009
  • This paper describes analysis of risk voltage for grounding electrode where earth leakage current is injected. To assess risk voltage of grounding electrode, the grounding simulator and CDEGS program were used to obtain measured data and theoretical results of this study. The grounding simulator was composed of a hemispherical water tank, AC power supply, a movable potentiometer, and test grounding electrodes. The shapes of grounding electrode model was ground rod. The potential rise was measured by grounding simulator, and the touch and step voltages were computed by CDEGS program. As a consequence, the potential rise of ground rod abruptly decreases with increasing the distance from the grounding electrode to the point to be tested. The touch voltage above the ground rod was low, but the step voltage was high. The measured results were compared with the computer calculated data and were known in good agreement.

Analysis of Grounding Resistance and Soil Resistivity Using Mock-up System in Jeju Soil (제주토양 목업시스템을 사용한 접지저항 및 대지저항률 분석)

  • Boo, Chang-Jin;Ko, Bong-Woon;Kim, Jeong-Hyuk;Oh, Seong-Bo
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.17 no.8
    • /
    • pp.536-543
    • /
    • 2016
  • The installation of grounding systems is important for the safe operation of power systems, and the soil resistivity is an important design consideration for such systems. It varies markedly with the soil type, moisture content and temperature. The Jeju geological structure is formed in a multi-layered structure characteristic of volcanic areas and, and the geological ground resistance values can appear even constructed the same areas ground system different from the soil structure. In this study, a mock-up system using representative soil from Jeju was constructed to analyze the variation of the grounding resistance. The mock-up system was configured using the Gauss-Newton algorithm inversion method to analyze the model numerically using the Wenner method through the soil resistivity measurements used to create the ground model. Also, we analyzed the change in the general ground resistance characteristics of the copper rod, copper pipe, and carbon rod that are used for grounding. The variation of the grounding resistance with the hydration status was found to be $2.9[{\Omega}]$, $16.5[{\Omega}]$ and $20.1[{\Omega}]$ for the copper rod, copper pipes, and carbon rod, respectively, and the influence of the ground moisture resistance of the carbon rod was found to be the lowest with a value of $141[{\Omega}]$.

Dynamic analysis and controller design for a slider-crank mechanism with piezoelectric actuators

  • Akbari, Samin;Fallahi, Fatemeh;Pirbodaghi, Tohid
    • Journal of Computational Design and Engineering
    • /
    • v.3 no.4
    • /
    • pp.312-321
    • /
    • 2016
  • Dynamic behaviour of a slider-crank mechanism associated with a smart flexible connecting rod is investigated. Effect of various mechanisms' parameters including crank length, flexibility of the connecting rod and the slider's mass on the dynamic behaviour is studied. Two control schemes are proposed for elastodynamic vibration suppression of the flexible connecting rod and also obtaining a constant angular velocity for the crank. The first scheme is based on feedback linearization approach and the second one is based on a sliding mode controller. The input signals are applied by an electric motor located at the crank ground joint, and two layers of piezoelectric film bonded to the top and bottom surfaces of the connecting rod. Both of the controllers successfully suppress the vibrations of the elastic linkage.