• 제목/요약/키워드: Gap arrester

검색결과 14건 처리시간 0.032초

송전선로용 폴리머 피뢰기의 직렬공극 특성 (Series-Gap Characteristics of Polymeric Arrester for Transmission Line)

  • 조한구;유대훈;이용순;김종채
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2008년도 하계학술대회 논문집 Vol.9
    • /
    • pp.491-492
    • /
    • 2008
  • This paper describes the series-gap characteristics of transmission line arrester with switching and lightning impulse flashover test. The transmission line arrester exhibited external gap because it is must not flashover with switching impulse on the other hand it is must flashover with lightning impulse. In accordance, minimum and maximum length of series-gap was determinated with these tests. As gap length is increased flashover voltage was increased in the range of 315.4 kV~496.3 kV and negative polarity exhibited a high voltage. As a result, It was thought tat the series-gap length of transmission line arrester exhibited in the range of 580 mm~1100 mm.

  • PDF

개폐서지 및 뇌충격 섬락시험에 따른 송전 피뢰기의 직렬공극 특성 (Series-Gap Characteristics of Transmission Line Arrester with Switching and Lightning Impulse Flashover Test)

  • 조한구;유대훈
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 추계학술대회 논문집
    • /
    • pp.484-485
    • /
    • 2007
  • This paper describes the series-gap characteristics of transmission line arrester with switching and lightning impulse flashover test. The transmission line arrester exhibited external gap because it is must not flashover with switching impulse on the other hand it is must flashover with lightning impulse. In accordance, minimum and maximum length of series-gap was determinated with these tests. As gap length is increased flashover voltage was increased in the range of 315.4 kV~496.3 kV and negative polarity exhibited a high voltage. As a result, It was thought tat the series-gap length of transmission line arrester exhibited in the range of 580 mm~1100 mm.

  • PDF

직렬 갭 피뢰기의 흡습시 전극표면의 변화 및 특성 (Characteristics and Change of Electrode Surface in Moisture Absorption on the Series Gap Surge Arrester)

  • 조한구;김향숙
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 하계학술대회 논문집 Vol.4 No.2
    • /
    • pp.1172-1175
    • /
    • 2003
  • The characteristics and change of electrode surface about Gap type surge arrester for protect DC subway rail were investigated with moisture absorption. Compared that tested about DC/AC discharge commencement voltage, residual voltage, Impulse, square wave impulse for DC rail surge arrester about Gap type surge arrester of moisture absorption state. The AC discharge commencement voltage acted greatly effect of moisture absorption than the DC discharge commencement voltage test.

  • PDF

내뢰성 향상을 위한 154 kV 송전선용 피뢰기의 성능 시험 (A Type Test of 154 kV Transmission Line Arrester for improvement of lightning performance)

  • 곽주식;강연욱;우정욱;심응보;박윤석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.454-456
    • /
    • 2003
  • This paper describes a type test results of 154 kV transmission line arrester with external gap. The test was carried on surge arrester unit and line arrester with external gap, respectively. Withstand voltage test demonstrate the voltage withstand capability of the line arrester with external series gap under the dry and wet conditions. In insulation coordination test external series gap shall be discharged every time when lightning impulse voltage with the steepness of more than 1500 $kV/{\mu}s$ are applied under the wet condition.

  • PDF

Optimal Design of a Follow Current Disconnector for DC Arresters in Traction Vehicles

  • Wang, Guoming;Kim, Sun-Jae;Park, Seo-Jun;Kil, Gyung-Suk;Ji, Hong-Keun
    • Transactions on Electrical and Electronic Materials
    • /
    • 제17권5호
    • /
    • pp.289-292
    • /
    • 2016
  • This paper dealt with the optimal design of a follow current disconnector for DC arresters used in electric traction vehicles. The disconnector separates the ground lead from an arrester to prevent a line-to-ground fault of an aged arrester and should not affect the operation and function such as the reference and the clamping voltage of the connected arrester. The designed disconnector is composed of a resistor, a spark gap, and a cartridge. The results showed that the sparkover voltage increased with the gap distance whereas the reference voltage was almost the same as that without the disconnector. The sparkover voltage was 3.95 kV when the gap distance was 0.5 mm. Regardless of the gap distance, the reference and the clamping voltage of the assembled disconnector with an arrester were measured to be the same as those of the arrester alone.

송전선로에 사용되는 갭형 피뢰기 소자의 뇌임펄스 전류특성 (Characteristics of Lightning Impulse Current of Zno Block for Transmission Line Arrester with External Gap)

  • 조한구;유대훈
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2009년도 춘계학술대회 논문집
    • /
    • pp.61-62
    • /
    • 2009
  • This paper describes the characteristics of lightning impulse current of ZnO block for transmission line arrester with external gap. The ageing parameters of lightning arresters ate impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by impulse current. Total energy applied to the ZnO arrester each time is $4/10{\mu}s$, 30kA and $2/20{\mu}s$, 10kA impulse current. Before and After the test, the residual voltage variation of varistors passed was below 5%. According to the test, it is thought that the ZnO arrester shows good stability with impulse current test.

  • PDF

송전선로에 사용되는 갭형 피뢰기 소자의 뇌임펄스 전류특성 (Characteristics of Lightning Impulse Current of ZnO Block for Transmission Line Arrester with External Gap)

  • 조한구;유대훈
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2007년도 하계학술대회 논문집 Vol.8
    • /
    • pp.458-459
    • /
    • 2007
  • This paper describes the characteristics of lightning impulse current of ZnO block for transmission line arrester with external gap. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by impulse current. Total energy applied to the ZnO arrester each time is $4/10{\mu}s$, 30kA and $2/20{\mu}s$, 10kA impulse current. Before and After the test, the residual voltage variation of varistors passed was below 5%. According to the test, it is thought that the ZnO arrester shows good stability with impulse current test.

  • PDF

Series Gap Type 피뢰기의 뇌임펄스 동작책무 및 온도의존성에 관한 연구 (A Study of Lightning Impulse Operating Duty and Temperature Dependence of Series Gap Type Arrester)

  • 조한구;유대훈
    • 한국전기전자재료학회논문지
    • /
    • 제22권8호
    • /
    • pp.659-664
    • /
    • 2009
  • This paper describes lightning impulse operating duty performance and temperature dependence of series gap type for transmission line arresters. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by lightning impulse current. In the discharge withstand test, total energy applied to the ZnO arrester each time is 4/10 ${\mu}s$, 30 kA. and in the operating duty test, the arrester has passed the test if thermal stability is achieved, if the residual voltage measured before and after the test is not changed by more than 5 %, and after the test reveals no evidence of puncture, flashover or cracking of the ZnO block. As a results, the residual voltage was in the range of 17.2${\sim}$20.3 kV and ZnO block bear up against at 2 shot of series impulse current of 30 kA. Also it was so excellent that the mechanical destruction does not occur at the 2 groups of 5 impulses current of 2/20 ${\mu}s$ 10 kA. According to the tests, it is thought that the ZnO arrester shows good stability with impulse current test. and it was found that the ambient temperature is increased resistive leakage current was increased in the range 47.3${\sim}$167.4 ${\mu}A$.

전차선로에서의 뇌격에 의한 가공지선과 보안기의 차폐효과 (Effects of an Overhead Ground Wire and Surge Arrester in the Railway due to Lightning Strokes)

  • 임성정;김재철;창상훈;정용철
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2000년도 춘계학술대회 논문집
    • /
    • pp.93-99
    • /
    • 2000
  • Using the EMTP(Electro Magnetic Transient Program) for the analysis of lightning direct voltage on the railway system, the shielding effects of overhead grounding wire on the railway were studied quantitatively. Installation of overhead ground wire and gap-type arrester such as s-horn Provides a 6.6㎸ HV distribution line with good protection effects. Even severe lightning induced voltage were create, 6.6㎸ HV lines can be withstand.

  • PDF

송전선로 피뢰기 적용 및 외부 갭형과 갭레스형의 동작특성 비교 (Comparison on Characteristics between air-gap type and gapless In transmission LA)

  • 유희영;김종채;김병헌;박윤석;이봉희
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.347-348
    • /
    • 2008
  • This paper presents the use of Line Surge Arresters on 154kV double circuit lines. The ouatge rate which is highly related to the tower footing resistance is showed during the last a few year. The general methods that have been adopted at lines also are introduced. Lightning performance of lines without and with line surge arrester is studied and compared. The characteristics between air-gap type and gapless type LSA also compared. Line surge arrester installation strategy is presented.

  • PDF