• 제목/요약/키워드: GCHP

검색결과 10건 처리시간 0.022초

학교 건물용 지열 히트펌프 시스템 설계와 지중 순환수 온도 변화 분석 (Design of Ground-Coupled Heat Pump (GCHP) System and Analysis of Ground Source Temperature Variation for School Building)

  • 손병후
    • 한국지열·수열에너지학회논문집
    • /
    • 제16권1호
    • /
    • pp.17-25
    • /
    • 2020
  • Ground-coupled heat pump (GCHP) systems have become an efficient alternative to conventional cooling and heating methods due to their higher energy using efficiency. Although some experimental and simulation works related to performance analysis of GCHP systems for commercial buildings have been done, relatively little has been reported on the performance evaluation of GCHP systems for school buildings. The purpose of this simulation study is to evaluate the performance of a hypothetical GCHP system for a school building in Seoul. We collected various data of building specifications and construction materials for the building and then modeled to calculate hourly building loads with SketchuUp and TRNSYS V17. In addition, we used GLD (Ground Loop Design) V2016, a GCHP system design and simulation software, to design the GCHP system for the building and to simulate temperature of circulating water in ground heat exchanger. The variation of entering source temperature (EST) into the system was calculated with different prediction time and then each result was compared. For 20 years of prediction time, EST for baseline design (Case A) based on the hourly simulation results were outranged from the design criteria.

단독주택 적용 지열 히트펌프 시스템의 성능 분석 (Performance Simulation of Ground-Coupled Heat Pump(GCHP) System for a Detached House)

  • 손병후;최종민;최항석
    • 설비공학논문집
    • /
    • 제23권6호
    • /
    • pp.392-399
    • /
    • 2011
  • Ground-coupled heat pump(GCHP) systems have been shown to be an environmentally-friendly, efficient alternative to traditional cooling and heating systems in both residential and commercial applications. Although some work related to performance evaluation of GCHP systems for commercial buildings has been done, relatively little has been reported on the residential applications. The aim of this study is to evaluate the cooling and heating performances of a vertical GCHP system applied to an artificial detached house($117\;m^2$) in Seoul. For this purpose, a typical design procedure was involved with a combination of design parameters such as building loads, heat pump capacity, borehole diameter, and ground thermal properties, etc. The cooling and heating performance simulation of the system was conducted with different prediction times of 8760 hours and 240 months. The performance characteristics including seasonal system COP, average annual power consumption, and temperature variations related to ground heat exchanger were calculated and compared.

병원 건물에 설치된 냉각탑 병용 지열 히트펌프 시스템의 냉방 성능 (Cooling Performance of Cooling Tower-Assisted Ground-Coupled Heat Pump (GCHP) System Applied in Hospital Building)

  • 손병후;이두영;민경천
    • 한국지열·수열에너지학회논문집
    • /
    • 제12권1호
    • /
    • pp.7-16
    • /
    • 2016
  • This paper presents the measurement and analysis results for the cooling performance of ground-coupled heat pump (GCHP) system using a cooling tower as a supplemental heat rejector. In order to demonstrate the performance of the hybrid approach, we installed the monitoring equipments including sensors for measuring temperature and power consumption, and measured operation parameters from May 1 to October 30, 2014. The results showed that the entering source temperature of brine returning from the ground heat exchanger was in a range of design target temperature. Leaving load temperatures to building showed an average value of $11.4^{\circ}C$ for cooling season. From the analysis, the daily performance factor (PF) of geothermal heat pumps ranged from 4.4 to 5.2, while the daily PF of hybrid GCHP system varied from 3.0 to 4.0 over the entire cooling season.

수평형 지열 히트펌프 시스템의 냉난방 성능 분석 (Performance Analysis of Ground-Coupled Heat Pump System with Slinky-Type Horizontal Ground Heat Exchanger)

  • 손병후
    • 설비공학논문집
    • /
    • 제24권3호
    • /
    • pp.230-239
    • /
    • 2012
  • Ground-coupled heat pump (GCHP) systems utilize the immense renewable storage capacity of the ground as a heat source or sink to provide space heating, cooling, and domestic hot water. The main objective of the present study is to investigate the cooling and heating performance of a small scale GCHP system with horizontal ground heat exchanger (HGHE). In order to evaluate the performance, a water-to-air ground-source heat pump unit connected to a test room with a net floor area of 18.4 m2 and a volume of 64.4 m3 in the Korea Institute of Construction Technology ($37^{\circ}39'N$, $126^{\circ}48'E$) was designed and constructed. This GCHP system mainly consisted of slinky-type HGHE with a total length of 400 m, indoor heat pump, and measuring devices. The peak cooling and heating loads of the test room were 5.07 kW and 4.12 kW, respectively. The experimental results were obtained from March 15, 2011 to August 31, 2011 and the performance coefficients of the system were determined from the measured data. The overall seasonal performance factor (SPF) for cooling was 3.31 while the system delivered heating at a daily average performance coefficients of 2.82.

강변여과수와 천부 지하수를 이용하는 지하수 열펌프시스템의 적정유량 (Optimum Pumping Rates of Ground-Water Heat Pump System Using Groundwater or Bank Infilterated Water)

  • 한정상;한혁상;한찬;전재수;김형수
    • 자원환경지질
    • /
    • 제40권6호
    • /
    • pp.833-841
    • /
    • 2007
  • 지하수열펌프시스템(GWHP)은 지원열펌프시스템(GSHP)가운데 성능이 가장 우수하며 저온의 천부지하수열을 이용하는 시스템이다. GWHP시스템은 지중연결 열펌프시스템(GCHP)에 비해 최대 블록부하와 전 시스템 성능에 부합되는 지하수유량을 기준으로 하여 설계를 하며 최적 지하수유량은 해당지역의 지하수온도, 판형열교환기의 규격과 전체펌프와 배관류의 전 양정고에 따라 결정한다. 대체적으로 전형적인 빌딩루프순환수의 필요유량은 1RT당 $9.5{\sim}11.4lpm$ 정도인데 비해 GWHP시스템이 필요로 하는 최적 지하수유량은 이보다 꿜씬 적은 $3.8{\sim}9.5lpm$정도이다.

에너지슬래브 적용 지열원 열펌프 시스템의 성능 특성에 관한 실증 연구 (Heating and Cooling Performance of a Ground Coupled Heat Pump System with Energy-Slab)

  • 최종민
    • 설비공학논문집
    • /
    • 제24권2호
    • /
    • pp.196-203
    • /
    • 2012
  • Energy foundations and other thermo-active ground structure, energy wells, energy-slab, and pavement heating and cooling represent an innovative technology that contributes to environmental protection and provides substantial long-term cost savings and minimized maintenance. This paper focuses on earth-contact concrete elements that are already required for structural reasons, but which simultaneously work as heat exchangers. Pipes, energy slabs, filled with a heat carrier fluid are installed under conventional structural elements, forming the primary circuit of a geothermal energy system. The natural ground temperature is used as a heat source in winter and a heat sink in summer. The geothermal heat pump system with energy-slab represented very high heating and cooling performance due to the stability of EWT from energy slab. However, the performance of it seemed to be affected by the atmospheric air temperature.

ATES 열펌프 시스템 성능 및 경제성 분석에 관한 연구 (Study on the Performance of an ATES Geothermal Heat Pump System and Economic Analysis)

  • 오명석;최종민
    • 설비공학논문집
    • /
    • 제24권4호
    • /
    • pp.289-296
    • /
    • 2012
  • The aim of this study is to investigate the performance of a heating and cooling system with aquifer thermal energy storage(ATES heat pump system) known as one of the underground thermal energy storage application systems. The ATES system was composed of heat pump unit and ATES, which was installed in a factory building located in Anseoung. The system represented very high heating and cooling performance, and showed nearly constant COP at each heating and cooling season due to the stability of EWT. The economic analysis about an ATES system and a conventional system was also executed. The conventional system adopted an air-conditioner in the summer season and a LNG boiler in the winter season. The payback period of the ATES system was estimated by 6.62 years.

열응답 실험 해석 및 국내 현황 (Thermal Response Test (TRT) interpretation and the status in Korea)

  • 심병완;최충현
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2010년도 춘계학술대회 초록집
    • /
    • pp.168.2-168.2
    • /
    • 2010
  • The growing market for geothermal heat pump system requires great consideration of quality control and assurance in design and construction. The borehole heat exchanger of GHP system should be sustainable, economical and ecological. Thermal Response Test (TRT) is a useful method for site investigation to obtain reliable data for a optimal system design from the technical and economical aspect. Intensive researches combined with exchange of experiences on an international level within the IEA ECES Annex 21 improved the technology. Major subjects on the interpretation of TRT are development of improved evaluation models, evaluation of the TRT with respect to geological layers and investigation of the influence of ground water. Current status of TRT in South Korea, as well as a new version of the Korean TRT standard test procedure was presented. TRT is mostly used for governmental supported projects with corresponds to more than 100 GCHP systems per year. More than 200 tests are applied, mostly on single U-tube heat exchangers (about 95%). Bentonite is the most common grouting to be used. KIGAM (Korea Institute of Geoscience & Mineral Resources) is also keeping a GIS geological and geothermal database. In the institute also laboratory measurements of rock properties are carried out. About 90% of the laboratory measurements of the rock heat conductivity shows higher values than the in-situ TRT.

  • PDF

냉각탑 병용 하이브리드 지열 히트펌프 시스템의 성능 분석 (Performance Analysis of Cooling Tower-Assisted Hybrid Ground-Coupled Heat Pump (HGCHP) System)

  • 손병후;이두영;최재호;민경천
    • 대한기계학회논문집 C: 기술과 교육
    • /
    • 제4권1호
    • /
    • pp.19-26
    • /
    • 2016
  • 하이브리드 지열 히트펌프 시스템은 열원을 안정적으로 유지하기 위해 보조 히트싱크나 보조 열원을 활용한다. 본 연구에서는 병원 건물에 설치한 지열-냉각탑 하이브리드 시스템의 냉난방 성능을 분석하였다. 시스템에 각종 센서와 계측 장비를 설치하였으며, 2014년 2월부터 2015년 2월까지 측정한 데이터를 이용하여 성능을 분석하였다. 냉방 기간 중, 냉수 공급 온도는 평균 $11.7^{\circ}C$이었으며, 설계 온도인 $12^{\circ}C$를 넘지 않았다. 또한 난방 기간 중에는 일평균 $39^{\circ}C{\sim}40^{\circ}C$의 온수를 공급하였다. 지열 히트펌프만의 월 평균 성능지수는 3.8에서 8.4의 범위에서 변하였다. 반면 냉각탑을 포함한 하이브리드 지열시스템의 월 평균 성능지수는 2.6에서 6.6 사이에서 변하였다.

지표수 열교환기 적용 지열 히트펌프 시스템의 냉방 성능 (Cooling Performance of Geothermal Heat Pump Using Surface Water Heat Exchanger)

  • 임효재;공형진;손병후
    • 설비공학논문집
    • /
    • 제29권6호
    • /
    • pp.316-326
    • /
    • 2017
  • Commercial buildings and institutions are predominantly cooled, thereby dissipating excess heat to a vertical ground heat exchanger (VGHE), than heat extracted over an annual cycle. Surface waters, such as lakes and ponds, provide a cost-effective means of reducing the VGHE length, and in balancing the thermal loads to the ground. This paper presents the measurement and analysis of the cooling performance of ground-coupled heat pump (GCHP) system, using surface water heat exchanger (SWHE) submerged in an artificial pond. In order to measure the performance of the system, we installed monitoring equipment, including sensors, for assessing the temperature and power consumption, after which the operation parameters were determined. The results from the thermal performance test for the SWHE indicate that the temperatures at the outlet of the SWHE and within the pond were affected by outdoor air temperature. In addition, the results reveal similar variation trends on temperatures; however, the peak temperatures of the SWHE were somewhat greater than those of outdoor air, due to the thermal capacity of the pond. Analyzing the cooling performance over the measurement period, the average coefficient of performance (COP) of heat pump was found to be 5.71, while that for the entire system was 2.99.