• Title/Summary/Keyword: Frost density

Search Result 33, Processing Time 0.022 seconds

A Study of Frost Formation on Different Hydrophilic Surfaces (다른 친수성능을 가진 두 표면에서의 착상에 관한 연구)

  • 김철환;신종민;하삼철
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.6
    • /
    • pp.519-524
    • /
    • 2002
  • An experimental study has been conducted to investigate the effects of surface energy on frost formation. Test samples with two different surfaces are installed in a wind tunnel and exposed to a humid airflow. Dynamic contact angles (DCA) for these surfaces are $23^{\circ}\;and\;88^{\circ}$, respectively. The thickness and the mass of frost layer are measured and used to calculate the frost density while frost formation is visualized simultaneously with their measurements. Results show that frost density increases as time increases at specific test conditions. The air Reynolds number, the airflow humidity and the cold plate temperature are maintained at 12,000, 0.0042 kg/kg and $-21^{\circ}C$, respectively. The surface with a lower DCA shows a higher frost density during two-hour test, but no differences in the frost density have been found after two hours of frost generation. Empirical correlations for thickness, mass and density are assumed to be the functions of the test time and DCA.

An Experimental Study of Frost Formation on the Horizontal Cylinder (수평 실린더 표면의 착상에 대한 실험적 연구)

  • Paik, Sang-Jin;Lee, Yoon-Been;Ro, Sung-Tack
    • Proceedings of the KSME Conference
    • /
    • 2000.04b
    • /
    • pp.240-245
    • /
    • 2000
  • In this study, thickness, density and effective thermal conductivity of frost forming on the horizontal cylinder were measured with various air temperature and humidity. Reynolds number and temperature of cooling surface are controlled 17300 and $-l5^{\circ}C$ respectively. In each case of air temperature $5^{\circ}C,\;10^{\circ}C,\;15^{\circ}C,$ varying absolute humidity, experiments were executed. In measuring frost surface temperature and thickness of frost layer, infrared thermocouples and CCD camera were used. Frost was gathered from cylinder to measure mass of frost layer. Experimental data showed that the thickness and effective thermal conductivity of the frost layer increase with respect to time. Thickness of frost layer increase with humidity increasing, and density of frost layer increase with air temperature rising. Frost growth with air temperature and density of frost layer with humidity are affected by whether dew point is below or above freezing point.

  • PDF

Modeling for Frost Growth on a Cold Plate (냉각 평판에서 서리 성장 모델링)

  • Yang, Dong-Keun;Lee, Kwan-Soo
    • Proceedings of the KSME Conference
    • /
    • 2004.04a
    • /
    • pp.1546-1551
    • /
    • 2004
  • This paper presents a mathematical model to predict the frost properties and heal and mass transfer within the frost layer formed on a cold plate. The laminar flow equations for the air-side are analyzed. and the empirical correlations of local frost properties are employed in order to predict the frost layer growth. The correlations of local frost density and effective thermal conductivity of frost layer, obtained from various experimental conditions, are derived as functions of various frosting parameters (Reynolds number, frost surface temperature, absolute humidity and temperature of moist air, cooling plate temperature, and frost density). The numerical results are compared with experimental data and the results of various models to validate the present model, and agree well with experimental data within a maximum error of 10%. The heat and mass transfer coefficients obtained from the numerical analyses are presented, as the results, it is found that the model for frost growth using the correlation of heat transfer coefficient without solving air flow have a limitation in its application.

  • PDF

A Characteristics Study on the Visualization and Heat Transfer of the Frost Formation Structure Variation by Control Plate Surface Temperature (표면온도 제어에 의한 착상층 구조변화의 가시화 및 열전달 특성 연구)

  • Kim Kyung-Chun;Ko Choon-Sik;Jeong Jae-Hong;Ko Young-Hwan;Shin Jong-min
    • 한국가시화정보학회:학술대회논문집
    • /
    • 2002.11a
    • /
    • pp.55-58
    • /
    • 2002
  • To control the frost formation, a temperature variation of the cooling plate and characteristics on hydrophilic and hydrophobic surfaces was attempted. As a temperature variation of the cooling plate, being closely related to the frost layer density of frost layer is found to be affected by the melting process inside the frost layer during the heating period. At characteristics on surface, completely different structures of frost are appeared in the initial stage of frost formation due to the difference in surface conditions, while those effects are vanished with time. It is found that the frost thickness, density and heat flux characteristics are closely associated with the frost structure.

  • PDF

The effect of surface contact angle on the behavior of frost formation in a fin-tube heat exchanger (핀-관 열교환기의 착상 거동에 대한 표면 접촉각의 영향)

  • Lee, K. S.;Jhee, S.;Lee, D. W.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.1
    • /
    • pp.95-101
    • /
    • 2000
  • The effect of surface contact angle on the behavior of frost formation in a fin-tube heat exchanger is investigated experimentally. It is shown that both heat exchangers with hydrophilic and hydrophobic surfaces appear to have a better thermal performance than bare aluminium heat exchanger, but the improvements are very small. There is a little increase in the amount of the frost deposited onto the heat exchanger with both hydrophilic and hydrophobic surface. However, the effect of contact angle on the frost density is observed ; the frost with high density forms on the heat exchanger with hydrophilic surface ; and the frost with low density is deposited onto the heat exchanger with hydrophobic surface when compared with the frost deposited onto the heat exchanger with bare aluminium surface. This may be attributed to the fact that the shape of water droplets which condense on the surface of heat exchanger at the early stage of frosting varies with contact angle, and thus makes a difference on the structure of frost formation. From the experiments with different relative humidity of inlet air, it is shown that the variations of operating parameter make no influence on the effect of surface contact angle on the frosting behavior in the heat exchanger.

  • PDF

Correlations of Frost Properties Considering the Environmental Parameters over a Cold Flat Plate (수평편판에서의 착상인자를 고려한 서리 물성치의 상관식)

  • Lee, Kwan-Soo;Kim, Yong-Chul;Jhee, Sung
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.25 no.8
    • /
    • pp.1046-1052
    • /
    • 2001
  • This study has been performed experimentally to measure the frost properties over a cold flat plate in order to obtain the correlations of the frost properties with various environmental parameters. Correlations of the frost surface temperature, thickness, density, and thermal conductivity are presented along with the experimental results as a function of environmental parameters, distance from the leading edge of test plate, and time. These correlations can be used to predict the frost properties with a maximum error of 8% in the following ranges : air temperature 15∼25$\^{C}$, relative humidity 60∼80%, air velocity 1∼3m/s and cooling plate temperature -15∼-25$\^{C}$.

Modeling for Prediction of Frost Formation Phenomena on a Cold Plate (냉각 평판에서 착상 현상 예측을 위한 모델링)

  • Yang, Dong-Keun;Kim, Jung-Soo;Lee, Kwan-Soo
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.28 no.6
    • /
    • pp.665-671
    • /
    • 2004
  • A mathematical model is presented to predict the frost properties and heat and mass transfer within the frost layer formed on a cold plate. The model consists of the laminar flow equations for air-side and the empirical correlation of local frost density. The correlation of local frost density used in this study is obtained from various experimental conditions by considering frosting parameters. The numerical results are compared with experimental data to validate the model, and agree well with experimental data within a maximum error of 9%.

Characteristic of Frost Growth on a Cold Cylinder Surface in Cross Flow (직교류 내 원관 표면에서의 서리층 성장 특성)

  • Yang Dong-Keun;Kim Min-Soo;Lee Kwan-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.18 no.2
    • /
    • pp.122-128
    • /
    • 2006
  • In this paper, frosting experiments were conducted with variations of frosting parameters in order to obtain the correlations of frost properties. As a result, the local thickness, density, and surface temperature of the frost layer were presented. The dimensionless correlations for the frost thickness, frost density, frost surface temperature and heat transfer coefficient were derived as functions of dimensionless frosting parameters by using a dimensional analysis.

Frost Formation on a Cylinder under Heat Pump Condition (히트펌프 조건의 원형관에서의 착상에 관한 연구)

  • Yoon, Shin-Hyuk;Cho, Keum-Nam;Hayase, Gaku
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.804-809
    • /
    • 2009
  • The present study measured frost pattern on a cylinder to propose empirical correlation equations for the local and average frost thickness, frost density and frost mass. The key parameters were diameter of the cylinders (7mm, 20mm), cooling surface temperature of the circular tube, absolute humidity of air, air temperature and air velocity. A 50% ethylene glycol aqueous solution was applied as a coolant. The frost thicknesses at both front and rear were larger than those at the other parts, while they were increased as diameter of the cylinder was increased. The local frost thicknesses at high air velocity were more uniform than those at low air velocity. The values predicted by Kim et al. under the freezer condition showed larger by the maximum of $30{\sim}50%$ than the measured data under heat pump condition. The empirical correlations for the local and average frost thickness and frost mass were proposed. The correlation equations for the frost thickness and frost mass under the heat pump condition in the present study might predict more accurate than the other correlation equations. The proposed correlations might be applied for the freezer condition within the maximum 15% deviation from the previous correlations under freezer condition.

  • PDF

Numerical Model for the Analysis of Frosting Behavior (착상 거동 해석을 위한 수치적 모텔)

  • Lee, Kwan-Soo;Yang, Dong-Keun;Jhee, Sung
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.3
    • /
    • pp.261-267
    • /
    • 2002
  • The integral boundary layer equation for the air side and the diffusion equation for the frost layer are numerically analyzed in order to predict the behavior of frost layer growth. The thickness and density of the frost layer obtained from the present study agree well with those of previous numerical results and experimental data with a maximum error of 13%. The characteristics of heat and mass transfer within the frost layer and the frost layer growth along the flow direction are investigated by performing numerical analysis. The effects of operating conditions on the frost layer growth are also examined.