• Title/Summary/Keyword: Freezing protection valve

Search Result 3, Processing Time 0.018 seconds

An Experimental Study on the Freezing Protection Valve Using Phase Change Material(PCM) for the Heat Exchanger (상변화물질(PCM)을 이용한 열교환기용 동파방지밸브에 관한 실험적 연구)

  • Yun, Jea-Ho;Kim, Joung-Ha;Jeong, Soon-Young;Yang, Yoon-Sub;Kim, Seong-Hyun;Song, Duk-Yong
    • Journal of the Korean Solar Energy Society
    • /
    • v.32 no.6
    • /
    • pp.127-133
    • /
    • 2012
  • This paper is an experimental study on the freezing protection valve used for solar water heating, air-conditioning systems, and plumbing systems. When the phase change occurs from liquid to solid, most of the substances except water volumetrically shrink. And referred to as PCM(Phase Change Material) a substance with such properties, the phase change temperature varies depending on the material. To prevent the freezing of the plumbing system, such as air-conditioning system in the winter season, we developed a several types of freezing protection valve using PCM whose freezing temperature are $2-4^{\circ}C$. The working principle of the freezing protection valve is that the fluid inside the pipe is released to prevent the system-collapse when fluid temperature reaches the freezing temperature of the PCM. And then the valve is closed and returned to the original position automatically when the temperature of the operating fluid rises. In this paper, the operating temperatures, discharge flow rate and the response characteristics of the valve during the operation are tested and investigated. From the results of this research the freezing protection valves employing PCM are expected to be commercialized in the near future.

Design Verification of ECS Condenser Icing Protection System by Flight Test of T-50 Advanced Trainer (T-50 비행시험을 통한 환경제어계통 콘덴서 빙결방지 설계 검증)

  • Nam, Yong-Seog;Kim, Yeonhi;Song, Seok-Bong;Seo, Dong-Yun;Son, Won-Ik;Park, Sung-Soon
    • Journal of Aerospace System Engineering
    • /
    • v.2 no.3
    • /
    • pp.40-44
    • /
    • 2008
  • T-50 ECS(environment control system) was designed to have freezing protection for the condenser. However during the ground and flight test, the freezing problem was occurred. This paper deals with the analysis of the freezing problem and introduces anti-freezing design using ADI(Active De-Icing) logic to solve the condenser freezing problem of T-50 ECS

  • PDF

Winter to replace the hydraulic test and pneumatic test comparative analysis of study on the optimal pressure (동절기 수압시험을 대체하는 공기압시험의 적정압력 비교분석에 관한 연구)

  • Kwoun, Young-Hee;Hwang, Dong-Hwan;Kim, Tae-Gil;Kang, Kyung-Sik
    • Journal of the Korea Safety Management & Science
    • /
    • v.16 no.2
    • /
    • pp.211-216
    • /
    • 2014
  • Using a high-rise building water piping after hydrostatic test of the reliability of the leak to be completed if the pressure is maintained until the leak is not commercially available considered. Due to the nature of high-rise buildings and the construction period will take several years from the lower levels of use of the water supply and fire fighting water pipe construction is in progress, the order of which I do most of the first pipe to the construction and more than three years. So kind of riser pipe is complete, install the valve in the basement by installing an automatic pump to maintain a constant pressure after hydrostatic test and after each floor plumbing piping is complete, the progress of the hydrostatic test without undergoing a separate branch pipe the valve is opened automatically when the number of the pressing pressure of the structure. I kind of do and keep working pressure of pipe until the completion of the construction work to keep the damage to human error when it is intended to prepare. In winter, the frost protection and an alternative to drainage water pipe is damaged or deformed, even if unaware of the finishing work to the building, the use of the damage caused by a leak in a after construction of finish work to be expected. Alternative to reduce this damage if the pressure test without fear of freezing to help maintain long-term commercial pressures may be considered.