• Title/Summary/Keyword: Foam proportioner

Search Result 5, Processing Time 0.02 seconds

A Study on Foam Mixing Characteristics in Steady State to Enhance the Performance of Proportioner for Foam System (포 소화설비용 소화약제 혼합장치의 성능향상을 위한 정량 혼합특성에 관한 연구)

  • Ku, Jae-Hyun
    • Journal of the Korean Society of Hazard Mitigation
    • /
    • v.9 no.5
    • /
    • pp.63-68
    • /
    • 2009
  • This study describes to analyze foam mixing characteristics in steady state to enhance the performance of proportioner for foam system designed to accurately proportion a foam liquid concentrate into a water stream up to constant concentration. The proportioner developed is experimentally evaluated in performance evaluation system consisted of a pump, tanks, pressure gauges, flow meters, a nozzle. As a result, the foam mixing performance of the line proportioner is found to increase with increased the water flow rate due to the venturi effect and with increased the cross-sectional area of the orifice and is analysed with 3 % in the error rate of $\pm4%$. For the pressure proportioner, the foam mixing performance is analyzed to increase with increased the water flow rate and with increased the inlet pressure and is analysed with 3% in the error rate of $\pm2%$.

An Experimental Study on the Improvement of Foam Fire-Extinguishing System's Mixing Ratios by Expanding the Cross Sectional Area of the Stock Solution Inhaling Piping (원액흡입배관 단면적 확장에 의한 포 소화설비 혼합비 개선에 관한 실험적 연구)

  • Yun, Ki-Jo;Jang, Kyung-Nam;Baek, Eun-Sun;Park, Bong-Rae;Park, Hee-Joog
    • Fire Science and Engineering
    • /
    • v.27 no.3
    • /
    • pp.30-37
    • /
    • 2013
  • The ultimate purpose of the present study is to secure a effective method for foam liquid discharge when the mixing ratio deviates from the permissible range due to a decrease in the bypass flow rate resulting from a decrease in the cross sectional area of the foam liquid piping ranging from the branching header of one foam proportioner to the branching headers of multiple branching foam fire-extinguishing systems in the region for fire extinguishing and then to the standpipe at the lower part of the storage tank when a fire occurred in a combustible tank. To this end, the cause of mixing ratio variations following changes in the flow rates of existing foam fire extinguishing systems was analyzed, methods for compensation for constant mixing ratios were investigated, and it was proved that metering orifice replacements that could expand the cross sectional area of the stock solution inhaling piping was the most effective way for the improvement of form fire extinguishing systems' mixing ratios through foam proportioner venturi, foam chamber orifice, and metering orifice replacement experiments.

[Retracted]Improving Performance of Foam Proportioner Utilizing Metering Venturi Type ([논문철회]미터링 벤츄리를 이용한 포소화약제 혼합장치의 성능개선)

  • Joo, Seung-Ho;Kong, Ha-Sung;Gong, Ye-Som
    • Fire Science and Engineering
    • /
    • v.29 no.3
    • /
    • pp.48-52
    • /
    • 2015
  • In this study, we have evaluated whether the mixing ratio is proper by creating a mixing device for foam proportioner that mainly is employed in practice utilizing a metering venturi type. In case of the mixing ratio for 3%, water under pressure of 76 mm in diameter and the original liquid of a foam fire extinguishing agent of 31.75 mm in diameter have showed up the fluctuation rate just as much as 3.1~3.5% of the mixing ratio. Because water under pressure of 101.6 mm in diameter and the original liquid of a foam fire extinguishing agent of 38.1 mm in diameter have showed up 3.3~3.7% of the fluctuation rate, water under pressure of 101.6 mm in diameter and the original liquid of a foam fire extinguishing agent of 38.1 mm in diameter have satisfied 3.0~3.9% of performance criterion. And also, in case of the 6% of mixture rate, water under pressure of 76.2 mm in diameter and the original liquid of a foam fire extinguishing agent of 31.75 mm in diameter have showed up the fluctuation rate just as much as 6.4~6.8% of the mixing ratio. Because water under pressure of 101.6 mm in diameter and the original liquid of a foam fire extinguishing agent of 38.1 mm in diameter have showed up 6.0~6.8% of the fluctuation rate, water under pressure of 101.6 mm in diameter and the original liquid of a foam fire extinguishing agent of 38.1 mm in diameter have satisfied 6.0~7.0% of performance criterion.

An Experimental Study on a Discharge Pressure, Flow Rate and Foam Discharge Concentration through the Nozzle According to the Foam Suction Nipple Diameter (노즐 구경에 따른 포 수용액의 압력과 유량 및 농도 변화에 관한 실험적 연구)

  • Jang, Kyung-Nam;Lee, Maing-Ro;Park, Bong-Rae;Yun, Ki-Jo;Baek, Eun-Sun
    • Fire Science and Engineering
    • /
    • v.29 no.2
    • /
    • pp.84-91
    • /
    • 2015
  • The purpose of this study is to suggest the reasonable model of the caliber in suction nozzle, the pressure of suction nozzle, and the flow rate about foam system of line proportioner type using in the pumpcar. To test this, the experimental study was accomplished on the ground of the standards for the Performance Certification and Product Inspection of Foam Fire-extinguishing Chemical Mixing Machine. Aqueous Film Forming Foam in 3% and pipe type air foam nozzle with line proportioner FE 40 type were used. Test result showed that the pressure of suction nozzle within the limits between 0.25 MPa and 0.35 MPa was appropriate when the caliber in suction nozzle is 4 mm. Also, the pressure of suction nozzle within the limits between 0.45 MPa and 0.60 MPa was appropriate in the higher pressure than 4 mm when the caliber in suction nozzle is 5 mm.