• Title/Summary/Keyword: Fire water

Search Result 1,096, Processing Time 0.028 seconds

Numerical analysis on the rapid fire suppression using a water mist nozzle in a fire compartment with a door opening

  • Lee, Jaiho
    • Nuclear Engineering and Technology
    • /
    • v.51 no.2
    • /
    • pp.410-423
    • /
    • 2019
  • Fire suppression using a water mist nozzle directly above an n-Heptane pool in a fire compartment with a door opening was numerically investigated using the Fire Dynamics Simulator (FDS) for the purpose of application in nuclear power plants. Input parameters for the numerical simulation were determined by experimental measurements. Water mist was activated 10 s after the fire began. The sensitivity analysis was conducted for three input parameters: total number of cubic cells of 6032-2,926,400, droplets per second of 1000-500,000, and extinguishing coefficient of 0-100. In a new simple calibration method of this study, the extinguishing coefficient yielding the fire suppression time closest to that measured by experiments was found for use as the FDS simulation input value. When the water mist jet flow made contact with the developed fire, the heat release rate instantaneously increased, and then rapidly decreased. This phenomenon occurred with a displacement of the flame near the liquid fuel pool. Changing the configuration of the door opening with different aspect ratios and opening ratios had impact on the maximum value of the heat release rate due to the flame displacement.

Extinguishment of Liquid Fuel Fire by Water Mist Containing Additives

  • Park, Jae-Man;Won, Jung-Il;Shin, Chang-Sub
    • International Journal of Safety
    • /
    • v.4 no.2
    • /
    • pp.24-29
    • /
    • 2005
  • An experimental study was presented for extinguishing characteristics of liquid fuel fire by water mist($Dv_{0.99}{\leq}200{\mu}m$) containing potassium acetate and sodium acetate trihydrate. To evaluate the extinguishing performance of water mist containing additives, the evaporation characteristics of a water droplet on a heated surface was examined. The evaporation process was recorded by a charge-coupled-device camera. Also, small-scale extinguishing tests were conducted for n-heptane pool fire in ventilated space. During the experiments, flame temperatures were measured, and concentrations of oxygen and carbon monoxide were analyzed by a combustion gas analyzer. The average evaporation rate of water droplet containing additives was lower than that of pure water at a given surface temperature and decreased with the concentration increase due to the precipitation of salt in the liquid-film and change of surface tension. In case of using additives, the fire extinguishing times was shorter than that of pure water at a given discharge pressure and it was because the momentum of a water droplet containing additives was increased. And also dissociated metal atoms, potassium or sodium, were reacted as a scavenger of the major radical species OH, H which were generated for combustion process. Moreover, at a high pressure of 4 MPa, the fire was extinguished through blowing effect as well as primary extinguishing mechanisms.

A Study on the Risk of Electric Shock from the Sprayed Water for Fire Suppression of the PV Installed Building (태양광 발전설비가 설치된 건물의 진화 시 주수에 의한 감전의 위험성에 관한 연구)

  • Kim, Jinsun;Kwon, Seong-Pil
    • Fire Science and Engineering
    • /
    • v.28 no.6
    • /
    • pp.47-51
    • /
    • 2014
  • In this study we investigated the risk of electric shock and the possibility of current flow from the sprayed water when fire took place in a photovoltaic (PV) installed building. The sprayed water was analysed by using a mathematical model, a water spray system for water conductivity was made. With changing the initial water flow rate the water resistance was measured, and compared with the numerically expected value. As the experimental and numerical computing result, we were able to define the requirements that must be considered in the fire of PV systems.

EVALUATION OF AN ACCIDENT MANAGEMENT STRATEGY OF EMERGENCY WATER INJECTION USING FIRE ENGINES IN A TYPICAL PRESSURIZED WATER REACTOR

  • PARK, SOO-YONG;AHN, KWANG-IL
    • Nuclear Engineering and Technology
    • /
    • v.47 no.6
    • /
    • pp.719-728
    • /
    • 2015
  • Following the Fukushima accident, a special safety inspection was conducted in Korea. The inspection results show that Korean nuclear power plants have no imminent risk for expected maximum potential earthquake or coastal flooding. However long- and short-term safety improvements do need to be implemented. One of the measures to increase the mitigation capability during a prolonged station blackout (SBO) accident is installing injection flow paths to provide emergency cooling water of external sources using fire engines to the steam generators or reactor cooling systems. This paper illustrates an evaluation of the effectiveness of external cooling water injection strategies using fire trucks during a potential extended SBO accident in a 1,000 MWe pressurized water reactor. With regard to the effectiveness of external cooling water injection strategies using fire engines, the strategies are judged to be very feasible for a long-term SBO, but are not likely to be effective for a short-term SBO.

The Study on Characteristics of Water Spray and Droplet from Fire Sprinkler Head (소화용 스프링클러 헤드의 살수분포 및 수적 특성에 대한 연구)

  • 추병길;최종욱;차경세
    • Journal of the Korean Society of Safety
    • /
    • v.16 no.2
    • /
    • pp.13-21
    • /
    • 2001
  • The effect of water spray for the fire sprinkler depends on droples distribution over maximum possible floor area. The present study are carried out for the characteristics of water spray and droplets experimentally and numerically km two fire sprinkler heads which are CHM head and CHl heal CHl head is self-production and CHl head is widely used up to date. As the result of using CHM head, water spray and droplets are distributed over large area because CHM head has smooth surface and non-flamed shape. When the pressure of fire sprinkler head is low, SMD(sauter mean diameter) is large and when the pressure of fire sprinkler head is high, SMD is small.

  • PDF

A Study on the performance test of Water mist system as a fire extinguish system for Ships (선박용 미분무수 소화설비의 성능평가연구)

  • Kim, Sung-Yoon;Ahn, Bung-Ho;Kim, Dong-Seuk;Kim, You-Taek
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.155-156
    • /
    • 2006
  • Developed and conducted a performance test of the Water mist system that is satisfied with the requirement of a fire test requiring Class 3 Engine Mock-up exceeding net volume $3,000m^3$ as per IMO's MSC/Circ. 668 Appendix B(Test method for fire testing equivalent water-based fire-extinguishing systems for machinery spaces of category A and cargo pump rooms).Even though fuel atomizing was continued for 15 sec. after stopping of the system according to the test method relating to the atomizing fire type, no fire was reignited. This result shows the excellence of the system. There was no damage to the contents of the system after the test.

  • PDF

Application of reinforcement learning to fire suppression system of an autonomous ship in irregular waves

  • Lee, Eun-Joo;Ruy, Won-Sun;Seo, Jeonghwa
    • International Journal of Naval Architecture and Ocean Engineering
    • /
    • v.12 no.1
    • /
    • pp.910-917
    • /
    • 2020
  • In fire suppression, continuous delivery of water or foam to the fire source is essential. The present study concerns fire suppression in a ship under sea condition, by introducing reinforcement learning technique to aiming of fire extinguishing nozzle, which works in a ship compartment with six degrees of freedom movement by irregular waves. The physical modeling of the water jet and compartment motion was provided using Unity 3D engine. In the reinforcement learning, the change of the nozzle angle during the scenario was set as the action, while the reward is proportional to the ratio of the water particle delivered to the fire source area. The optimal control of nozzle aiming for continuous delivery of water jet could be derived. Various algorithms of reinforcement learning were tested to select the optimal one, the proximal policy optimization.

Estimation of FDS Prediction Performance on the Operation of Water-Mist (미세물분무 작동에 대한 FDS 예측 성능 평가)

  • Ko, Gwon Hyun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.15 no.8
    • /
    • pp.4809-4814
    • /
    • 2014
  • The aim of the present study was to estimate the prediction performance of a FDS (Fire Dynamic Simulator) to simulate the fire behaviors and suppression characteristics by operating a water-mist. Rosin-Rammler/log-normal distribution function was used to determine the initial droplet distribution of water-mist and the effects of its model constant were considered. In addition, the simulation models were validated by a comparison of the predicted fire suppression characteristics with water-mist injection pressures to the previous experiments, and the thermal flow behaviors and gaseous concentration variations were analyzed. The results showed that water-mists with the same mean diameter were affected by the characteristics of the droplet size distribution, which have different size and velocity distributions at the downstream location. The fire simulations conducted in this study determine the initial droplet size distribution tuned to the base of the spray characteristics measured by previous experiments. The simulation results showed good agreement with the previous measurements for temperature variations and fire suppression characteristics. In addition, it was confirmed that the FDS simulation with a water-mist operation supplies useful details on estimations of the thermal flow fields and gaseous concentration under water mist operation conditions.

Interpretation of the Five Viscera's Ascending Kidney-Water and Descending Heart-Yang

  • Bang, Jung-Kyun
    • The Journal of Korean Medicine
    • /
    • v.26 no.4
    • /
    • pp.162-167
    • /
    • 2005
  • According to the principle of ascending water and descending fire, water has the property of wetting downward, which is the opposite of fire, which has the property of blazing upward. Thus, they work differently according to their innate properties. Nature and the human body maintain harmony through the interaction of ascending water and descending fire. When applied to the human body, the heart and kidney are the center of this principle. In other words, the heart above is the fire and the kidney downward is water. When the heart-fire harmonizes downward, the kidney becomes warm, enabling genuine vital functions to be active. When the kidney yin moves upward, the heart receives the nourishing yin to harmonize nutrients and blood. Thereby, physiological functions become normal throughout the blood meridians. However, in the ascending kidneywater and descending heart-yang of the heart and the kidney, the liver and lung are the major functional organs. In other words, the liver through the dispersing and raising yang functions moves water, which is the vital essence of the kidney, upward. And the lung, through the astriction?clearing of the lung and descending Qi?dispersing functions, moves the heart-fire downward. These functions are deeply related with changing seasons; thus, these functions can be explained with the ascending kidney-water and descending heart-yang of the five viscera.

  • PDF