• Title/Summary/Keyword: Fire spread prevention

Search Result 96, Processing Time 0.027 seconds

The Real Scale Fire Tests for Vertical Fire Spread Study of External Finishing Material (외벽 마감재료의 수직화재 확산 연구를 위한 실물화재 실험)

  • Kweon, Oh-Sang;Yoo, Yong-Ho;Kim, Heung-Youl;Kim, Jung-Hyun;Min, Se-Hong
    • Fire Science and Engineering
    • /
    • v.26 no.6
    • /
    • pp.85-91
    • /
    • 2012
  • To reduce human life and property damage at the fire in a building, it is most critical to control flame spread in the early stage. Fire spread prevention measure generally includes fire resistance performance securing of structure member in the arson zone and use limitation based on combustion performance of finishing material. The latter is most fundamental fire safety design to determine flame spread, but domestic combustion test determines combustion performance by specimen sized fire test method. Thus, there are many restrictions in the determination of combustion performance by composite material such as sandwich panel. Especially, outer finishing material uses a variety of composite material such as dry bit, aluminum composite panel, and metal panel compared to inner finishing material. Therefore, this study would determine vertical fire spread features by a full scaled fire experiment through the test method of ISO 13785-2, an international test standard.

A Study on the Heat Release Characteristics of Fire Load for Performance Based Design of Multiplexes: A Focus on the Heat Release Rate and Fire Spread Rate of Cinema Seats (복합영상관의 성능위주설계를 위한 가연물의 연소발열특성 연구: 객석의자의 열발생률 및 연소확산속도를 중심으로)

  • Nam, Dong-Gun;Jang, Hyo-Yeon;Hwang, Cheol-Hong;Lim, Ohk-Kun
    • Fire Science and Engineering
    • /
    • v.34 no.1
    • /
    • pp.11-17
    • /
    • 2020
  • As performance-based design (PBD) has a direct impact on evacuation safety assessments, designing fire scenarios based on real fire tests is essential. To improve the reliability of the PBD for fire safety in multiplexes, information on fire behavior, such as heat release rate (HRR) and fire spread rate, are provided in this study by conducting a standard fabric flammability test. To this end, several chairs were arranged in a pattern that resembled a theater-style seating. The peak HRR and heating value per unit mass for each chair ranged from 415 kW to 988 kW and 15.2 MJ/kg to 23.8 MJ/kg, respectively. The heating values per unit mass of the new and old chairs were 23.6 MJ/kg and 16.7 MJ/kg, respectively. As the quantity of plastic and cushioning materials in the new chairs was more than that of the old ones, the new chairs were more vulnerable to fire hazards. Furthermore, when the chairs were arranged in a line, the fire spread rate was observed to be 0.39-0.42 m/min, regardless of the ignition location. Finally, a fire growth curve showing the peak HRR and fire spread rate was also demonstrated.

Experimental Study on the Flash Over Delay Effects according to the Prevention of Flame Spread between Composite Material Panels (복합자재의 패널 간 화염확산방지에 따른 플래시오버 지연 효과에 대한 실험적 연구)

  • Kim, Do-hyun;Cho, Nam-Wook
    • Fire Science and Engineering
    • /
    • v.31 no.2
    • /
    • pp.1-8
    • /
    • 2017
  • A sandwich panel is a composite material composed of a double-sided noncombustible material and insulation core which is used in the inner, outer walls, and roof structure of a building. Despite its excellent insulation performance, light weight and excellent constructability, a flame is brought into the inside of the panel through the joint between the panels, melting the core easily and causing casualties and property damage due to the rapid spread of flame. The current Building Law provides that the combustion performance of finishing materials for buildings should be determined using a fire test on a small amount of specimen and only a product that passes the stipulated performance standard should be used. This law also provides that in the case of finishing materials used for the outer walls of buildings, only materials that secured noncombustible or quasi-noncombustible performance should be used or flame spread prevention (FSP) should be installed. The purpose of this study was to confirm the difference between the dangers of horizontal and vertical fire spread by applying FSP, which is applied to finishing materials used for the outer walls of buildings limitedly to a sandwich panel building. Therefore, the combustion behavior and effects on the sandwich panel according to the application of FSP were measured through the construction to block the spread of flame between the panels using a full scale fire according to the test method specified in ISO 13784-1 and a metallic structure. The construction of FSP on the joint between the panels delayed the spread of flame inside the panels and the flash over time was also delayed, indicating that it could become an important factor for securing the fire safety of a building constructed using complex materials.

Biological Damage and Risk Assessment of The Wood Cultural Properties in Fire Prevention Area (화재방제구역에 따른 목조문화재 생물손상 및 생물위험도 평가)

  • Kim, Dae Woon;Chung, Yong Jae
    • Journal of the Korean Wood Science and Technology
    • /
    • v.43 no.1
    • /
    • pp.104-111
    • /
    • 2015
  • The three-year inspection of 20 tree stumps in the fire prevention area around the wooden building confirmed that termite colonies had been rapidly spread. In particular, four buildings among thirty one wooden buildings of Songgwang-sa temple were infected by the termite, indicating that the habitate of termite has been spread across the fire prevention area over the temple area. However, a non-destructive microwave diagnosis showed that internal damages have been progressed until now, suggesting a high risk to the building. These results suggest that the fire prevention area should be properly maintained to have harmful element controlled. Therefore, effective methods are required to eliminate tree stumps or wood materials used to establish fire prevention area near wooden buildings.

Developing of Slope Calculation Algorithm for Forest Fire Spread Modeling (산불확산모델링에 적합한 경사계산 알고리즘 개발)

  • An, Sang-Hyun;Kang, Yong-Seok;Son, Young-Gi;Lee, Si-Young;Shin, Young-Chul
    • Journal of the Korean Association of Geographic Information Studies
    • /
    • v.10 no.2
    • /
    • pp.122-128
    • /
    • 2007
  • GIS is used much research for efficient forest fire management and forecasting and slope has been known as high-leverage thing in spread of forest fire specially. Various algorithms are used usually to calculate slope angle of topography from DEM(Digital elevation model). However, because spread speed of forest fire is different according to uphill slope and downhill slope, it need new slope calculation algorithm. Therefore, developed slope calculation algorithm can reflect uphill slope and forest fire spread speed of looking downhill slope.

  • PDF

Effect of External Thermal Insulation Composite System with a Non-combustible Calcium Silicate Based Mineral on The Mitigation for Reducing Fast Spread of Flame (불연성 무기 단열재를 화재확산 방지구조로 적용한 외단열 마감시스템의 화재성능)

  • Lee, Jong-Chan;Park, Jong-Chul;Song, Hun
    • Journal of the Korea Institute of Building Construction
    • /
    • v.16 no.5
    • /
    • pp.397-403
    • /
    • 2016
  • As a building energy saving standard strengthened, The number of building installed external thermal insulation composite system(ETICS) using EPS insulation increased. But frequent fire accident in the buildings installed EIFS using EPS led to strengthening of building fire safety regulation. This study is for fire property of EPS ETICS reinforced with noncombustible calcium silicate-based mineral insulation as a fire spread prevention structure(FSPS). Fire test for large scale wall by ISO 13785-2 was applied and results showed EPS EIFS with FSPS got 3~8 times superior fire safety than normal EIFS by visual investigation. Temperature and heat flux measurement results, which data of upside of specimen were lower than downside, also supported fire safety of EIFS with FSPS.

Assessment of Grid Sensitivity in the FDS Field Model to Simulate the Flame Propagation of an Electric Cable Fire (케이블 화재의 화염전파 해석을 위한 FDS 모델의 격자민감도 평가)

  • Kim, Sung-Chan;Lee, Seong-Hyuk
    • Journal of the Korean Society of Safety
    • /
    • v.23 no.4
    • /
    • pp.30-35
    • /
    • 2008
  • The present study has been conducted to examine the effect of grid resolution on the predicted results for electric cable fire using pyrolysis model in FDS(Fire Dynamics Simulator, version 5). The grid independent test for different grid resolutions has been performed for a PE coating cable and the grid resolution is defined by the non-dimensional characteristic length of fire and mean grid size. The calculated maximum heat release rate and mean flame spread rate were almost constant for higher grid resolution of 20${\sim}$25 and the computing time for the grid resolution takes approximately 20hours to solve flame propagation with pyrolysis model. The geometrical simplification of a electric cable dose not greatly affect on the maximum heat release rate and flame spread rate and the rectangular approximation of cable shape gives acceptable result comparing with the round cable with stepwise grid.

Mechanism analysis through Water fire case (정수기 화재발생 사례를 통한 재현실험)

  • Lee, Jeong-Il
    • Proceedings of the Safety Management and Science Conference
    • /
    • 2011.11a
    • /
    • pp.593-618
    • /
    • 2011
  • Development of the economy and the growing income of people interested in the leisure and health has been focused. Past the town common wells and groundwater around the water, but health is a priority these days to solve the drinking water directly from tap water, but most people work from home, through the water purifier has been resolved. Depending on seasonal changes and personal taste of coffee, if you can enjoy a snack and water purifier is a restaurant, lounge, public areas and focusing on the rapid spread of the fire, water purifier as compared to the total number of fires increased by 0.03% per year trend on, but the washrooms fire and fire-related research data and case studies with analysis of the exact cause lack of proper preventive measures are insufficient reality. In this study, focusing on electrical energy using a water cooler to understand the structure and principles of fire, the fire revealed the mechanism is vulnerable to the consideration of factors, the exact cause of the fire investigation and the Assistant, manufacturing defects, and to contribute to fire prevention review should.

  • PDF

A Comparative Analysis on the building Fire Protection Standards of Korea and Japan (한·일 건축물 방화구획 기준 비교분석)

  • Shin, Yeoung-Deok;Han, Ji-Woo;Lee, Byeong-Heun;Kwon, Young-Jin
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2019.05a
    • /
    • pp.4-5
    • /
    • 2019
  • Smoke and fire spread throughout the building as a result of problems in the fire prevention section of Uijeongbu Apartment Fire in 2015 and Jecheon Sports Center Fire in 2017 in Korea, causing a number of casualties. It is believed that the fire compartment standards need to be reviewed as the fire in recent buildings continues to show problems. In this study, a comparative analysis was conducted on the fire prevention zone standard with Japan to improve the fire compartmente standard in Korea.

  • PDF

A Study on the Use of Balcony Areas to Improve Fire Escape for Residents in Apartments (화재피난 방안 수립을 위한 공동주택 거주자의 발코니 사용실태 조사)

  • Lee, So-Young;Lee, Myung-Sik
    • Korean Journal of Human Ecology
    • /
    • v.17 no.3
    • /
    • pp.541-552
    • /
    • 2008
  • With the increase of apartments and expansion of balcony areas, fire safety issues are becoming more important. Many researchers have conducted a lot of researches to reduce vertical flame spread in the balcony when an apartment unit is in fire. However, there have rarely been studies to use balcony area as a space for fire escape and evacuation. The study aims to examine the conditions of balcony use in apartments in order to find out prevention elements from fire escape and evacuation, and to investigate residents' satisfaction with balcony. For this study, questionnaires were collected from apartment residents and workers of architectural planning and construction companies. The findings show as follows: first, the balcony is generally used as a storage in each apartment unit nowadays. Second, when fire breaks out, many storage items could disturb residents' safe escape by blocking escape route, and easily promote to spread flame vertically in the balcony.