• Title/Summary/Keyword: Fire extinguishing

Search Result 393, Processing Time 0.032 seconds

A Study on the Direct Discharge Test for Verifying Design Concentration and Soaking Time for CO2 Fire Extinguishing System of Total Flooding (전역방출방식 CO2 소화설비의 설계농도 및 유지시간 검증을 위한 직접방사실험에 관한 연구)

  • Lee, Se-Myeoung;Moon, Sung-Woong;Ryu, Sang-Hoon
    • Fire Science and Engineering
    • /
    • v.26 no.6
    • /
    • pp.15-23
    • /
    • 2012
  • Indirect Test Method is often used instead of direct test method in test method for extinguishing performance of $CO_2$ extinguishing facility because of high cost, environment problems and difficulties of procedure. But in the danger facilities for a unit of nation, such as a petrochemical plant, a nuclear power plant, or etc. is better to verify the performance of the extinguishment through direct discharge test. In $CO_2$ extinguishing system for total flooding system installed in dangerous facilities in Korea, each protected area in surface fire and deep-seated fire had selected and verified of extinguishing performance of $CO_2$ extinguishing facilities. To get recognized as extinguishing performance, discharged $CO_2$ concentration to protected area should be equivalence with design concentration standards (NFSC and NFPA). The Design Concentration means that $CO_2$ extinguishing agent is considerate of concentration for percentage of allowance (20 %) from extinguishing concentration which available to control of flame. As test result, surface fire and deep seated fire in protected area is obtained $CO_2$ design concentration and maintained design concentration more than 20 minutes as deep-seated fire. Through this study, we introduced direct discharging test method and decision method. And furthermore, especially in the dangerous facilities as a unit of Nation, we suggested necessity about reliability of extinguishing facilities to use direct test method.

Characteristics of Protein Foam Agent by Stabilizer on the Ship Fire Extinguishment (선박화재 적용 단백포 소화약제의 안정제에 따른 소화특성)

  • Lee, Eungwoo;Shin, Changsub
    • Journal of the Korean Society of Safety
    • /
    • v.30 no.4
    • /
    • pp.79-85
    • /
    • 2015
  • Onboard fire extinguishing system is important to protect cargo and human lives and every oil tanker has foam type fire extinguishing system. Because of environmental problem, agent which contains materials such as Perfluorinated compounds are regulated and the development of the environmental friendly agent is required. The protein foam has less environmental pollution problem and has an excellent fire extinguish performance to oil fire. In the research, bivalency metal salts were added as stabilizer to increase fire resistance and stability of the foam. Ferrous sulfate, Iron chloride and Nickel chloride were used and to adjust to vessel, sea water was applied. As a stabilizer increased, the expansion ratio was raised. However 25% drainage time was decreased over 2.0 wt.% which is knowable that the foam brokes easily. The amount of generated foam was measured to check fluidity of foam and it appeared that when $FeSO_4$ 1.2 wt.% was added, the amount of generated foam reached large and also the 25% drainage time was high. To evaluate the fire extinguishing performance for oil fire, the small scale oil fire test was executed. When $FeSO_4$ 1.2 wt.% was added, fire extinguishing time was in its shortest which informs fluidity of foam and stability are important factors on fire extinguishing efficiency.

Extinguishing Characteristics of Zeolite adsorbed Dry Chemical Powder (분말 소화약제가 흡착된 제올라이트의 소화 특성)

  • Shin, Changsub;Park, Hojun
    • Journal of the Korean Society of Safety
    • /
    • v.27 no.6
    • /
    • pp.59-63
    • /
    • 2012
  • The use of dry chemical powder has been increased as it can be stored for a long period and sustain in stable condition compared to gas or liquid phase extinguishing agents. A new type of dry chemical powder using Zeolite was produced in the research. Chemical powder was adsorbed into Zeolite 13X, a porous material appearing negative catalytic effect, to create extinguishing powder obtaining core shell structure and measured physical properties and run a small scale fire extinguishment. SEM, XRD, TA analysis was also executed, and extinguishing characteristics were measured by fire extinguishing experiment on oil pool fire. The experiment showed that the average particle size of Zeolite 13X was equivalent, indicating about $3{\pm}1{\mu}m$ and thermal analysis result illustrated that Zeolite 13X showed exothermic reaction peaks at $900^{\circ}C$ due to solid-state transformation. Extinguishing characteristics on oil fire of $NaHCO_3$/Zeolite 13X and $NH_4H_2PO_4$/Zeolite were improved, influenced by adsorbed extinguishing powders on Zeolite 13X and Zeolite 13X that contains high phase transition temperature.

A Study on Estimating of Additional Gas for the Unencloseable Openings of The Gaseous Extinguishing Systems (가스계 소화설비의 개구부 보충량 추정에 대한 연구)

  • Jeong, Keesin
    • Fire Science and Engineering
    • /
    • v.26 no.6
    • /
    • pp.1-6
    • /
    • 2012
  • There are specific indications about additional gas for the unencloseable openings of the carbon dioxide extinguishing systems. But there are no indications for other gas extinguishing systems including clean agent extinguishing systems only have the principle when it need, apply it. Therefore, this study suggested applying the equation of additional gas for the unencloseable openings of the carbon dioxide to all of the other fire suppression gas that we are use.

A Study on the Design Program Development of the Carbon Dioxide Fire Extinguishing System Using an Optimization (최적화 기법을 이용한 이산화탄소 소화설비의 설계프로그램 개발에 관한 연구)

  • Lee, Dong-Myung
    • Fire Science and Engineering
    • /
    • v.28 no.3
    • /
    • pp.1-9
    • /
    • 2014
  • In this study, it was developed to the design program optimization the design factors of the carbon dioxide fire extinguishing system on the basis of design theory for the carbon dioxide fire extinguishing system, national emergency management agency (NEMA) notice No. 2012-11, KS B 6261 and steepest descent method of optimization. The design program was developed to C++ compiler based on established the logic and algorithms and was to operate on the Windows operating system. The optimization of design factors for the carbon dioxide fire extinguishing system are minimized subject to constraint on agent flow rate, emission time and design variables (pipe size etc.). It was verified to the design program performance for test system, and it was provided to the foundation for optimal design in fire fighting field. Also, it is considered to improve the efficiency of the fire extinguishing system and to maximize of fire suppression as the construction of the carbon dioxide extinguishing system based on the optimal design factors.

A Development of Methodology for NOVEC Gas Fire Extinguishing System (NOVEC 가스 소화 설비 설계방법론 개발)

  • Yun, Jeong-In;Choi, Jae-Hyuk
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.39 no.3
    • /
    • pp.206-210
    • /
    • 2015
  • The most important thing for NOVEC gas fire extinguishing equipment is to release NOVEC gas, which contained in the extinguishing container, to the safety section by the time appointed. For this matter, it is significant to decide arrangement and size of the proper piping equipment. This study has developed the design methodology of NOVEC gas fire extinguishing equipment in use of pipe network analysis techniques. Based on the design methodology, each design coefficient is chosen. It is found that the calculated result, which is 6.498 seconds, has been counted within the 10 seconds limit, which is fairly satisfied with extinguishing releasing time based on the developed methodology. At that time, the pressure loss is 21.09bar.

Effectiveness of Friction Loss Calculation Used for Water Mist Fire Extinguishing System on Marine Vessels

  • Lee Kyung-Woo;Kim You-Taek;Lee Young-Ho;Kim Mann-Eung
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.29 no.1
    • /
    • pp.86-97
    • /
    • 2005
  • Nowadays, Water Mist Fire Extinguishing System is increasingly used in maritime field for various application. The fire extinguishing capability of the system should be verified by hydraulic calculation in the same manner as the conventional water based fire extinguishing system such as sprinkler system. water spray system and etc. Additionally, the review of effectiveness of friction loss calculation method used for hydraulic calculation is needed because the pipe flow characteristic of its piping system has higher Reynolds number than that of the conventional system. In this paper the review work was carried out based on the NFPA Code 750.

Analysis of Performance and Development of Environment-friendly High Expansion Foam Concentrate (친환경 고발포 소화약제 개발 및 성능 분석 연구)

  • Kim, Ha-Young;Nam, Jun-Seok;Rie, Dong-Ho
    • Journal of the Korean Society of Safety
    • /
    • v.25 no.4
    • /
    • pp.25-29
    • /
    • 2010
  • Foam concentrate is used for fire-extinguishing purposes, occurring foam, mixed with air. In huge oil-fire or the efficiency of fire-extinguishing with small quantity of water, Foam concentrate is used widely. However, perfluorooc tanoicsulfonate and nonylpenol that are included in Foam concentrate could be exposure in danger while they were discharged. The purpose of the research is the development of environment-friendly high expansion foam that exclude the dangerous substances and improvement of danger of the existing foam concentrate. The developed foam is analyzed as the environment-friendly foam in indexes of the environment-toxicity, the biodegradation appraisal, and the dangerous substances-detecting. In addition, the performances of expansion rate, discharge rate, and fire-extinguishing are suitable in the domestic regulation, so it is useful for fire-extinguishing in real fire situation.

A Study on B Class Fire Extinguishing Performance of Air Ratio in the Compressed Air Foam System (압축공기포 소화설비의 공기포비에 따른 B급 소화성능 연구)

  • Lee, Jang-Won;Lim, Woo-Sub;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.27 no.6
    • /
    • pp.8-14
    • /
    • 2013
  • This research is to evaluate the fire extinguishing performance at a mixing ratio of pressurized air in the fire extinguishing system of compressed air foam (CAF) which injects compressed air into foam liquid and then discharging. The experimental device is made use of exclusive foam extinguishing facility for compressed air foam that is produces based on Canada National Laboratory and UL 162 standard, apply model of oil fire (B Class) 20 unit in accordance with "Standard of Model Approval and Product Inspection for Fire Extinguishing Agent" to the fire Extinguishing model. Compressed air is injected through the air mixture and study the tendency depending on increasing air foam ratio 1 : 4, 1 : 7, 1 : 10. In addition, the comparison experiments between synthetic surfactants foam and AFFF carry out with it at the air foam ratio 1 : 4. As a result, in the condition of same discharging flow, fire extinguishing effect of AFFF is the fastest at the air foam ratio 1 : 7 and the slowest at 1 : 10. Moreover, the fire extinguishing effect of AFFF in the comparison expeiments between AFFF and synthetic surfactants foam is faster than the other.

Wetting Agent Performance Evaluation Using Scale Model (축소모형 실험을 통한 침윤소화약제 소화성능 평가)

  • Kim, Nam-Kyun;Lim, Kyung-Bum;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.28 no.2
    • /
    • pp.20-25
    • /
    • 2014
  • In this study, the extinguishing performance evaluation of wetting agent for wood crib was conducted by using a scale model equipment that we designed. To confirm the optimal conditions of the experiment, a test was changed amount of fire extinguishing water and the number of timber. As a result, the discrimination of the fire extinguishing performance was seen only when 20 pieces of wood and the extinguishing water of 100 mL were used. After evaluating the extinguishing performance of domestic and foreign wetting extinguishing agents under these conditions, a reignition was occurred in only when we used water. In addition, the discrimination of extinguishing performance was seen through the temperature distribution according to the time of watering. Based on the results of this experiment, this study is expected to be able to use as a basis on presenting a method of optimized performance evaluation of wetting extinguishing agent.