• 제목/요약/키워드: Fire engineering design

검색결과 978건 처리시간 0.022초

Methodology for investigating the behavior of reinforced concrete structures subjected to post earthquake fire

  • Behnam, Behrouz;Ronagh, Hamid R.;Baji, Hassan
    • Advances in concrete construction
    • /
    • 제1권1호
    • /
    • pp.29-44
    • /
    • 2013
  • Post earthquake fire (PEF) can lead to the collapse of buildings that are partially damaged in a prior ground-motion that occurred immediately before the fire. The majority of standards and codes for the design of structures against earthquake ignore the possibility of PEF and thus buildings designed with those codes could be too weak when subjected to a fire after an earthquake. An investigation based on sequential analysis inspired by FEMA356 is performed here on the Life-Safety performance level of structures designed to the ACI 318-08 code after they are subjected to two different earthquake levels with PGA of 0.35 g and 0.25 g. This is followed by a four-hour fire analysis of the weakened structure, from which the time it takes for the weakened structure to collapse is calculated. As a benchmark, the fire analysis is also performed for undamaged structure and before occurrence of earthquake. The results show that the vulnerability of structures increases dramatically when a previously damaged structure is exposed to PEF. The results also show the damaging effects of post earthquake fire are exacerbated when initiated from second and third floor. Whilst the investigation is for a certain class of structures (regular building, intermediate reinforced structure, 3 stories), the results confirm the need for the incorporation of post earthquake fire in the process of analysis and design and provides some quantitative measures on the level of associated effects.

대형서점 적재가연물의 초기 연소발열성상 (Heat Release Characteristics of Typical Live Fire Load in Large Bookstore)

  • 남동군
    • 한국화재소방학회논문지
    • /
    • 제25권2호
    • /
    • pp.88-94
    • /
    • 2011
  • 건축물 적재가연물의 연소성상 및 발열특성은 건물 내부의 화재전파속도와 화재규모 등을 크게 좌우하는 중요한 요인이다. 그러나 대형 서점의 적재가연물은 다른 건축용도에 비해 다량 적재되어 있기 때문에 화재시 건물 전체의 화재피해가 대형화할 가능성이 있지만 연소발열성상이 화재실험 등으로 파악되어 있지 않다. 따라서 본 연구는 대형서점의 적재가연물인 목재 서가 등을 재현한 시험체를 대상으로 연소실험을 실행하여 연소발열성상을 파악하였다. 또한 이 결과를 바탕으로 대형서점의 화재시 화재안전성을 검토하고 대형 서점의 화재안전설계에 필요한 적재가연물의 연소표면적당 최대열방출률과 화재성장률 등을 제시하였다.

성능위주소방설계의 법적문제 및 개선방안 (The Legal Problems and Improvement in the Performance Based Design of Fire-fighting)

  • 이종영;백옥선
    • 한국화재소방학회논문지
    • /
    • 제24권1호
    • /
    • pp.54-63
    • /
    • 2010
  • 2009년 1월 1일부터 개정 "소방시설공사업법"의 시행에 따라 일정한 건축물의 경우에는 반드시 성능 위주소방설계를 하여야 한다. 성능위주소방설계는 구조 면적 용도 수용인원 등 건축물의 특성을 반영하여 가장 효율적으로 소방안전을 달성하고자 하는 설계이다. 성능위주소방설계는 일반적인 소방대상물에 비해 규모나 구조에서 특성이 있는 건축물로서 "국가화재안전기준"으로 대표되는 사양위주설계로 화재안전을 담보할 수 없거나 획일적인 소방설계를 하는 것이 부적합한 건축물 등에 있어 의미가 있다. 그러나 소방관련 법령에서는 성능위주소방설계의 의무대상물과 설계자격만을 규정하고 있고, 성능위주소방설계제도를 시행하기 위한 그 밖의 구체적인 사항에 관한 규정을 두지 않고 있기 때문에 실제 시행상의 어려움이 발생하고 있다. 이 논문에서는 성능위주소방설계와 관련하여 현행법령을 분석함으로써 성능위주소방설계제도의 바람직한 시행을 위한 법제도적 개선방안을 제시한다.

COMPARISON OF DESIGN & PERFORMANCE OF SPRINKLER SYSTEM IN KOREA FIRE CODE AND NATIONAL FIRE CODE

  • Kim, Won-K
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 1997년도 International Symposium on Fire Science and Technology
    • /
    • pp.610-616
    • /
    • 1997
  • One of the notable changes in Korean Industry in 1990's was globalization. Many of Korea plants have been built In the foreign countries and many of foreign plants have been build in Korea. And it is believed that many foreign insurance companies will begin their business in Korea soon, as Korea will open their insurance market to them. While sprinkler system plays very important role in total fire protection system, Korean sprinkler system design has not been studied in depth. Thus, it is not easy to convince the performance of Korean sprinkler system and compare it to NFPA 13, Standard for the Installation of Sprinkler System. Design guideline from both system will be listed and compared in detail. Fire water demand from both system will be reviewed to evaluate its adequacy. Water spray density and actuation time will be estimated, too.

  • PDF

폭렬 현상을 고려한 RC 구조물의 PBD기반 구조내화설계 기술개발에 관한 연구(III) -일본의 내화안전성평가기법을 활용한 사례조사 연구- (A Study on the Structural Fire Resistance Performance Design of RC Structural according to the Explosive Spalling - A Case Study on the Evaluation Method of Structural Fire Resistance in Japan -)

  • 김세종;이재영;권영진
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 추계학술논문발표회 논문집
    • /
    • pp.310-315
    • /
    • 2008
  • The objective of design for a post flash-over fire is contain the fire and prevent structural collapse, as necessary to meet the performance requirements. In the post flash-over phase of a fire all of the combustible objects in the compartment are burning and the heat release rate is limited either by the fuel surface area or the available air supply. So for the PBD situations, the process of evaluation method for fire phenomena is very important. It is the aim of this study to investigate and analyze the evaluation method of structural fire resistance in Japan.

  • PDF

소방설비 내진설계에 관한 각국 기준 비교 연구 (Review of Code Provisions on Seismic Design of Fire Protection System)

  • 이현진;신이철;이재영;서동구;한병찬;김재환;권영진
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2008년도 춘계학술논문발표회 논문집
    • /
    • pp.238-241
    • /
    • 2008
  • In this paper, provisions related with the seismic design and equipments of fire protection system are being considered. The provisions from various international codes on seismic design fire protection system were reviewed. The codes, reviewed are, Japanese code, NFPA guideline and Korean code. It is noted that all the codes excepted to korean code consider earthquake effect to evaluate seismic forces and behaviors. But, korean provision are not covered in seismic response in all. A brief description on limitations in korean code is also presented.

  • PDF

옥내소화전설비의 방수압 측정 개선에 관한 연구 (A Study on Improvement of Discharge Pressure Measurement of Indoor Fire Hydrant System)

  • 민세홍;정상호
    • 한국화재소방학회논문지
    • /
    • 제26권3호
    • /
    • pp.67-72
    • /
    • 2012
  • 건축물 실내에서의 화재발생 시 초기 소화설비로 적용하고 있는 옥내소화전설비와 스프링클러설비는 초기화재 진압용으로 큰 역할을 담당하고 있다. 최근 건축물의 지붕형태는 차별화된 지역문화와 디자인이 접목된 다양한 형태의 건축물이 건립되고 있다. 차별화된 지붕형태, 즉 일부 건축물의 지붕형태가 경사(박공)형태로 계획 건립되고, 또한 공중정원을 활용한 조망계획을 하다 보니 옥내소화전설비의 방수압력을 측정하는데 있어 옥상공간은 제한적이고, 너무 협소하여 옥내소화전 소방호스를 전개(최대 5개)하여 방수압력 측정하는데 있어 문제점이 도출되고 있다. 이러한 문제점을 보완하여 옥내소화전설비의 효율적인 관리와 화재 시 초동조치가 가능하도록 개선방안을 연구하고자 한다.