• 제목/요약/키워드: Fire dynamic simulator

검색결과 50건 처리시간 0.03초

Study on Disaster Prevention in Case of Fire at Subway Platform with Platform Screen Door

  • Rie, Dong-Ho;Yoon, Sung-Wook;Ko, Jae-Woong;Lee, Keun-Oh
    • International Journal of Safety
    • /
    • 제4권2호
    • /
    • pp.36-42
    • /
    • 2005
  • A study on fire phenomena in a subway transit mass station has been carried out as a part of disaster prevention plan at the subway station. The ventilation facilities installed in both the platform and the trackway are designed to convert into a smoke exhaust system in emergency situation, creating an environment necessary for evacuation. 3 dimensional Numerical Simulations based on the CFD are carried out using a simulation tool, Fire Dynamic Simulator. Total of six different cases are made and performances are compared each other to find optimal vents operation to ensure safer environment for evacuation at the platform area considering the installation of platform screen door.

반밀폐된 ISO 9705 화재실에서 비정상 화재특성 예측을 위한 FDS의 성능평가 (Performance Evaluation of FDS for Predicting the Unsteady Fire Characteristics in a Semi-Closed ISO 9705 Room)

  • 문선여;황철홍
    • 한국화재소방학회논문지
    • /
    • 제26권3호
    • /
    • pp.21-28
    • /
    • 2012
  • 비정상(unsteady) 화재성장이 발생되는 반밀폐된 구획에서 환기부족화재의 열 및 화학적 특성에 관한 FDS(Fire Dynamics Simulator)의 예측성능 평가가 수행되었다. 이를 위해 실규모 ISO 9705 표준 화재실의 출입구 폭이 0.1 m로 축소되었으며, spray 노즐을 통해 Heptane 연료유량은 선형적으로 증가되었다. 수치계산에 대한 신뢰도 확보를 위하여 동일 조건에서 수행된 실험결과와의 상세한 비교가 이루어졌다. 적절한 격자계를 이용한 FDS의 결과는 구획 내부의 온도 및 열유속(heat flux)은 비교적 잘 예측하지만, 비정상 CO 및 $CO_2$ 생성특성은 적절히 예측하지 못함을 확인하였다. 이러한 결과는 최근 수행된 유사조건의 정상상태 환기부족 구획화재에 대한 FDS 예측결과와 상반된 것으로서, 반밀폐된 구획화재 모델링에서 FDS를 이용한 비정상 CO 생성특성 예측에 상당한 주위가 요구됨을 확인하였다.

철도차량 화재모델링에서의 재료별 연소특성 시험법 조사 (Test Methods for FDS modeling for passenger trains)

  • 이덕희;이철규;정우성
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2007년도 추계학술대회 논문집
    • /
    • pp.982-988
    • /
    • 2007
  • The input data for the interior material of the train is one of the key points for enhancing the accuracy of fire simulation. In this study, we investigated the Fire Test Methods for the Fire Dynamic Simulator modeling for railroad passenger trains. We should get the thermal inputs such as ignition temperature, conductivity, specific heat, vaporization heat, effective heat release. With the simple conduction model for cone-calorimeter test, they could get more than HRR. Kinds of methodology were introduced for better thermal data for real material.

  • PDF

FDS 분석을 통한 승객 및 선원 생존율 향상에 대한 연구 (A Study on the Improvement of Survival Rate of the Passengers and Crews according to FDS Analysis)

  • 김원욱;김종수;박외철
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제39권3호
    • /
    • pp.312-317
    • /
    • 2015
  • 선박은 충돌, 좌초 및 화재 등의 여러 가지 원인으로 승객 및 선원들이 긴급 피난을 해야 하는 경우가 많이 발생한다. 일반적으로 모든 피난에서 생존율을 높이기 위해서는 피난 시간의 단축이 아주 중요한 요소이나 선박의 복잡하고 좁은 구조적 특성은 신속한 피난에 장애 요소가 되고 있다. 특히, 선박은 그 구조상 동일한 규모의 화재 발생 시 타 화재에 비해 확산속도가 빨라 신속한 피난이 필요하다. 또한, 선박은 해상에서 운항하는 특성으로 좋지 않은 해상 상태에서는 승객 및 선원이 행동적 제약이 발생한다. 이 연구에서는 인명 안전 차원에서 선박 구조 변경이 승객 및 선원의 생존율 향상에 미치는 영향에 대해 이론적 접근 및 수치 시뮬레이션을 통해 분석하고자 한다. 분석 도구로는 3차원 화재분석 전용 프로그램인 FDS(Fire Dynamic Simulator)를 이용하였으며 화재 시 인명 안전에 영향을 가장 큰 영향을 미치는 온도 상승 및 가시거리 감소를 분석하였다. 그 결과 선박의 복도 폭 및 천장의 높이만 개선하여도 인명 안전에 상당한 도움이 되는 것으로 분석되었다.

New algorithm for simulating heat transfer in a complex CPFS (Cable Penetration Fire Stop)

  • Yun, Jong-Pil;Kwon, Seong-Pil;Cho, Jae-Kyu;Yoon, En-Sup
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 제어로봇시스템학회 2003년도 ICCAS
    • /
    • pp.1798-1803
    • /
    • 2003
  • In this work the dynamic heat transfer occurring in a cable penetration fire stop system built in the firewall of nuclear power plants is three-dimensionally investigated to develop a test-simulator that can be used to verify effectiveness of the sealants. The dynamic heat transfer can be described by a partial differential equation (PDE) and its initial and boundary conditions. For the shake of simplicity PDE is divided into two parts; one corresponding to the heat transfer in the axial direction and the other corresponding to the heat transfer on the vertical layers. Two numerical methods, SOR (Sequential Over-Relaxation) and FEM (Finite Element Method), are implemented to solve these equations respectively. The axial line is discretized, and SOR is applied. Similarly, all the layers are separated into finite elements, where the time and spatial functions are assumed to be of orthogonal collocation state at each element. The heat fluxes on the layers are calculated by FEM. It is shown that the penetration cable influences the temperature distribution of the fire stop system very significantly. The simulation results are shown in the three-dimensional graphics for the understanding of the transient temperature distribution in the fire stop system.

  • PDF

사각 둔각물체 주위의 반응유동장에 대한 수치적 연구 (Numerical Study on the Reacting Flow Field abound Rectangular Cross Section Bluff Body)

  • 이정란;이의주
    • 한국화재소방학회논문지
    • /
    • 제27권6호
    • /
    • pp.64-69
    • /
    • 2013
  • 본 연구에서는 엔진 나셀 화재를 모사하고 이전의 실험결과를 보충하기위해 이차원 둔각물체 주위의 반응유동장에 대하여 수치해석을 수행하였다. Direct numerical simulation (DNS) 기반의 fire dynamic simulator (FDS)를 이용하여 반응유동장의 특성을 조사하였고, 실험결과와의 비교를 통해 화학반응식을 결정하였다. 산화제는 공기를 사용하였고, 연료는 메탄을 사용하였다. 동축류와 대향류 분사 모두의 경우에 화염의 안정성이나 모양은 둔각물체 주위의 와 강도와 크기에 크게 영향을 받았다. 동축류 분사의 경우 계산에 통한 화염소화한계를 결정하였는데 연료유속이 커질수록 공기의 유속 또한 커지는 경향이 있었고, 그 속도들 또한 기존의 실험결과와 잘 일치함을 볼 수 있었다. 유동장 특성에 대한 화학반응의 효과를 고찰하기 위해 반응이 없는 경우를 계산하여 비교하였다. 모든 경우에 비반응 유동장에 비해 반응 유동장의 후류와는 크기도 감소하고 세기도 감소함을 볼 수 있었는데 이는 반응에 의한 후류의 온도증가가 유체의 밀도 및 모멘텀을 감소시켰기 때문으로 판단된다.

지하공간시설에서의 피난안전대책을 위한 시뮬레이션 해석 (Simulation analysis for evacuation safety countermeasure in underground facilities)

  • 김봉찬;김세종;김경구;이주희;권영진
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2011년도 춘계학술논문발표회 논문집
    • /
    • pp.100-105
    • /
    • 2011
  • 본 연구에서는 재실자의 밀도가 높은 지하상가는 공간의 특성상 화재가 발생할 경우 다량의 유독가스의 발생 및 연기의 이동경로와 인간의 피난경로 일치로 인하여 피난안전에 큰 위험성이 있다고 사료된다. 이에 지하철 역사와 연결되어 있는 지하상가를 선정 후, 일본 피난안전성평가수법과 FDS(Fire Dynamic Simulator) 및 SIMULEX를 이용하여 비교 분석을 하였으며, 그 결과, 화재발생 후 6분이 경과 시 위험한 것으로 판단되었다. 그에 대한 대책으로 자연 배연구를 설치하여 시뮬레이션 수행을 한 결과 가시도확보 및 각 출구에서의 온도가 하강하는 것을 확인할 수 있었다.

  • PDF

선박 구조 개선을 통한 승무원의 피난 효율 향상을 위한 연구 (A study on the efficiency advancement for evacuation of the crews by ship structural improvement)

  • 김원욱;이명호;김종수
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제38권3호
    • /
    • pp.342-348
    • /
    • 2014
  • 육상구조물의 대형화재는 특수한 소방장비와 그에 적합한 방법에 의해서 소방관에 의해서 진압된다. 하지만 해양구조물은 육상으로부터 어떠한 도움없이 승무원에 의해서 진압되고 이들은 선박의 구조적 특성과 선박의 충돌 및 화재와 같은 여러 가지 원인에 의하여 신속한 탈출이 어렵다. 일반적으로 화재에 의한 인명손상의 경우에는 연기에 의한 질식사가 대부분을 차지하므로 탈출 시간의 단축은 생존율을 향상에 아주 중요한 역할을 한다. 본 연구에서는 3차원 화재 분석 전용 프로그램인 FDS(Fire Dynamic Simulator)를 이용하여 화재 발생 시 승무원 생존율 분석을 위한 거주 공간내의 온도 및 연기유동에 의한 가시거리를 분석한다. 기존의 선박은 화재 경보 발령 시 방화문이 자동으로 폐쇄되도록 설계되어 있다. 이는 화재가 발생한 구역에 승무원이 없을 경우에는 화재의 확산 및 연기의 유동 지연에 아주 효과적이다. 그러나 대피시간이 지연될 경우에는 방화문 안쪽에 위치한 승무원들에게는 치명적일 수 있다. 이 논문에서는 화재로 인해 방화문이 폐쇄되어 승무원들이 이 방화문을 열고 탈출하는 경우와 연구에서 제안하는 차단막을 설치했을 경우의 화재 구역의 온도상승 및 연기유동 속도를 비교 분석한다.

승강장 스크린도어 설치에 따른 배연설비운영에 대한 연구 (A Study of Smoke Exhaust Facility Operation of Subway Platform with Installation of Platform Screen Door)

  • 이동호;고재웅;김하영
    • 한국안전학회지
    • /
    • 제21권1호
    • /
    • pp.35-40
    • /
    • 2006
  • A study on fire phenomena in a subway transit mass station has been carried out as a part of disaster prevention plan at the subway station. The ventilation facilities installed in both the platform and the trackway are designed to convert into a smoke exhaust system in emergency situation, creating such an environment as necessary for evacuation. 3 dimensional Numerical Simulations based on the CFD are carried out using a simulation tool, Fire Dynamic Simulator. Additionally, four different vent modes are made and performances are compared with the original design mode and each other to find better operation of vents at both the platform and the trackway in case of fire. From the result, an vent operational characteristics under the condition of installed PSD is clarified for the effective smoke and heat removal from the platform area compared with non installed PSD.

선박구조가 승무원 생존율에 미치는 영향에 대한 연구 (A Study on the Crew's Survival ratio according to ship's structure)

  • 김원욱
    • 한국항해항만학회지
    • /
    • 제34권6호
    • /
    • pp.423-427
    • /
    • 2010
  • 선박은 충돌로 인한 침수, 화재 등 여러가지 이유로 긴급피난을 감행해야하는 경우가 많다. 특히, 선박의 경우 그 구조의 특성상 좁고 미로같은 복잡한 형태로 구성되어 신속한 탈출이 어렵다. 화재에 의한 인명손상의 경우 연기에 의한 질식사가 대부분을 차지하므로 신속한 탈출은 생존율 향상에 중요한 역할을 한다. 이 연구에서는 선박화재시 연기거동과 가시거리 확보 등에 대해 화재 분석 전용프로그램인 FDS(Fire Dynamic Simulator)를 이용하여 검토한다. 승무원 피난의 경우는 인간행동특성을 고려한 Pathfinder로 검토하였다. 이러한 분석 프로그램을 이용하여 기존 선박구조에 대한 화재확산과 승무원 피난시간을 검토하고 이와 동시에 변경된 구조가 승무원 피난에 미치는 영향을 검토하고자 한다.