• Title/Summary/Keyword: Fire Safety Design

Search Result 676, Processing Time 0.027 seconds

Evaluation of the Prediction of B-RISK-FDS-Coupled Simulations for Multi-Combustible Fire Behavior in a Compartment (구획실 내 가연물들의 화재거동에 대한 B-RISK와 FDS 연계 화재 시뮬레이션 예측성능 평가)

  • Baek, Bitna;Oh, Chang Bo
    • Fire Science and Engineering
    • /
    • v.33 no.4
    • /
    • pp.50-58
    • /
    • 2019
  • The prediction performance of B-RISK was evaluated for the fire behaviors of combustibles in a compartment using Fire Dynamics Simulator (FDS). First of all, to predict the heat release rate (HRR) for two combustible sets, the HRR for one combustible set and the design fire curve were used as input values for B-RISK. Comparing results of B-RISK calculations with experimental data for two combustible sets, it was found that B-RISK results predicted insufficiently for fire growth rate of experimental data but there was good agreement for maximum HRR and total HRR with the experimental data. And the B-RISK results were used for input values of FDS to evaluate the fire behaviors of B-RISK results. Comparing results of FDS calculations with experimental data, the simulation results showed that the temperature and concentrations of O2, CO2 in the fire growth phase were different from the experimental data. However, when using the B-RISK result for percentile 70%, the simulation results sufficiently predicted the overall fire behaviors.

A Development of Methodology for NOVEC Gas Fire Extinguishing System (NOVEC 가스 소화 설비 설계방법론 개발)

  • Yun, Jeong-In;Choi, Jae-Hyuk
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.39 no.3
    • /
    • pp.206-210
    • /
    • 2015
  • The most important thing for NOVEC gas fire extinguishing equipment is to release NOVEC gas, which contained in the extinguishing container, to the safety section by the time appointed. For this matter, it is significant to decide arrangement and size of the proper piping equipment. This study has developed the design methodology of NOVEC gas fire extinguishing equipment in use of pipe network analysis techniques. Based on the design methodology, each design coefficient is chosen. It is found that the calculated result, which is 6.498 seconds, has been counted within the 10 seconds limit, which is fairly satisfied with extinguishing releasing time based on the developed methodology. At that time, the pressure loss is 21.09bar.

A new model for transient heat transfer model on external steel elements

  • Chica, J.A.;Morente, F.
    • Steel and Composite Structures
    • /
    • v.8 no.3
    • /
    • pp.201-216
    • /
    • 2008
  • The Eurocode system provides limited information regarding the structural fire design of external steel structures. Eurocode 1 provides thermal action for external member but only in steady-state conditions. On the other hand, Eurocode 3 provides a methodology to determine heat transfer to external steelwork, but there is no distinction in cross section shapes and, in addition, the calculated temperature distribution is assumed to be uniform in the cross section. This paper presents the results of a research carried out to develop a new transient heat transfer model for external steel elements to improve the current approach of the Eurocodes. This research was carried out as part of the project EXFIRE "Development of design rules for the fire behaviour of external steel structures", funded by the European Research Programme of the Research Fund for Coal and Steel (RFCS).

Comparative Study on the Estimation Method of Fire Load for Residential Combustibles (주거공간 가연물의 화재하중 산정방법의 비교연구)

  • Choi, Su-Young;Kim, Jung-Yong;Nam, Dong-Gun;Kim, Sung-Chan
    • Fire Science and Engineering
    • /
    • v.27 no.6
    • /
    • pp.38-43
    • /
    • 2013
  • As a preliminary study to evaluate the reliability of the calculation method of fire load for residential furniture combustibles, the present study estimates the fire load considering the volume data obtained by the 3D geometrical information of combustibles and material properties based on the literature survey and sample burning test. A kitchen sink cabinet, couch and workstation were investigated for estimating its fire load and real fire test have been performed to measure total energy released from the combustibles. Based on total energy measured from real fire test, the relative error of the estimated fire load due to literature survey and measured material properties showed 6~120% and less than 20%, respectively. It shows that the estimation error of fire load are greatly affected by its material properties as well as geometrical information of combustibles and the present study will be able to contribute to accurate estimation of fire load.

A Study on the Walking Speed of Crowd for Safety Evacuation Design of the Elderly (고령자의 피난안전설계를 위한 군집보행속도에 관한 연구)

  • Hong, Hae-Ri;Seo, Dong-Goo;Hasemi, Yuji;Kown, Young-Jin
    • Fire Science and Engineering
    • /
    • v.25 no.1
    • /
    • pp.19-26
    • /
    • 2011
  • Korea is rapidly becoming an aging society. As a basic research on increasing evacuation safety design at silver facilities, the study was conducted in consideration of different foot's pace according to the number of seniors and their locations in a crowding of ordinary people and seniors all together. When the seniors were located at the front, the pace reduced to 0.81m/s on average. With 10 seniors which covered 50% of the crowd, the pace decreased to 0.85m/s. It is true that Korea has no existing researches on evacuation behaviour, and functions mentioned in its evacuation safety design is lack of practicality. Therefore, it is certainly necessary to secure any data of the evacuation behavior through various studies on seniors' evacuation behaviors.

Experimental Study on Calculation of Critical Velocity in Accordance with Gradient of a Road Tunnel at Fire (도로터널 화재시 경사도에 따른 임계풍속산정에 관한 실험적 연구)

  • Kim, Jong-Yoon;Seo, Tae-Beom;Rie, Dong-Ho;Lim, Kyung-Bum;Yoo, Ji-Oh
    • Journal of the Korean Society of Safety
    • /
    • v.21 no.5 s.77
    • /
    • pp.1-5
    • /
    • 2006
  • This study provides a basic data necessary to design a facility of smoke management after calculating the critical velocity of the gradient scale model tunnel and reviewing its adequacy to establish an optimum disaster prevention system for a road tunnel at fire. The experiment is carried out by using Froude scaling to a scale model which is about 1/29 as big as the real tunnel, and its critical velocity calculation is calculated to the 0-2% gradient of the tunnel. The result shows that the higher the gradient is, the stronger the critical velocity, but that it doesn't affect the critical velocity so much when the gradient is less 2%. In addition, this result is studied in comparison with the results done by other researchers to review the adequacy of the critical velocity.

A Numerical Study of the Effect of Sprinkler Spray on the Flow Characteristics Induced by Fire (스프링클러 분무가 화재유동특성에 미치는 영향에 관한 수치해석 연구)

  • Kim, Sung-Chan
    • Fire Science and Engineering
    • /
    • v.26 no.5
    • /
    • pp.105-110
    • /
    • 2012
  • The present study investigates the effects of sprinkler spray on fire driven flow characteristics in a compartment based on numerical approach. The FDS (Fire Dynamics Simulator), a widely used fire field model, was used to simulate the fire induced flow and sprinkler spray and a series of grid independence tests have been performed to obtain the optimal grid size. In order to validate the result predicted by FDS model, the calculated results were compared with experimental results of Magnone et al.. The FDS model matches quite well to experiments in temperature profile and mass flux through doorway, however, the discrepancy between the FDS model and experiments increases with increasing water discharge rate. As with previous study, the FDS calculation also shows a decrease of mass flow rate of combustion products through doorway due to the sprinkler spray. This study can contribute to optimize the sprinkler system design and verify the validity of the fire field model with sprinkler spray.

Standard Proposed for Fire Safety Evaluation of Railway Tunnels and Evaluation of Fire Temperature (철도터널내 화재시 내화성능 평가를 위한 기준 제안 및 화재 온도 평가)

  • Won, Jong-Pil;Choi, Min-Jung;Lee, Su-Jin;Lee, Sang-Woo
    • Journal of the Korea institute for structural maintenance and inspection
    • /
    • v.14 no.3
    • /
    • pp.196-200
    • /
    • 2010
  • The number of railway tunnels has been increasing rapidly. Although fires in long railway tunnels are rare, the consequences can be devastating. Prior to this study, there were no adequate time-temperature curves for the fire safety assessment of Korean railway tunnels. We studied a standard foreign time-temperature curve for which the heat rate is based on the traffic and the types of vehicles. We then proposed a hydrocarbon curve as a fire design model for railway tunnels in Korea. We examined the implications of this proposed model on railway tunnel structures using numerical analysis.

A Study of the Improvement Plan and Real Condition Estimation of Fire Protection Safety Management for Power Plants in Korea (국내발전소 소방안전관리 운영실태조사 및 개선방안에 관한 연구)

  • Kang, Gil-Soo;Choi, Jae-wook
    • Fire Science and Engineering
    • /
    • v.31 no.2
    • /
    • pp.61-73
    • /
    • 2017
  • The Fukushima Nuclear Disaster in 2011 and California Power Failure in 2001 are examples of the importance of the power plant safety management that caused huge national loss with a power-related mass casualty incident. In a situation where humans cannot live without electricity, efforts to strengthen the systematic firefighting safety management in power plants that produce electricity with large amounts of hazardous materials as fuel, such as nuclear energy, coal and gas, are essential to protect life and prevent property loss and stable economic growth from fire explosion accident or radiation leak due to the negligence of safety management and natural disasters such as earthquakes, which has recently become an issue. This study examined the operating situation of firefighting safety management in power plants with firefighting officials employed by five power generation companies including Korea Southern Power Co., Ltd. and Korea Hydro & Nuclear Power Co. Ltd., which are in charge of the domestic power supply. As a result, for the systematic firefighting safety management of power plants, improvement plans were drawn, including the development of an effective business manual and a comprehensive management system, the substantiality of firefighting safety education, and the strengthening of seismic designs to prepare for earthquakes.

A Study on the Evacuation of People used the evacuation model on Fire in Shopping Mall (피난 모델을 이용한 대형할인매장의 화재시 피난에 관한 연구)

  • 이수경;이상준
    • Fire Science and Engineering
    • /
    • v.14 no.4
    • /
    • pp.17-22
    • /
    • 2000
  • For life safety design of shopping mall, we selected a shopping mall, and calculated the evacuation time of means of egress. It is calculated by two kind of evacuation method. One is the computer simulation model, EXODUS. The other is Japan's method. Study way is a model structure study, selecting real shopping mall and setting scenario, calculating the evacuating time. result of study, evaluation time is very high. Therefore we confirmed that the building of means of egress is not fit to evacuation more the capacity of setting population.

  • PDF