• Title/Summary/Keyword: Fin-tube heat exchange

Search Result 20, Processing Time 0.018 seconds

Heat transfer coefficients for single-Phase flow in a micro-fin tube (마이크로휜 관내의 단상유동 열전달계수)

  • 권정태;김무환
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.10 no.4
    • /
    • pp.423-430
    • /
    • 1998
  • Single phase heat transfer coefficients were measured for turbulent water flow in a micro-fin tube by using Wilson plot technique. An experiment for counterflow heat exchange between the micro-fin tube and its outer annulus passage was performed. The annulus side heat transfer resistance was varied and the overall heat transfer coefficients were measured. The single-phase heat transfer coefficients in a micro-fin tube were obtained by Wilson plot technique. Nusselt numbers based on the real heat transfer area and the nominal area were about 35% and 50% larger than those for smooth tube respectively Also, single-phase heat transfer correlations based on real heat transfer area and nominal area have been proposed for a micro-fin tube.

  • PDF

Performance Comparison of Fin-Tube Heat Exchanger and Aluminum Heat Exchanger (핀 튜브 열교환기와 알루미늄 열교환기의 성능 비교)

  • Chang, K.S.;Lee, H.S.;Kim, J.D.;Hong, S.R.
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.408-413
    • /
    • 2008
  • This study presents comparison of the air side heat transfer and friction characteristics in a heating condition between Louver fin-tube heat exchangers and aluminum heat exchangers. Experiments are performed for the Louver fin-tube heat exchangers and aluminum heat exchangers using a calorimeter, which is designed based on air-enthalpy method described in ASHRAE standards. The air velocities its are varied from 0.7 to 1.6 m/s with 0.3 m/s interval. A study result shows that the heat transfer performances of aluminum heat exchangers are $40{\sim}80%$ higher than those of Louver fin-tube heat exchangers per unit volume, mass and heat transfer area.

  • PDF

Performance Comparison of 7mm Fin-Tube Heat Exchangers for Various Design Conditions (설계 조건에 따른 7mm 직경 핀-관 열교환기의 성능비교)

  • Chang, Keun-Sun;Kim, Hyuk;Hong, Seok-Ryul;Kim, Young-Jae
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.633-638
    • /
    • 2006
  • This study presents the air side heat transfer and friction characteristics of fin-tube heat exchangers with various fin types. A total of 8 samples of heat exchangers are tested. Fin patterns tested are slit, louver and plate fins. Each fin type has three cases of number of tube rows(N=1, 2, 3) and two different fin pitches. The results are plotted in terms of Colburn j-factor and friction factor f with respect to Reynolds number in the range of 200 to 510.

  • PDF

An Experimental Study on the Heat Exchange Performance at Various EGR Cooler Types (EGR 쿨러 Type에 따른 열교환성능에 관한 실험적 연구)

  • Shon, Jungwook;Woo, Seungchul;Park, Jongwook;Chun, Taesoo;Lee, Kihyung
    • Transactions of the Korean Society of Automotive Engineers
    • /
    • v.23 no.6
    • /
    • pp.608-614
    • /
    • 2015
  • Nitrogen oxide(NOx) emission reductions are required to meet the strict emission regulations for environmental protection. Most of the Exhaust Gas Recirculation(EGR) system applied to a diesel engine can relatively decrease the NOx at a low cost, but it has a disadvantage in that the PM generation is promoted due to the hot intake air temperature. Thus, high heat exchange efficiency of the EGR cooler is required for an effective removal of NOx. In this study, heat exchange efficiency for various types of heat exchangers used in EGR cooler was measured under same conditions, and determined best heat exchange performance shape depending on type of heat exchanger.

Heat Transfer Characteristics of Heat Exchange Module for a Water Tube Type Modular Boiler (모듈형 수관식 보일러를 위한 열교환 모듈의 열전달 특성)

  • Ahn, Joon;Kim, Jong-Jin;Kang, Sae-Byul
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.24 no.3
    • /
    • pp.265-270
    • /
    • 2012
  • A finned tube type heat exchange module has been proposed for a multi-burner water tube boiler. Fin density and length increase in streamwise direction to equalize the evaporation for each module, which makes it difficult to apply conventional bulk design procedure. The design program has been improved by updating data for every row of tubes along the flow. A numerical simulation has been also conducted to evaluate the effect of inlet conditions and validated with experiment. The heat transfer of the first row has been underpredicted by the conventional Zhukauskas correlation, since the acceleration of the flow due to the blockage is not fully inflected. The fin tip temperature is also underpredicted by Bessel solution, because of the interaction with neighboring fins.

Performance Evaluation of Double-Tube Condenser using Smooth and Micro-Fin Tubes for Natural Mixture Refrigerant (Propane/Butane)

  • Lee, Sang-Mu;Lee, Joo-Dong;Koyama, Shigeru;Park, Byung-Duck
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.15 no.1
    • /
    • pp.25-33
    • /
    • 2007
  • The investigation has been made into the prediction of heat exchange performance of a counter flow type double-tube condenser for natural refrigerant mixtures composed of Propane/n-Butane or Propane/i-Butane in a smooth tube and micro-fin tube. Under various heat transfer conditions, mass flux, pressure drop and heat transfer coefficient of the mixed refrigerants were calculated using a prediction method, when the length of condensing tube, total heat transfer rate, mass flux and outlet temperature of coolant were maintained constant. Also, the predicted results were compared with those of HCFC22. The results showed that the mixed refrigerants of Propane/n-Butane or Propane/i-Butane could be substituted for HCFC22, while the pressure drop and overall heat transfer coefficient of the refrigerants were evaluated together.

Condensing Performance Evaluation in Smooth and Micro-Fin Tubes for Natural Mixture Refrigerant (Propane/Butane) (프로판/부탄 혼합자연냉매의 평활관과 마이크로핀관 내의 응축성능평가)

  • Lee Sang-Mu;Lee Joo-Dong;Park Byung-Duck
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.17 no.9
    • /
    • pp.816-823
    • /
    • 2005
  • This paper deals with the heat exchange performance prediction of a counter flow type double-tube condenser for natural refrigerant mixtures composed of Propane/n-Butane or Propane/i-Butane in a smooth tube and a micro-fin tube. The local characteristics of heat transfer, mass transfer and pressure drop are calculated using a prediction method developed by the authors. The total pressure drop and the overall heat transfer coefficient are also evaluated on various heat exchange conditions. The calculated results of the natural refrigerant mixtures are compared with HCFC22. In conclusion, natural refrigerant mixtures composed of Propane/n-Butane or Propane/i-Butane are appropriate candidates for alternative refrigerant from the viewpoint of heat transfer characteristics.

Performance and Heat transfer Characteristics of Louver Fin-tube Heat Exchanger for Simultaneous Cooling/Heating Heat Pump (동시 냉난방 히트펌프용 루버핀-관 열교환기 성능 및 전열특성 실험연구)

  • Kwon, Young-Chul
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.8 no.6
    • /
    • pp.1337-1342
    • /
    • 2007
  • An experimental study has been performed to investigate the performance and heat transfer characteristics of the heat exchanger for simultaneous cooling/heating heat pump. The heat transfer performance was measured using an air-enthalpy calorimeter and a constant temperature water bath, to obtain the performance evaluation and analysis of a fined tube heat exchanger. Six finned tube heat exchangers with louver fin were tested under a heating condition. Air-side heat transfer and friction were presented in terms of j-factor and f-factor. The heat transfer coefficient increased with decreasing the fin pitch, j-factor and f-factor on the fin pitch and the number of tube rows decreased with increasing Reair.

  • PDF

The Development of Catalytic Combustor With Heat Exchanger

  • Phil, Yu-Sang;Seok, Seo-Yong;Seop, Song-Kwang
    • Proceedings of the Korea Society for Energy Engineering kosee Conference
    • /
    • 2002.05a
    • /
    • pp.21-27
    • /
    • 2002
  • Catalytic combustor with heat exchangers are often employed in process technology where a compact design is required [1]. The use of fin and tube heat exchanger offers the enhanced surface area for heat exchange. The recent progress and performance of the fin-tube heat exchanger, especially airside, has been reviewed extensively by Wang[2].(Omitted)

  • PDF

Experimental Study of Heat Transfer Performance of Louver-Fin Heat Exchanger (Louver-Fin 열교환기의 열전달 특성 실험 연구)

  • Chang, K.S.;Kweon, Y.C.;Hong, S.R.;Kim, J.D.;Lee, H.S.;Park, B.K.
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.209-215
    • /
    • 2007
  • This study presents the air side heat transfer and friction characteristics of fin-tube heat exchangers. Variations of heat transfer performance in each row are investigated in the present work. Experiments were performed for the Louver fin-tube heat exchangers using air-enthalpy type calorimeter, which is based on air-enthalpy method described in ASHRAE standards. The air velocity was varied from 0.7 to 2.5 m/s with 0.3 m/s interval. The results are plotted in terms of Colburn j-factor and friction factor of with respect to Reynolds number in the range of 200 to 1100.

  • PDF