Advances In Air-Cooled Heat Exchanger Technology for Residential Air-Conditioning

  • Webb Ralph L.;Kim Nae-Hyun
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • 제13권4호
    • /
    • pp.184-195
    • /
    • 2005
  • This paper describes the recent work on advanced technology concepts applied to air cooled heat exchangers for residential air-conditioning. The concepts include vortex generators for the air-side, micro-fin or flat tubes for the refrigerant-side. Advances in understanding of heat transfer mechanisms, predictive models are discussed.

V형 원형휜-원형관의 강제대류 열유동 특성 (Forced Convection Characteristics of V shape Circular fin-tube Heat Exchanger)

  • 이종휘;임무기;강희찬
    • 설비공학논문집
    • /
    • 제21권12호
    • /
    • pp.649-655
    • /
    • 2009
  • The purpose of the present study is to investigate the flow resistances and heat transfer characteristics of V-shaped circular fin-tube heat exchangers. Four types of V-shaped fins in which the fin areas are identical but the areas of the V-shaped portion are different have been tested numerically. The results obtained for heat transfer, pressure drop, and fin temperature are discussed in this paper. With increase in the area of the V-shaped portion, the pressure drop and heat transfer increase up to 40% and 24%, respectively, in the present test range.

Numerical analysis of a plain-fin type heat exchanger with two tubes in a crevice-type heat pipe

  • Kim, Eun-Pil
    • Journal of Advanced Marine Engineering and Technology
    • /
    • 제40권8호
    • /
    • pp.686-691
    • /
    • 2016
  • This paper employs numerical tools to obtain an optimal thermal design of a heat exchanger with plain-fins. This heat exchanger is located at the condensing section of a crevice-type heat pipe. The plain-fins in the heat exchanger are radically mounted to two tubes in the condensing section. To obtain the optimal design parameters, a computational fluid dynamics technique is introduced and applied to different placement configurations in a system module. Owing to its effects on the heat pipe performance, the temperature difference between the tube surfaces and ambient air is investigated in detail. A greater heat dissipation rate occurs when the plain-fin offsets change from 2 to 3 mm. When this temperature difference is ${\Delta}T=70^{\circ}C$, the upper part of the plain-fins undergoes an accumulation of heat. At below $70^{\circ}C$, the dissipation of heat is accepted. A rectangular plain-fin geometry with varying widths and heights does not have a significant impact on the heat dissipation through-out the overall system. In addition, the temperature distributions between different plain-fin pitches show an equal profile even with different fin pitches.

핀튜브 열교환기용 전관확관 유닛 개발 (Development of Hybrid Expander Unit for Fin Tube Heat Exchanger)

  • 노건상;김종남
    • 한국기계기술학회지
    • /
    • 제13권4호
    • /
    • pp.165-168
    • /
    • 2011
  • In this paper, the hybrid tube expander unit for fin and tube type heat exchanger are developed by means of enlarging and inserting the smooth tube with a small diameter to a finned tube having larger diameter. In other word, the tube expander tool that is easy to attach and remove from tube is developed. The hybrid tube expander unit developed in this study can move easily and enlarge the tube without fixing at tube sheet. Also, this unit has a function removing scales inside tube by replacing a tube expander ball.

직교류 핀-튜브형 열교환기에서 팬 위치변화에 따른 열전달 성능변화 연구 (Numerical Study on Heat Transfer Performance of Crossflow Fin-tube Heat Exchanger Depending on Different Fan Positions)

  • 김원형;박태선
    • 대한기계학회논문집B
    • /
    • 제39권3호
    • /
    • pp.271-278
    • /
    • 2015
  • 직교류 핀-튜브 열교환기의 대류연절달에 대해 수치해석 연구가 수행되었다. 팬위치에 따른 열전달 성능변화를 조사하기 위하여 분사와 흡입형태로서 몇 가지 팬위치가 선택되었다. 열교환기의 튜브는 엇갈림 배열이며, 튜브의 온도와 유입공기의 온도는 각각 $50^{\circ}C$$30^{\circ}C$이다. 해석결과로부터 3차원 유동구조가 검토되었으며, 팬의 다양한 설치 위치에 따른 대류 열전달계수와 열교환기 입출구 사이의 평균 온도차에 대한 분석을 통해 열교환기 성능을 논의되었다.

열교환기 형태에 따른 이산화탄소용 가스쿨러와 증발기의 성능비교 (The Performance Comparison of $CO_2$ Gascooler and Evaporator with Heat Exchanger Type)

  • 배경진;조홍현
    • 한국지열·수열에너지학회논문집
    • /
    • 제6권2호
    • /
    • pp.15-22
    • /
    • 2010
  • The natural refrigerants have used into HVAC equipments because the CFCs and HFCs have some environmental problems like high ODP and GWP. The carbon dioxide has small effect on the environmental problem but also good thermodynamics properties. In this study, the simulation study on the performance and characteristics of a $CO_2$ gascooler and evaporator using a fin-tube and microchannel heat exchanger has been conducted. Besides, the comparison of performance with operating condition was carried out in order to apply to the $CO_2$ heat pump system. As a result, the front sizes of a gascooler and evaporator using a microchannel were decreased by 63% and 58%, respectively, compared to those using a fin-tube. The performance of the fin-tube gascooler and evaporator were more responsive to the variation of operating conditions compared to that of microchannel. The pressure drop of a fin-tube heat exchanger was higher than that of a microchannel one.

흡착식 냉동기의 흡착탑에서 열 및 물질전달에 관한 수치적 연구 (A Numerical Study for the Heat and Mass Transfer in Silica gel/Water Adsorption Chiller's Adsorber)

  • 권오경;윤재호;김종하;김용찬;주영주
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2005년도 동계학술발표대회 논문집
    • /
    • pp.341-346
    • /
    • 2005
  • Nowadays, adsorption chillers have been receiving considerable attentions as they are energy-saving and environmental1y benign systems. A Fin & tube type heat exchanger in which adsorption/desorption take place is required more compact size. The adsorption chiller is expected to have high energy-efficiency in utilizing the waste heat exhausted from a process. The objectives of this paper are to investigate the effect of fin pitch of fin & tube on the adsorption performance and to develop an optimal design fin & tube heat exchanger in the silica gel/water adsorption chiller. Previous study concluded that optimal particle size selected 0.5mm, type HO silica gel, and fundamental heat transfer & mass transfer experiments carried out. From the numerical results, the adsorption rate for the fin pitch 2.5mm is the highest than that for the fin pitch 5mm, 7.5mm and 10mm. Also cooling water & hot water temperature affect the adsorption rate.

  • PDF

착상 시 공기 유속이 슬릿 핀-관 열교환기 서리층 생성에 미치는 영향에 관한 연구 (Effect of air velocity on frost formation of slit fin-and-tube heat exchanger under frosting condition)

  • 신성홍;조금남;하야세 가쿠
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.252-257
    • /
    • 2007
  • The present study investigated the effect of air velocity on frost formation of slit fin-and-tube heat exchanger under frosting condition. The slit fin-and-tube heat exchanger with outer tube diameter 7.0mm and 1 row was used. Air side pressure drop, photographs of frost distribution, frost accumulation and frost thickness were presented with respect to the frosting time. In the early stage of experiment, the case with air velocity of 1.5m/s showed 403% higher for the air pressure drop than the case with the air velocity of 0.5m/s. As the frost was accumulated, the effect of air velocity on air pressure drop was decreased. In the end stage of test, air pressure drops of two cases were very close and air pressure drop for the air velocity of 0.5m/s was higher than that of 2.0m/s. It was also shown in the photographs of frost distribution, frost accumulation and frost thickness. From frost thickness, fanning friction factor was presented.

  • PDF

슬릿과 평판 핀-관 열교환기의 공기측 열전달 및 마찰특성 (Air-side Heat Transfer and Friction Characteristics of Finned Tube Beat Exchangers with Slit Fin or Plain Fin)

  • 권영철;장근선;박병권;권정태;정지환
    • 에너지공학
    • /
    • 제16권1호
    • /
    • pp.7-14
    • /
    • 2007
  • 본 연구는 핀-관 열교환기의 건표면과 습표면 조건에서의 공기측 열전달 및 마찰특성을 실험을 통해 이해하고자 수행하였다. 핀-관 열교환기의 성능평가 및 해석기술을 확보하기 위하여 공기엔탈피식 칼로리 미터를 이용하였다. 핀형상은 슬릿과 평판이며, 관경은 7.0mm로 2열과 3열 핀-관 열교환기 4종에 대해 실험하여, 건표면과 습표면의 공기측 열전달 및 마찰특성을 조사하였다. 습표면에서 습도변화(RH 50%, 70%)에 따른 습도영향도 조사하였다. 건표면 조건에서 Re 수가 증가할수록 j 계수는 감소하며, 2열이 3열보다 높았다. 마찰계수는 슬릿 핀이 평판 핀보다 높았다. 습표면 조건에서 슬릿 핀이 평판 핀보다 그리고 2열이 3열보다 우수한 열전달효과를 나타내었다. j 계수와 마찰계수는 습도변화, 열수, 핀 형상에 따라 달라짐을 확인하였다.

Corrugate 휜-관 현열 열교환기의 구조에 따른 공기측 열전달 및 압력손실 특성 (Characteristic of air-side sensible heat transfer and pressure drop on the corrugate fin tube heat exchangers)

  • 류준일;전창덕;이진호;남임우
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2007년도 동계학술발표대회 논문집
    • /
    • pp.216-221
    • /
    • 2007
  • An experiment was carried out to investigate the effect of a coolant circuit arrangement on the heat transfer and air pressure drop of a fin-tube sensible heat exchanger with the corrugated fin surface. The air inlet temperature was set to $23^{\circ}C$,the relative humidity to 50% and the air inlet flow rate to 20, 22, $25m^3/min$, respectively. while the coolant temperature was set to $7^{\circ}C$, and the coolant mass flow rate to 10, 16, 22kg/min, respectively. Experiment showed that the exchanger having a diameter of 12.7mm with parallel circuit does better performance in sensible heat transfer and air pressure drop than those three of diameter of 12.7mm with a series circuit and that with diameter of 15.88mm with a parallel circuit.

  • PDF