• Title/Summary/Keyword: Fault current limiting operation

Search Result 101, Processing Time 0.023 seconds

Analysis on Current Limiting Characteristics of Transformer Type SFCL with Additionally Coupled Circuit

  • Lim, Seung-Taek;Ko, Seok-Cheol;Lim, Sung-Hun
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.2
    • /
    • pp.533-539
    • /
    • 2018
  • In this paper, the transformer type superconducting fault current limiter (SFCL) with additionally coupled circuit was suggested and its peak fault current limiting characteristics due to the fault condition to affect the fault current were analyzed through the fault current limiting tests. The suggested transformer type SFCL is basically identical to the previous transformer type SFCL except for the additional coupled circuit. The additional coupled circuit, which consists of the magnetically coupled winding to the primary and the secondary windings together with another superconducting element and is connected in parallel with the secondary winding of the transformer type SFCL, is contributed to the peak fault current limiting operation for the larger transient fault current directly after the fault occurrence. To confirm the fault current limiting operation of the suggested SFCL, the fault current limiting tests of the suggested SFCL were performed and its effective peak fault current limiting characteristics were analyzed through the analysis on the electrical equivalent circuit.

Analysis on Current Limiting Characteristics of a Hybrid SFCL with the First Half Cycle Limiting Operation Due to Resistance of Superconducting Element (초전도소자의 저항변화에 따른 반주기내 한류형 하이브리드 초전도 전류제한기의 전류제한 특성 분석)

  • Kim, Jin-Seok;Lim, Sung-Hun;Kim, Jae-Chul;Choi, Jong-Soo
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.10
    • /
    • pp.1817-1822
    • /
    • 2011
  • The fault current has been increasing due to expansive substation facilities for meeting the increase of demand. To limit increasing fault current in a power system, among methods the superconducting fault current limiter (SFCL) has been considered to be adopted in the power grid. However, in case of adopting SFCL in the power system, most of SFCLs need to solve problems such as recovery, cost. With efforts to solve those problems, the novel fault current limiting device which is called hybrid SFCL is developed. To apply the hybrid SFCL, it has to be needed to analyze application possibility and itself operation characteristics. In this paper, the fault current limiting and operation characteristics of hybrid SFCL with first half cycle the limiting operation in case of various resistances of superconducting element were analyzed through experiment.

Analysis on Current Limiting Characteristics of a Superconducting Fault Current Limiter (SFCL) with a Peak Currnt Limiting Function (피크전류제한 기능을 갖는 초전도한류기의 전류제한 특성분석)

  • Han, Tae-Hee;Lim, Sung-Hun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.24 no.1
    • /
    • pp.47-51
    • /
    • 2011
  • The superconducting fault current limiter (SFCL) with a peak current limiting function according to the initial fault current with the different amplitudes was suggested. The proposed SFCL, which consists of two limiting components, causes only the first superconducting element among two limiting components to be quenched in case that the initial fault current with the lower peak amplitude happens. On the other hand, the initial fault current with the higher peak amplitude makes both the superconducting elements of two limiting components to be quenched, which contributes to the peak current limiting function of the SFCL. To confirm the fault current limiting operation of the proposed SFCL, the short-circuit tests of the SFCL according to the fault angle were carried out and its effective fault current limiting operations could be discussed.

Current Limiting Characteristics of a SFCL with Two Triggered Current Limiting Levels in a Simulated Power Distribution System (모의배전계통에 두 트리거 전류레벨을 이용한 초전도한류기의 전류제한 특성 분석)

  • Ko, Seok-Cheol;Han, Tae-Hee
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.26 no.2
    • /
    • pp.134-139
    • /
    • 2013
  • When the accident occurred in power distribution system, it needs to control efficiently the fault current according to the fault angle and location. The flux-lock type superconducting fault current limiters (SFCL) can quickly limit when the short circuit accidents occurred and be made the resistance after the fault current. The flux-lock type SFCL has a single triggering element, detects and limits the fault current at the same time regardless of the size of the fault current. However, it has a disadvantage that broken the superconductor element. If the flux-lock type SFCL has separated structure of the triggering element and the limiting element, when large fault current occurs, it can reduce the burden of power and control fault current to adjust impedance. In this paper, this system is composed by triggering element and limiting element to analyze operation of limiting current. When the fault current occurs, we analyzed the limiting and operating current characteristics of the two triggering current level, and the compensation characteristics of bus-voltage sag according to the fault angle and location.

Study on Current Limiting Characteristics of a Flux-locktype SFCL using Series Connected Two Coils with Twice Triggering Operation

  • Han, Tae-Hee;Ko, Seok-Cheol;Lee, Byongjun;Lim, Sung-Hun
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.3
    • /
    • pp.777-781
    • /
    • 2014
  • The current limiting characteristics of the flux-lock type superconducting fault current limiter (SFCL) using series connected two coils with twice triggering operation, which consists of series connected two coils and two superconducting (SC) modules with the inserting resistance, was analyzed. The feature of the suggested SFCL is that it can limit the fault current by triggering either one SC module or two SC modules comprising the SFCL depending on the amplitude of the fault current. To verify the current limiting operation of the suggested SFCL, the short-circuits in the fault location with the different fault currents were tested and its useful operations were described through the analysis on the tested results.

Analysis on Fault Current Limiting Characteristics According to Peak Current Limiting Setting of a Flux-Lock Type SFCL with Peak Current Limiting Function (피크전류제한 설정에 따른 피크전류제한 기능을 갖는 자속구속형 초전도한류기의 고장전류제한 특성 분석)

  • Ko, Seok-Cheol
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.12
    • /
    • pp.68-73
    • /
    • 2012
  • In this paper, the fault current limiting characteristics of a flux-lock type superconducting fault current limiter (SFCL) with peak current limiting function were analyzed through its short-circuit tests. The setting condition for the peak current limiting operation was derived from its electrical equivalent circuit, which was dependent on the inductance ratio between the third coil and the first coil. Through the analysis on the short-circuit tests for the flux-lock type SFCLs with the different inductance ratio between the third coil and the first coil, the setting value for the peak current limiting operation of the flux-lock type SFCL with peak current limiting function could be confirmed to be adjusted with the variation of the inductance ratio between the third coil and the first coil.

Variations of Initial Fault Current Limiting Instant According to Fault Angles in the Flux-lock Type SFCL (자속 구속형 전류제한기의 사고각에 따른 초기 사고전류 제한 시점 변화분석)

  • Park, Chung-Ryul;Lim, Sung-Hun;Park, Hyoung-Min;Choi, Hyo-Sang;Han, Byoung-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.61-64
    • /
    • 2004
  • In this paper, we investigated the variations of initial fault current limiting instant according to fault angles in the flux-lock type SFCL. The flux-lock type SFCL consists of the coil 1 and the coil 2 that are wound in parallel each other through an iron core. The operation of the flux-lock type SFCL can be divided into the subtractive polarity winding and the additive polarity winding operations according to the winding directions between the coil 1 and coil 2. The subtractive polarity winding operation could be analyzed with three modes. On the other hand, the additive polarity winding operation could be analyzed with five modes. The variations of initial fault current limiting instant in two winding directions were dependent on the fault angles. It was confirmed from experiment that the fault current limiting instant was getting faster and the magnitude of fault current at the initial fault time was getting higher for higher fault angle.

  • PDF

Analysis on Operation Characteristics of Hybrid Superconductor Fault Current Limiter(SFCL) with First Half Cycle Non-Limiting Operation (반주기 이후 하이브리드 초전도 전류제한기의 동작 특성 분석)

  • You, Il-Kyoung;Kim, Jin-Seok;Kim, Myoung-Hoo;Lim, Sung-Hun;Kim, Jae-Chul;Choi, Jong-Soo
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.2
    • /
    • pp.239-244
    • /
    • 2011
  • Due to large demand, the increase of fault current has caused the capacity of power machines in power grid to increase. Among several countermeasures, the superconducting fault current limiter (SFCL) has been noticed as one of the promising countermeasures to solve these problems. However, in spite of excellent current limiting performances of the SFCL, the application of SFCL to power system has been delayed due to both the limited space for the SFCL's installation and its longer recovery time after the fault removal. In order to solve these problems, a hybrid type SFCL was developed. In this paper, we studied the operation characteristics of the hybrid SFCL with first half cycle non-limiting operation by modelling using PSCAD/EMTDC and experiment. It was shown through the simulation using PSCAD/EMTDC and the simulated experiment that the fault current limiting and the fast recovery operations of the hybrid SFCL with the first half cycle non-limiting operation were achieved.

Analysis on Fault Current Limiting Characteristics of Three-Phase Transformer Type SFCL using Double Quench According to Three-Phase Ground-Fault Types (이중퀜치를 이용한 삼상변압기형 초전도한류기의 삼상지락 고장 종류에 따른 고장전류 제한 특성 분석)

  • Shin-Won Lee;Tae-Hee Han;Sung-Hun Lim
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.36 no.6
    • /
    • pp.614-619
    • /
    • 2023
  • The fault current limiting characteristics of three-phase transformer type superconducting fault current limiter (SFCL), which consisted of three-phase primary and secondary windings wound on E-I iron core, one high-TC superconducting (HTSC) element connected with the secondary winding of one phase and another HTSC element connected in parallel with other two secondary windings of two phases, were analyzed. Unlike other three-phase transformer type SFCLs with three HTSC elements, three-phase transformer type SFCL using double quench has the merit to perform fault current limiting operation for three-phase ground faults with two HTSC elements. To verify its proper three-phase ground fault current limiting operation, three-phase ground faults such as single-line ground, double-line ground and triple-line ground faults were generated in three-phase simulated power system installed with three-phase transformer type SFCL using double quench. From analysis of its fault current limiting characteristics based on tested results, three-phase transformer type SFCL using double quench was shown to be effectively operated for all three-phase ground faults.

Analysis on Current Limiting Characteristics of a Fault-lock Type SFCL Applied into a Simulated Power System (모의전력계통에 적용된 자속구속형 초전도 전류제한기의 전류제한 특성 분석)

  • Han, Tae-Hee;Lim, Sung-Hun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.24 no.2
    • /
    • pp.141-146
    • /
    • 2011
  • When the current of the superconducting element exceeds its critical current by the fault occurrence, the quench of the high-$T_C$ superconducting fault current limiter (HTSC) comprising the flux-lock type superconducting fault current limiter (SFCL) occurs. Simultaneously, the magnetic flux in the iron core induces the voltage in each coil, which contributes to limit the fault current. In this paper, the fault current limiting characteristics of the flux-lock type SFCL as well as the load voltage sag suppressing characteristics according to the flux-lock type SFCL's winding direction were investigated. To confirm the fault current limiting and the voltage sag suppressing characteristics of the this SFCL, the short-circuit tests for the simulated power system with the flux-lock type SFCL were carried out. The flux-lock type SFCL designed with the additive polarity winding was shown to perform more effective fault current limiting and load voltage sag suppressing operations through the fast quench occurrence right after the fault occurs and the fast recovery operation after the fault removes than the flux-lock type SFCL designed with the subtractive polarity winding.