• Title/Summary/Keyword: FRP Hot Stick

Search Result 1, Processing Time 0.017 seconds

Design of Dielectric Detector for FRP Hot Stick in EHV Live line Maintenance

  • Chawporn, Talerngkiat;Sriratana, Witsarut;Trisuwannawat, Thanit
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 2005.06a
    • /
    • pp.2063-2066
    • /
    • 2005
  • This paper presents an approach to detect the dielectric condition of FRP Hot Stick in EHV high voltage cable whereas shutting down the power system is not necessary. The radio frequency generating method is adopted by transmitting radio wave into the Electrodes. This instrument is small, easy to use and also inexpensive. Furthermore, the impurity level of dirt on high voltage insulator (non-ceramic type) will be analyzed by using the methods based on IEEE Std.978-1984 at 105 kV.DC. /305 mm. and OSHA Regulation 1910.269 Part J - live line tools. The frequency at 10-20 MHz is applied to FRP Hot Stick via Electrode1 and from FRP Hot Stick surface to Electrode 2. After that the results will be evaluated by testing in each condition of FRP Hot Stick, such as dry surface, hot surface, foil winding and conductor inserting. Finally, the watt loss will be examined and compared with the loss from humidity and Carbon tracking. The important components of this system are radio frequency generating unit, frequency stabilizing unit, frequency amplifier, FRP Hot Stick frequency counter, processing unit, and display unit.

  • PDF