• Title/Summary/Keyword: FCL(Fault Current Limiter)

Search Result 76, Processing Time 0.028 seconds

The Study on Reducing Voltage Sags Due to The Distribution System Faults (배전계통 사고에 의한 전압저하 저감방법에 관한 연구)

  • 김진성;오용택;노대석
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.18 no.4
    • /
    • pp.88-96
    • /
    • 2004
  • The sag is phenomenon that magnitude of load voltage temporarily decreases because of power system fault. If a certain equipment in industrial process have any trouble result from sag, it can cause utility to be charged for enormous economics loss. Therefore it need to analyze the characteristic of sag and then mitigation method for sags in distribution system in oder to increase reliability. This paper suggests a sags mitigation method with concentrating on mitigation-device interface method, especially FCL that is Fault Current Limiter. And this effect has been done using PDCAD/EMTDC computer simulation analysis.

Simulation of the Three-phase DC Reactor Type Fault Current Limiter for the Short-circuit Test (삼상형 dc reactor형태 한류기의 단락회로실험을 위한 시뮬레이션)

  • Lee, Eung-Ro;Lee, Seung-Je;Lee, Chan-Joo;Ko, Tae-Kuk;Hyun, Ok-Bae
    • Proceedings of the KIEE Conference
    • /
    • 2001.07b
    • /
    • pp.717-719
    • /
    • 2001
  • This paper deals with simulation of the three-phase dc reactor type fault current limiter(FCL). This is a preliminary step to develop the FCL's faculties for an application to high voltage transmission line. A three-phase dc reactor type FCL consists of transformers, diodes, and a superconducting coil. By this simulation for the short-circuit test we can investigate the safety of FCL's elements. And, result of simulation will contribute parameter toward optimal design.

  • PDF

Experimental and Analytical Studies on the Characteristics of Fast Switch in Combinations of Various Superconducting Tapes (다양한 선재 조합에 따른 이종 초전도 스위치의 특성 실험 및 분석)

  • Lee, Ji-Ho;Kim, Young-Jae;Na, Jin-Bae;Choi, Suk-Jin;Jang, Jae-Young;Hwang, Young-Jin;Kim, Jin-Sub;Ko, Tae-Kuk
    • Progress in Superconductivity and Cryogenics
    • /
    • v.13 no.1
    • /
    • pp.31-35
    • /
    • 2011
  • A Hybrid Fault Current Limiter(FCL) which has more advantages in fast response and thermal characteristics than a simple resistive FCL had been proposed by our group. The Hybrid FCL consists of a resistive FCL for the magnitude of the first peak of fault current, and a fast switch for detecting fault current and generating the repulsive force within a cycle in fault situation. In ideal case, the impedance of the fast switch wound with two other kinds of HTS tape is negligibly zero in normal operation. But, during the fault situation, each HTS tape has different quench characteristics because of asymmetric current distribution. And this phenomenon causes effective flux and this flux opens the switch through the repulsive force applied to a metal plate of the fast switch. The magnitude of the repulsive force affects the switching characteristics of the fast switch. It should be large enough to raise the metal plate up. Otherwise the arc re-out break which are caused by not enough repulsive force to raise the metal plate up can cause unintended operation of the fast switch. In this paper, the numerical calculation of the repulsive force applied to the metal plate of the fast switch in various combinations of HTS tapes was performed by using the short-circuit test and finite element method.

Resistive Hts-Fcl Emtdc Modeling By Using Probabilistic Design Methodology

  • Yoon, Jae-Young;Kim, Jong-Yul;Lee, Seung-Ryul
    • KIEE International Transactions on Power Engineering
    • /
    • v.4A no.2
    • /
    • pp.69-72
    • /
    • 2004
  • Nowadays, one of the serious problems in the KEPCO system is a much higher fault current than the SCC (Short Circuit Capacity) of the circuit breaker. Since superconductivity technology has become more developed, the HTS-FCL (High Temperature Superconductor-Fault Current Limiter) may become an attractive alternative to solving the fault current problem. In order to achieve the best performance, the parameters of HTS-FCL should be designed optimally. Under this setting, this paper presents the optimal design method of parameters for resistive type HTS-FCL using the Monte Carlo technique.

Feasibility Study on the Application of 154kV HTS-FCL in Korean Power System (국내 실계통에서의 154kV 초전도한류기 계통적용 가능성 검토)

  • Lee Seung Ryul;Kim Jong-Yul;Choi Heung-Kwan;Yoon Jae Young
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.12
    • /
    • pp.661-669
    • /
    • 2004
  • As the load density of KEPCO system is higher, the fault current can be much higher than SCC(Short Circuit Capacity) of circuit breaker. Fault current exceeding the rating of circuit breaker is a very serious problem in high density load area, which can threaten the stability of whole power system. Even though there are several alternatives to reduce fault current, as the superconductivity technology has been developed, the HTS-FCL (High Temperature Superconductivity Fault Current Limiter) can be one of the attractive alternatives to solve the fault current problem. This study presents the application plication of 154kV HTS-FCL in Korean power system.

Quench Behaviors of Superconducting YBCO film for Fault Current Limiters applying Protective Current Transformer (변류기(p-CT)를 적용한 YBCO 초전도 저항형 한류기의 ?치 특성)

  • 박권배;이방욱;강종성;오일성;현옥배
    • Progress in Superconductivity
    • /
    • v.5 no.2
    • /
    • pp.128-131
    • /
    • 2004
  • The resistive superconducting fault current limiters (SFCLs) are very attractive devices for the electric power network. But they have some serious problems when the YBCO thin films were used for the current limiting materials due to the in homogeneities caused by manufacturing process. When the YBCO films have some inhomogeneities, simultaneous quenches are difficult to achieve when the fault current limiting units are connected in series for increasing operating voltage ratings. Magnetic field application is one of the prospective way of inducing simultaneous quenches far the series-connected resistive FCL components. Magnetic field was typically generated by the fault current thorough a coil, which is connected to components of the fault current limiter in series, leaving the problem, which provides significant inductance to the power line and suppresses critical current density of the superconducting components. In this article we investigated the possible application of the protective current transformer (p-CT), which is available current source to the magnetic coil. This system inductively coupled to the circuit, therefore, remarkably reducing impedance to the circuit. The current by the protective current transformer was directly fed to the coil, generating magnetic field large enough to reduce critical current density of the components. This successfully induced simultaneous quenches of the series-connected resistive FCL components.

  • PDF

Operational Characteristics of Flux-lock Type SFCL using Series Resonance

  • Lim, Sung-Hun;Han, Byoung-Sung;Choi, Hyo-Sang
    • Transactions on Electrical and Electronic Materials
    • /
    • v.6 no.4
    • /
    • pp.159-163
    • /
    • 2005
  • We analyzed the fault current limiting characteristics of a flux-lock type $high-T_c$ super­conducting fault current limiter (HTSC-FCL) using series resonance between capacitor for series resonance and magnetic field coil which was installed in coil 3. The capacitor for the series resonance in the flux-lock type HTSC-FCL was inserted in series with the magnetic field coil to apply enough magnetic field into HTSC element, which resulted in higher resistance of HTSC element. However, the impedance of the flux lock type HTSC-FCL has started to decrease since the current of coil 3 exceeded one of coil 2 after a fault accident. The decrease in the impedance of the FCL causes the line current to increase and, if continues, the capacitor for the series resonance to be destructed. To avoid this operation, the flux-lock type HTSC-FCL requires an additional device such as fault current interrupter or control circuit for magnetic field. From the experimental results, we investigated the parameter range where the operation as mentioned above for the designed flux-lock type HTSC-FCL using series resonance occurred.

Reduction of Electromagnetic Force in AC Distributed Winding of Fault Current Limiter under Short-Circuit Condition

  • Ghabeli, Asef;Yazdani-Asrami, Mohammad;Doroudi, Aref;Gholamian, S. Asghar
    • Journal of Magnetics
    • /
    • v.20 no.4
    • /
    • pp.400-404
    • /
    • 2015
  • Various kinds of winding arrangements can be used to enable fault current limiters (FCL) to tolerate higher forces without resulting in a substantial increase in construction and fabrication costs. In this paper, a distributed winding arrangement is investigated in terms of its effects on the short-circuit forces in a three-phase FCL. The force magnitudes of the AC supplied windings are calculated by employing a finite element-based model in the time stepping procedure. The leakage flux and radial and axial force magnitudes obtained from the simulation are compared to those obtained from a conventional winding arrangement. The comparison shows that the distributed winding arrangement significantly reduces the radial and, especially, the axial force magnitudes.

Operational Characteristics of Bride Type SFCL Using Switching Operation of Resistive Type HTSC Element (저항형 고온초전도 소자의 스위칭동작을 이용한 브리지타입 고온초전도 전류제한기의 동작 특성)

  • Lim, Sung-Hun;Park, Chung-Ryul;Lee, Jong-Hwa;Ko, Seok-Cheol;Park, Hyeong-Min;Choi, Hyo-Sang;Han, Byoung-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2004.04a
    • /
    • pp.83-85
    • /
    • 2004
  • We proposed the bridge type fault current limiter(FCL) using switching operation of high-Tc superconducting(HTSC) thin film. The proposed bridge type FCL consists of HTSC thin film, a diode bridge and a dc reactor. The controller for the operation of an interrupter is required in the conventional bridge type FCL to prevent the continuous increase of fault current after a fault happens. On the other hand, the proposed bridge type FCL can limit the fault current without the interrupter and the controller for its operation by the resistance generated when the gradually increased fault current exceeds HTSC thin film's critical current. We calculated the time when the gradually increased fault current started to be limited by the resistance generated in HTSC thin film after a fault happened and confirmed that it could be dependent on the amplitude of source voltage. The experimental results well agreed with the calculated ones from simulation.

  • PDF