• 제목/요약/키워드: Extinguishing concentration

검색결과 53건 처리시간 0.016초

할론대체물질의 새로운 불꽃소화농도 측정장치에 관한 연구 (A Study on the Measurement of Flame Extinguishing Concentration of Halon Alternatives by New Test Equipment)

  • 김재덕;임종성;이윤우;이윤용
    • 한국화재소방학회논문지
    • /
    • 제8권1호
    • /
    • pp.3-8
    • /
    • 1994
  • A new test system was established to measure the flame extinguishing concentration of Halon alternatives. The main characteristic of this system is to use the solid paraffin with a wick instead of liquid fuel, such as n-Heptane. Our results showed that the extinguishing concentration of compounds was lower than that of other existing data, but the trend was consistent with others. The flame extinguishing concentration of all tested compounds were not almost effected by gas flow velocity. The system produces good reliable data with a minimum error for measuring the flame extinguishing concentration. Therefore our new system can be utilized as a standard equipment to evaluate Halon alternatives.

  • PDF

가스계 혼합소화약제의 불꽃소화농도 (Flame Extinguishing Concentrations of Mixed Gaseous Agents)

  • 김재덕;임종성;이윤우;이윤용
    • 한국화재소방학회논문지
    • /
    • 제15권1호
    • /
    • pp.34-40
    • /
    • 2001
  • 가스계 혼합소화약제의 소화성능을 검토하기 위하여 Cup-burner test장치를 설치하고 이성분계 및 삼성분계 혼합물의 불꽃소화농도를 측정하였다. 시험대상 이성분계 혼합물은 이산화탄소/HFC-23, 이산화탄소/HCFC-22, 이산화탄소/HFC-227ea, 이산화탄소/HFC-125, 이산화탄소/FIC-13I1, Hexafluoropropylene/HFC-23이고 삼성분계 흔합물은 이산화탄소/HFC-237HFC-l34a, 이산화탄소/HFC-23/HFC-227ea, 이산화탄소/HFC-23/HFC-125이다. Cup-burner test장치에서 측정된 가스계 혼합물의 소화농도는 단일성분의 소화농도와 혼합물의 구성비로 이루어진 모델에 의해 잘 예측됨을 알 수 있었다. 특히 이 모델은 혼합물의 구성성분이 물리적 소화성능을 지닐 때 잘 적용되며 화학적 소화성능의 영향이 강해질수록 측정값과의 오차가 커진다.

  • PDF

단백포소화약제의 유동성 변화에 따른 소화 특성 (The Extinguishing Characteristics by Fluidity Variation of Protein Foam Extinguishing Agent)

  • 신창섭;정현정
    • 한국안전학회지
    • /
    • 제29권2호
    • /
    • pp.18-23
    • /
    • 2014
  • Foam extinguishing agent is widely used for extinguishing combustible liquid fires. Compared to other foam type extinguishing agents, protein foam has relatively low cost and low toxicity and produces stable foam blanket which is excellent in heat resistance and sealability, despite it has weak fluidity. Therefore the study investigated foaming characteristics followed by various factors affecting the fluidity of the protein foam extinguishing agent. The extinguishing characteristics differentiated by the changes in fluidity were also experimented. Foaming performance was compared by measuring the expansion ratio and the 25% drainage time. Moreover, the 25% drainage time and the extinguishing time was compared. The results showed that the 25% drainage time and the expansion ratio were increased as the pressure of nozzle and the concentration of hydrolyzed protein liquid enlarged. However the foaming and extinguishing performance were not improved when the condition exceeded certain level of pressure and concentration. The fastest fire extinguishing condition was the nozzle pressure 4bar with the 85wt.% of concentration of hydrolyzed protein liquid.

등유의 소화성능 평가를 위한 불활성 가스의 소화농도에 관한 연구 (A Study on the Extinction Concentration of Inert Gas for Extinction Performance Estimation of Kerosene)

  • 최재욱
    • 한국안전학회지
    • /
    • 제22권3호
    • /
    • pp.34-38
    • /
    • 2007
  • The experiment was done to investigate extinguishing concentrations of different inert gases of verying concentrations made in contact with Kerosene. The experimental results obtained are as follows; at a standard amount of air flow was 40L/min, the extinguishing concentration of Argon, Nitrogen, Carbon dioxide and Helium for Kerosene were 36.5%, 27.3%, 17.4%, 12.3%, respectively. And, according to these results, Helium of 12.3% showed the lowest extinguishing concentration.

불활성 가스계 혼합소화약제의 n-Heptane 불꽃소화농도 및 배가스 조성 (Flame Extinguishing Concentrations and Flue Gas Compositions of n-Heptane by Mixed Inert Gas Agents)

  • 김재덕;김영래;홍승태;이성철
    • 한국화재소방학회논문지
    • /
    • 제16권3호
    • /
    • pp.77-83
    • /
    • 2002
  • 질소, 아르곤, 이산화탄소와 같은 불활성가스 및 이들의 혼합물을 소화약제로 하여 n-Heptane을 연료로한 cup-burner test 장치에서 불꽃소화농도와 연소시 배가스의 조성을 측정하였다. 이성분 불활성가스계 혼합소화약제의 소화농도는 혼합물의 구성비를 이용한 모델에 의해 잘 예측됨을 알 수 있었다. 불활성 가스계 혼합 소화약제에 의한 소화작용에 있어서 혼합가스의 평균비중이 클수록 소화 성능이 우수하였다. 또한 밀폐된 공간의 구조가 소화에 영향을 미칠 수 있음을 확인하였다. 연소시 배가스 중 이산화탄소 조성은 사용하는 소화약제의 양이 증가할수록 감소하였다. 일산화질소 발생은 소화약제의 질소 함량과는 상관이 없으며 공기유량을 크게 하여 불꽃을 크게 했을 때 검출되었다.

제트확산화염에서의 불활성기체 소화농도 (Flame- Extinguishing Concentrations of Inert Gases in Jet Diffusion Flames)

  • 지정훈;이의주
    • 한국안전학회지
    • /
    • 제24권1호
    • /
    • pp.21-25
    • /
    • 2009
  • Extinguishing limits of laminar ethylene/oxygen flames in both normal and inverse co-flow jet burner have been determined experimentally and computationally. An inert gas($N_2$, Ar, $CO_2$) was added into the oxidizer to find the critical concentration and the effectiveness of the agents on flame extinction. The experimental results showed that the physical aspect of inert gases was main mechanism for flame blow-out as same as cup burner test, but the flow effect should be considered to determine the extinction concentration. The numerical prediction was performed with modified WSR model and the result was in good agreement with the measurements. The experimental and numerical methods could be used for the assessment of various flame suppression agents such as minimum extinguishing concentration.

전역방출방식 CO2 소화설비의 설계농도 및 유지시간 검증을 위한 직접방사실험에 관한 연구 (A Study on the Direct Discharge Test for Verifying Design Concentration and Soaking Time for CO2 Fire Extinguishing System of Total Flooding)

  • 이세명;문성웅;유상훈
    • 한국화재소방학회논문지
    • /
    • 제26권6호
    • /
    • pp.15-23
    • /
    • 2012
  • $CO_2$ 소화설비의 소화성능 시험방법에는 직접시험방법이 가장 좋지만, 고비용과 환경문제 그리고 시험절차의 어려움으로 간접시험방법을 사용하는 경우가 많다. 그러나 석유화학플랜트나 원자력발전소와 같은 국가 중요위험시설은 화재가 발생하면 대형피해가 발생할 수 있으므로 직접방사시험을 통해 소화성능을 검증할 필요가 있다. 본 연구는 국가 중요위험시설에 설치된 전역방출방식의 $CO_2$ 소화설비 중에서 표면화재 방호구역과 심부화재 방호구역을 각각 선정하여 $CO_2$ 소화설비의 소화성능을 검증해 보았다. 소화성능은 방호구역 내에 방사된 $CO_2$의 농도가 설계농도기준(NFSC 및 NFPA)에 만족해야 그 성능을 인정받을 수 있다. 여기서, 설계농도는 $CO_2$ 소화약제가 화염을 제어할 수 있는 소화농도에 여유율 20 %를 감안한 농도를 의미한다. 시험결과 표면화재와 심부화재 방호구역 모두 $CO_2$ 설계농도를 확보하고 있음을 확인하였고 심부화재의 경우에는 20분 이상 설계농도가 유지되었다. 본 연구를 통해 국가 중요위험시설에 대한 직접방사시험 방법 및 판정방법을 소개하였고 향후 이와 같은 국가 중요위험시설에는 직접방사시험을 통해 소화설비의 신뢰성을 검증해야 할 필요성을 제기하였다.

질소와 노벡 혼합가스를 이용한 청정소화약제의 소화성능에 관한 연구 (A Study on Clean Agent Fire Extinguishing Ability Using Nitrogen and Novec Mixtures Gas)

  • 임우섭;정종진;남동군;사공성호;김종원;최근주
    • 한국안전학회지
    • /
    • 제23권6호
    • /
    • pp.76-83
    • /
    • 2008
  • In the course of increasing in human and material damage caused by fire, it is an important research field to develop clean extinguishing agent which does no harm to global environment as well as has a good extinguishing efficiency. This research is a basic step to develop a new clean extinguishing agent. In order to get a satisfactory result, we tested fire extinguishing ability using nitrogen and Novec mixtures gas which are inert gas and new clean extinguishing agent. We used Cup Burner Test made by international standard ISO-14520 regulations of gaseous extinguishing agent ability test, and the fuels used in the test are n-heptane, methanol, ethanol, iso-propanol and 1-butanol. The experimental results of flame extinguishing concentration are n-heptane 6.54%, methanol 8.47%, ethanol 6.98%, isopropanol 6.10% and butanol 6.54% by pure Novec agent. So the finding is that a new clean agent, Novec has an efficient extinguishing ability in a state of gas. Also, in a test as to mixtures gas of nitrogen and Novec, it has a good result for minimum oxygen concentration is under 16%.

컵버너시험에서 소화기준에 따른 불활성기체의 소화농도에 대한 정량적 차이 (Quantitative Difference in the Extinguishing Concentration of Inert Gases with Fire Suppression Criteria in a Cup Burner Test)

  • 조재호;황철홍
    • 한국화재소방학회논문지
    • /
    • 제28권3호
    • /
    • pp.34-42
    • /
    • 2014
  • 본 연구에서는 $CH_4$$C_3H_8$ 연료의 컵버너 비예혼합화염에서 Swing, Rotation, Lifted 및 Blow-out과 같은 화염 불안정성을 발생시키는 불활성기체($N_2$, Ar, $CO_2$ 및 He)의 농도를 측정하였으며, 소화기준(즉, 화염날림 또는 화염불안정성 개시)에 따른 소화농도의 정량적 차이를 검토하였다. 소화농도의 차이는 부상화염의 발생 그리고 낮은 소화성능의 불활성기체일수록 증가됨을 확인하였다. 소화기준에 따른 소화농도의 최대 차이는 $C_3H_8$-air 비예혼합화염의 최대 연료유속의 조건(1.3 cm/s)에서 약 35%이다. 또한 화염 불안정성의 개시를 기준으로 측정된 소화농도는 정확한 그리고 경제적 설계 농도의 관점에서 유용한 정보를 제공할 것으로 기대된다.

산업용 질소발생기에 대한 청정소화설비로의 적용가능성에 관한 연구 (A Study on the Possibility of Application as a Natural Extinguishing System for $N_2$ Generator)

  • 서병택;장영근
    • 한국화재소방학회논문지
    • /
    • 제24권2호
    • /
    • pp.139-144
    • /
    • 2010
  • 본 연구에서는 산업용으로 일반적으로 사용하고 있는 질소발생기를 사용하여 할론 계열의 소화약제를 대체할 청정소화설비로 적용할 수 있는지에 대한 소화성능 실험을 간단히 수행하였다. 산업용 질소발생기의 소화성능을 분석하기 위하여 간단한 방호구역을 제작하여 실제 질소발생기에서 발생하는 질소가스를방사하면서 방호구역 내의 산소농도 변화를 실험적으로 파악하였다. 실험결과, 현재 많이 사용하고 있는 질소발생기로 방호구역 $100m^3$에 대하여 질소가스를 $5m^3$/min로 방사하면 3분 이내에 방호구역 내의 산소 농도를 15% 이내로 낮추어 질식소화가 충분히 가능하다.