• Title/Summary/Keyword: Evaporation heat transfer

Search Result 274, Processing Time 0.025 seconds

A study on the characteristics of heat transfer and pressure drop in plate type evaporator with U-turn for automotive air conditioner (유턴 흐름을 갖는 차량공조용 플레이트형 증발기의 전열특성에 관한 연구)

  • 강정길;김종수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.4
    • /
    • pp.472-483
    • /
    • 1999
  • The evaporation heat transfer and pressure drop characteristics for HFC-l34a in flat plate type heat exchangers with enhanced beads were experimentally investigated. Three plate type evaporators with different geometric condition of U-turn area were tested. Mass fluxes were tested over the range of 83kg/$m^2$s to 166kg/$m^2$s, and heat fluxes were varied from 4㎾/$m^2$ to 12㎾/$m^2$. Evaporation temperature was 5$^{\circ}C$ with inlet qualities of 0.1 to 1.0. There was no notable difference in the heat transfer coefficient by geometric variation of U-turn area, but the third plate with cross-ribbed channel at U-turn area was better than others in the evaluation using volume goodness factor comparison. Also, the mixtures of HFC-l34a and PAG oil was tested to determine oil effects on heat transfer and pressure drop. As oil concentration was increased, heat transfer coefficient was increased by 22~48% up to the 3wt.%, but decreased by 14~22% at the 4wt.%. The pressure drop was increased by the maximum of 100% as oil concentration was increased.

  • PDF

An experimental study on heat transfer characteristics in a vertical micro-fin tube during evaporation process of carbon dioxide flowing upward (이산화탄소의 마이크로 핀관 내 상향유동 증발열전달 특성에 관한 연구)

  • Kim, Yong-Jin;Cho, Jin-Min;Kim, Min-Soo
    • Proceedings of the SAREK Conference
    • /
    • 2007.11a
    • /
    • pp.247-251
    • /
    • 2007
  • Because of the ozone layer depletion and global warming, new alternative refrigerants are being developed. In this study, evaporation heat transfer characteristics of carbon dioxide flowing upward in a vertical micro-fin tube have been investigated by experiment. Before a test section, a pre-heater is installed to adjust the inlet quality of the refrigerant to a desired value. The micro-fin tube with outer diameter of 5 mm and length of 1.44 m was selected as the test section. The test was conducted at mass fluxes of 318 to $530\;kg/m^2s$, saturation temperature of -5 to $5^{\circ}C$, and heat fluxes of 15 to $30\;kW/m^2$. As the vapor quality increases, the heat transfer coefficients of carbon dioxide are increased, and the heat transfer coefficients increase when the heat fluxes and saturation temperatures increase, and there was not much of influence of mass flux on the heat transfer coefficients.

  • PDF

Evaporation Heat Transfer Characteristics of CO2 R-22 and R-134a in a Horizontal Smooth Tube (수평원관 내 CO2 R-22 및 R-134a의 증발열전달 특성에 관한 실험적 연구)

  • Yun, Rin;Hwang, Jun-Hyeon;Choi, Young-Don;Kim, Yong-Chan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.26 no.7
    • /
    • pp.911-918
    • /
    • 2002
  • Evaporation heat transfer coefficients of carbon dioxide($CO_2$), R-22, and R-134a in a horizontal smooth tube were measured and analyzed as a function of heat flux, mass flux, and evaporating temperature. The experiments were carried out by varying heat flux from 10 to 20 $kW/m^2$, mass flux from 170 to 340 $kg/m^2s$, and saturation temperatures of 5 and $10^{\circ}C$. It was found that the heat transfer coefficient of $CO_2$ decreased with a rise of quality due to an earlier liquid-film dryout as compared to R-22 and R-134a. Averaged heat transfer coefficients of $CO_2$ were 22-63% higher than those of R-22 and R-134a at all test conditions. The effects of mass flux and heat flux on averaged heat transfer coefficients were much greater in $CO_2$ than in R-22 and R-134a. When comparing $CO_2$ test results with the correlations in the literature, the existing models yielded large deviations at medium and high qualities. Therefore, a generalized correlation for $CO_2$evaporation heat transfer needs to be developed by including the effects of dryout phenomenon.

A Study on the Evaporation Characteristics of Water or Nanofluid Droplets on a Heated Surface (물과 나노유체 액적의 고온 벽면에서의 증발 특성에 관한 연구)

  • Kim, J.H.;Lee, K.J.;Jung, S.W.;Kang, B.S.
    • Journal of ILASS-Korea
    • /
    • v.21 no.4
    • /
    • pp.177-183
    • /
    • 2016
  • In this study, the evaporation characteristics of water or nanofluid droplets on a heated surface was investigated by visualization of the evaporation process and evaluation of the heat transfer coefficient using the droplet temperature measured. The evaporation characteristics was compared between water and nanofluid droplets and the effects of the mass ratio of nanofluid and the inclination of heated surface were analyzed. The heat transfer rate of nanofluid droplet was higher than that of water droplet. The heat transfer coefficient was increased with the increase of the mass ratio of nanofluid. The effect of the inclination of heated surface was much higher than that of fluid type used, which indicates that the inclination of heated surface should be considered as one of influential parameters in the spray cooling process.

Analysis of Evaporative Heat Transfer in a Porous Layer by Capillary Model (모세관 모델에 의한 다공층내의 증발 열전달 해석)

  • 김홍제;이진호
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.16 no.2
    • /
    • pp.391-399
    • /
    • 1992
  • The analysis of the evaporative heat transfer in the inclined porous layer (0.deg.<.theta.<90.deg.) is made by using capillary model. The length of the evaporation zone is obtained numerically by integrating the differential equation using a Runge-Kutta algorithm. As a result, the length of the evaporation zone is inverse proportional to the dimensionless number, E(=Re*.phi./cos.theta.) representing the evaporation intensity, and the relationship of these parameters shows linear in the log graph.

Experimental Studies on the Evaporative Heat Transfer Characteristics of CO2/Propane Refrigerant Mixtures in Horizontal Smooth and Micro-fin Tubes (이산화탄소/프로판 혼합냉매의 수평평활관 및 마이크로 핀관에서의 증발열전달에 관한 실험적 연구)

  • Cho, Jin-Min;Kim, Yong-Jin;Kim, Min-Soo
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.32 no.4
    • /
    • pp.290-299
    • /
    • 2008
  • Evaporation heat transfer characteristics of $CO_2$/propane mixtures in horizontal smooth and micro-fin tubes have been investigated by experiment. The experiments were carried out for several test conditions of mass fluxes, heat fluxes, compositions of $CO_2$/propane refrigerant mixtures and tube geometries. Direct heating method was used for supplying heat to the refrigerant where the test tube was uniformly heated by electric current which was applied to the tube wall. Heat transfer coefficient data during evaporation process of $CO_2$/propane mixtures were measured for 5 m long smooth and micro-fin tubes with outer diameters of 5 mm, respectively. The tests were conducted at mass fluxes of 318 to 997 $kg/m^2s$, heat fluxes of 6 to 20 $kW/m^2$ and for several mixture compositions (100/0, 75/25, 50/50, 25/75, 100/0 by wt% of $CO_2$/propane). The differences of heat transfer characteristics between smooth and micro-fin tubes for various compositions of $CO_2$/propane refrigerant mixtures and the effect of mass flux, and heat flux on enhancement factor (EF) and penalty factor (PF) were presented.

Heat Transfer Analysis of Concrete Members Considering Evaporation Heat under High Temperature (고온 하에서 기화열을 고려한 철근콘크리트 부재의 온도해석)

  • Lee, Taegyu
    • KSCE Journal of Civil and Environmental Engineering Research
    • /
    • v.29 no.4A
    • /
    • pp.355-363
    • /
    • 2009
  • When water inside the concrete member evaporates by high temperature, the evaporation heat which absorbs surrounding temperature occurs. The rate of increment of the internal temperature in concrete is reduced due to the evaporation heat in spite of continuously increasing external temperature. In this paper, the prediction method of internal temperature of concrete members considering the evaporation heat under the high temperature is presented. Finite element method is employed to facilitate thermal analysis for any position of member. And the thermal characteristics models of high strength concrete affected by high temperature are proposed. To demonstrate the validity of this numerical procedure, the prediction by the proposed algorithm is compared with the test results of other researchers. The proposed algorithm shows a good agreement with the experimental results including the phenomenon that temperature is lost by the evaporation heat.

Evaporation Heat Transfer and Pressure Drop Characteristics of R-134a in the Oblong Shell and Plate Heat Exchanger

  • Park, Jae-Hong;Kim, Young-Soo
    • Journal of Mechanical Science and Technology
    • /
    • v.18 no.12
    • /
    • pp.2284-2293
    • /
    • 2004
  • The evaporation heat transfer coefficient h$\_$r/ and frictional pressure drop Δp$\_$f/ of refrigerant R-134a flowing in the oblong shell and plate heat exchanger were investigated experimentally in this study. Four vertical counterflow channels were formed in the oblong shell and plate heat exchanger by four plates of geometry with a corrugated sinusoid shape of a 45 chevron angle. Upflow of refrigerant R-134a boils in two channels receiving heat from downflow of hot water in other channels. The effects of the refrigerant mass flux, average heat flux, refrigerant saturation temperature and vapor quality of R-134a were explored in detail. Similar to the case of a plate heat exchanger, even at a very low Reynolds number, the flow in the oblong shell and plate heat exchanger remains turbulent. The results indicate that the evaporation heat transfer coefficient h$\_$r/ and pressure drop Δp$\_$f/ increase with the vapor quality. A rise in the refrigerant mass flux causes an increase in the h$\_$r/ and Δp$\_$f/. But the effect of the average heat flux does not show significant effect on the h$\_$r/ and Δp$\_$f/. Finally, at a higher saturation temperature, both the h$\_$r/ and Δp$\_$f/ are found to be lower. The empirical correlations are also provided for the measured heat transfer coefficient and pressure drop in terms of the Nusselt number and friction factor.

Thin Film Evaporation on Horizontal Plain Tubes (수평 평활관 외측의 액막 증발에 관한 연구)

  • Kim, J.O.;Kim, N.H.;Choi, K.K.
    • Solar Energy
    • /
    • v.18 no.4
    • /
    • pp.49-57
    • /
    • 1998
  • In this study, thin film evaporation of water on a horizontal plain tube is experimentally investigated. At a high heat flux, boiling of water is noticed inside the film. Once boiling occurs, evaporation heat transfer coefficient increases as the heat flux increases. In the non-boiling region, however, the heat transfer coefficient remains uniform irrespective of the heat flux. In this region, the heat transfer coefficient increases as the film flow rate increases. Comparison with existing correlations is also provided.

  • PDF

Heat Transfer Enhancement Characteristics for Falling-Film Evaporation on Horizontal Enhanced Tubes with Aqueous LiBr Solution (LiBr 수용액을 이용한 수평관 유하액막 증발의 촉진관 전열향상 특성)

  • Kim, Dong Kwan;Kim, Moo Hwan
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.22 no.9
    • /
    • pp.1267-1276
    • /
    • 1998
  • Falling-film evaporation experiments with aqueous lithium bromide (LiBr) solution were performed to investigate the heat transfer characteristics of enhanced copper tubes. Enhanced tubes (a knurled tube, a spirally grooved tube, and a tube coated with $20{\mu}m$ aluminum particles) and a bare tube were selected as test specimens. Averaged evaporation fluxes of water were obtained from horizontal tubes with various film Reynolds numbers, system pressures, LiBr concentrations and degrees of wall superheat. The enhanced performance of steam generation was compared between tubes with varying parameters. The knurled tube geometry showed the most excellent performance among the tubes tested. The specified enhanced tubes were more useful for generating steam on a low grade heat source such as waste heat.