• Title/Summary/Keyword: Evacuation floor

Search Result 96, Processing Time 0.026 seconds

Optimization Method for Patient Placement by Floor in Elderly Care Hospital for Evacuation Safety (피난안전성을 위한 요양병원의 층별 환자배치에 대한 최적화방안)

  • Lee, Hong-Sang;Kong, Ha-Sung
    • Journal of the Korea Safety Management & Science
    • /
    • v.22 no.3
    • /
    • pp.43-51
    • /
    • 2020
  • This study analyzed the appropriate placement method by floor for evacuating all occupants during the nighttime through evacuation simulation. The analysis results are as follows. First, when non-self evacuating patients were placed on the first floor, 266 patients and 6 workers were found to be evacuated after 460 seconds. This result shows that it is meaningful to place non-self evacuating patients on the lower floor with a time that is faster than 540 seconds, which is an evaluation criterion set using life Safety standards for human. This result is a time faster than the evaluation criteria of 540 seconds, which is set using the life safety standards, and it can be confirmed that it is meaningful to place non-self evacuating patients on the lower floor. Next, as a result of placing non-self evacuating patients from the first floor to the fourth floor, it was found that evacuation of all occupants required 460 seconds for the first floor, 834 seconds for the second floor, 1,508 seconds for the third floor, and 1,915 seconds for the fourth floor. These results indicate that the placement of non-self evacuating patients on the rest of the floors, except for the first floor, can lead to dangerous results in excess of 540 seconds, which is a flashover time. As a result, it is necessary to place non-self evacuating patients on a lower floor for safe evacuation. The study has limitations except for comparative analysis of changes in evacuation time due to changes in the number of workers at eldery care hospitals and situations in which fire-fighting facilities such as sprinkler facilities operated. It is necessary to study the evacuation time linked to the operation of the fire-fighting facilities and the evacuation time according to the change in the number of workers in the future.

Effective Evacuation based on Elementary School's Floor Layout (초등학교 층별 구성과 비상시 대피효율성의 관계)

  • Kwun, Joon-Bum;Kim, Duk-Su;Kim, Khil-Chae
    • Journal of the Korean Institute of Educational Facilities
    • /
    • v.23 no.3
    • /
    • pp.3-10
    • /
    • 2016
  • This study compared evacuation effectiveness between the conventional school floor plan and a suggested hypothetical floor plan that was generated by a mathematical model that is commonly applied in the field of industrial engineering. Recent school buildings became much more complicated in floor planning due to the new educational system and modern curriculum than the old days. Nevertheless, architect's approach to floor composition in terms of fire emergency evacuation planning, still has no relation to optimized effective but relies more on a conventional school planning. Therefore, since elementary school buildings are much more likely to be exposed to any fire related events than middle school or high-school, emergency exit effectiveness based on spatial composition has to be seriously evaluated with a scientific method. The algorithm, which acquires the number of persons in each spatial type (node) per floor and the minimum physical distance between spatial types (arc), can propose the most optimized spatial compositing per floor regarding emergency evacuation event. Consequently, this study evaluated elementary school's fire exit effectiveness with the scientific tool and suggested the most reliable spatial composition per floor regarding possibile emergency evacuation event.

A Study on the Relationship Analysis Model between Visibility and Evacuation Time by User's Movement in the Lower Floor of General Hospital (종합병원 저층부에서의 이용자 이동에 따른 가시성과 피난 시간의 상관관계 분석 모델에 관한 연구)

  • Jung, Gi Hyun;Kweon, Jihoon
    • Journal of the Regional Association of Architectural Institute of Korea
    • /
    • v.21 no.3
    • /
    • pp.11-21
    • /
    • 2019
  • The purpose of this study was to present an analysis model for finding the correlation between visibility and evacuation time as users move in the outpatient department of the general hospital. The spatial scope of the study was limited to the first floor and second floor which are used for the outpatient department. Traffic density in outpatient departments was surveyed on site. Based on the surveyed traffic density, the evacuation simulation model was established for calculating the escape route and evacuation time for an individual user. The traffic density of the outpatient department as per the evacuation time was also calculated. With using evacuation simulations, the flow of evacuees was calculated through the density of traffic over the time of evacuation. Visibility data were set in the simulation model for users' escape routes. A correlation analysis between the product of evacuation flow measure and visibility measure of the evacuation population and evacuation time was performed. The analysis result showed negative correlation within a specific distance range. This study presented an analysis model showing that the evacuation condition considering spatial visibility in the outpatient department of general hospital visibility was negatively related to the analyzed evacuation time at the design stage.

Evacuation Efficiency on School Auditorium Floor Layout (학교강당의 평면적 특징에 따른 대피효율에 관한 연구)

  • Kwun, Joon-Bum;Kim, Duk-Soo;Kim, Khil-Chae
    • Journal of the Korean Institute of Educational Facilities
    • /
    • v.24 no.2
    • /
    • pp.3-10
    • /
    • 2017
  • This study compared evacuation effectiveness between the conventional school auditorium plan and a suggested hypothetical plan that was generated by a mathematical model, which is commonly applied in the field of industrial engineering. Recent school buildings became much more complicated in floor planning due to new social needs and modern curriculum than the old days. Nevertheless, architect's approach to floor composition in terms of fire emergency evacuation planning, still has no relation to optimized effective but relies more on an conventional school planning. Therefore, since school buildings are much more likely to be exposed to any fire related events than any other building types, emergency exit effectiveness based on spatial composition has to be seriously evaluated with a scientific method. The algorithm, which acquires the number of persons in each spatial type(node) per floor and the minimum physical distance between spatial types(arc), can propose the most optimized spatial layout per floor regarding emergency evacuation event. Consequently, this study evaluated school's fire exit effectiveness focusing on auditorium area with the scientific tool and suggested the most reliable spatial layout regarding possibile emergency evacuation event.

Analysis of the Evacuation Safety of Indoor Stadiums with Automatic Opening/Closing Exit Installations (출입문용 자동개폐장치를 설치한 실내체육관의 피난안전성 분석)

  • An, Jae-Chun;Kong, Ha-Sung
    • Journal of the Korea Safety Management & Science
    • /
    • v.22 no.3
    • /
    • pp.15-21
    • /
    • 2020
  • This study analyzed the evacuation time in indoor stadiums when exits that automatically open/close when the fire sensor is triggered are installed as a means to improve the problem of closing certain exits. Firstly, when spectators on the 2nd floor stands exit through the 1st floor exits, the RSET of all inhabitants was 529.8 seconds when the automatic opening/closing exits are broken and employees are not present. Secondly, when spectators on the 2nd floor stands exit through the 1st floor exits, the RSET of all inhabitants was 445 seconds when the automatic opening/closing exits with 750mm width are working but employees are not present. Lastly, when spectators on the 2nd floor stands exit through the 1st floor exits, the RSET of all spectators was 337 seconds when the automatic opening/closing exits with 1,500mm width are working and employees are present. As a result, it was revealed that the evacuation time is shortened when the automatic opening/closing exits are working. Additional comparative studies with actual simulations of people evacuating an indoor stadium and firefighting simulations considering smoke flow are necessary.

A study on the planning for fire evacuation of the high-rise buildings using the fire evacuation simulator (화재 대피 시뮬레이터를 이용한 초대형 고층 건물의 화재 대피 계획에 관한 연구)

  • Park, Yang-Soo;Lim, Dong-Jin
    • Proceedings of the KIEE Conference
    • /
    • 2000.11d
    • /
    • pp.618-620
    • /
    • 2000
  • In case of fire in the high-rise buildings, the appropriate and safe evacuation plans for the building residents are very important to minimize the number of casualties. Since the evacuation time usually depends on the floor plans of the buildings, the evacuation plans should be considered while the architectural design is done. Conventionally, the calculation of the evacuation time in the case of fire breakout is based on the approximate mathematical equations which are prone to error. In this study, the simulator model is developed to help the architectural designers to access the more accurate evacuation time and find out the floor plans which offers the most safe evacuation plans for the residents in case of fire.

  • PDF

A study on the simulator development for fire evacuation of the high-rise buildings (초고층 건물의 화재 대피 시뮬레이터 개발에 관한 연구)

  • 박양수;임동진
    • 제어로봇시스템학회:학술대회논문집
    • /
    • 2000.10a
    • /
    • pp.308-308
    • /
    • 2000
  • In case of fire in the high-rise buildings, the appropriate and safe evacuation plans for the building residents are very important to minimize the number of casualties. Since the evacuation time usually depends on the floor plans of the buildings, the evacuation plans should be considered while the architectural design is done. Conventionally, the calculation of the evacuation time in the case of fire breakout is based on the approximate mathematical equations which are prone to error In this study, the simulator model is developed to help the architectural designers to access the more accurate evacuation time and find out the floor plans which offers the most safe evacuation plans for the residents in case of fire.

  • PDF

A Study on the Estimation of the Number of Suitable Entrances for Emergency Evacuation Facilities through Modeling and Simulation (M&S를 통한 비상대피시설의 적정 출입구 개수 산정에 관한 연구)

  • Lee, Jeong-Moon;Roh, Jeong-Heon;Park, Young-Jun
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2019.05a
    • /
    • pp.129-130
    • /
    • 2019
  • In this research, we determine the proper number of entrances in the evacuation facilities for civil and military personnel. The current standards on the emergency evacuation facility only sets the number of possible evacuees and the according architectural floor area since the evacuation have been completed. However, other than static standards such as the floor area, there is needs to consider the dynamic standards along with allowable evacuation time such as the number of entrance, staircases and so on. Therefore, we need to consider the number of entrances and their location in order to account for the allowed evacuation time of particular number of people in a set area. The outcome could be contributed to the standards which should contain the dynamic conditions associated with evacuation.

  • PDF

A study on the simulator development for fire evacuation of office buildings (사무용 건물의 화재 대피 시뮬레이터 개발에 관한 연구)

  • Park, Yang-Soo;Lim, Dong-Jin
    • Proceedings of the KIEE Conference
    • /
    • 1999.11c
    • /
    • pp.543-545
    • /
    • 1999
  • In case of fire in the high-rise buildings, the appropriate and safe evacuation plans for the building residents are very important to minimize the number of casualties. Since the evacuation time usually depends on the floor plans of the buildings, the evacuation plans should be considered while the architectural design is done. Conventionally, the calculation of the evacuation time in the case of fire breakout is based on the approximate mathematical equations which are prone to error. In this study, the simulator model is developed to help the architectural designers to access the more accurate evacuation time and find out the floor plans which offers the most safe evacuation plans for the residents in case of fire.

  • PDF

A Basic Study on the Evacuation Plans of Buildings (건축물의 피난계획에 관한 기초적 연구)

  • 고치원
    • Fire Science and Engineering
    • /
    • v.14 no.4
    • /
    • pp.1-6
    • /
    • 2000
  • With the "Fire Protection Building Plan" of the Building Center of Japan as a sample, actual evacuation plans used for large scaled and multi-storied buildings are analyzed. Sufficient number of samples were classified into 6 categories. For room evacuation, time to pass through the exit was the most critical point for larger spaces and movement time in the room was the key for smaller evacuation object zone and less number of evacuees. Seen from the location of fire breakout point, it was witnessed that the numbers of crowding at the exits of the fire escape staircase are serious for floor level evacuation. For vertical traffic line, it was actually proved that time to fire escaping floor is problem of higher buildings. It was also proved that special evacuation methods are in practical use in many buildings in japan.

  • PDF